background image

6

English

Refer to Table 1 for tightening torque.

Table 1

CAUTION

Overtightening may damage the flare and cause leaks.

Be careful for oil not to adhere to any portions other 

than a flare part. If oil adhere to resin parts etc., there is 

a possibility of damaging by deterioration.

Refer to Table 2 if no torque wrench is available.
Using a wrench to tighten flare nuts causes the tightening
torque to suddenly grow much tighter after a certain point.
From there, tighten the nut further by the appropriate angle
listed in Table 2.

(2) After the work is finished, make sure to check that

there is no gas leak.

(3) After checking for gas leaks, be sure to insulate the

pipe connections referring to Fig. 8.

Insulate using the insulation for fitting (3) (4) included with 
the liquid and gas pipes. Besides, make sure the insula-
tion for fitting (3) (4) on the liquid and gas piping has its
seams facing up.
(Tighten both edges with clamp (9).)

For the gas piping, wrap the mid. sealing pad (6) over the 
insulation for fitting (4) (flare nut part).

CAUTION

Be sure to insulate any field piping all the way to the piping 

connection inside the unit. Any exposed piping may cause 

condensation or burns if touched.

When brazing the refrigerant piping, perform nitrogen
replacement first, or perform the brazing (CAUTION 2) while
feeding nitrogen into the refrigerant piping (CAUTION 1), and 
finally connect the indoor unit using the flare connections.

(Refer to Fig. 9)

CAUTION

1. When brazing a pipe while feeding nitrogen inside the

pipe, make sure to set the nitrogen pressure to 0.02 MPa
(0.2 kg/cm

2

) using the pressure reducing valve.  (This

pressure is such that breeze is blown to your cheek.)

2. Do not use a flux when brazing the refrigerant pipe joints.

Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) which does not require flux.
(Using a flux containing chlorine may cause the piping to
corrode.  Using a welding flux containing fluorine may
cause the refrigerant lubricant to deteriorate, and affect
adversely the refrigerant piping system.)

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install the 
unit without a torque wrench, you may follow the installation 
method mentioned below.

After the work is finished, make sure to check that there is 
no gas leak.

When you keep on tightening the flare nut with a spanner, there 
is a point where the tightening torque suddenly increases. From 
that position, further tighten the flare nut the angle shown below:
Table 2

Pipe 

size

Tightening torque

Flare dimen-

sion A (mm)

Flare shape

Ø6.4

15 – 17 N·m

8.7 – 9.1

 

Ø9.5

33 – 39 N·m

12.8 – 13.2

Ø12.7

50 – 60 N·m

16.2 – 16.6

 Ø15.9

63 – 75 N·m

19.3 – 19.7

A

45

0

2

0

R0.4-0.8

90

0

2

0

Main unit

Wrap over the top of the 
flare nut connection.

(accessory)

(accessory)

Insulation for fitting (3)
(accessory)

Liquid pipe

Fig. 8

Main unit

Attach to base

Piping insulation material 
(main unit)

Piping insulation material
(Field supply)

Turn seams up

Flare nut connection

Clamp (9) (accessory)

Piping insulation material
(Field supply)

Clamp (9)
(accessory)

Liquid Piping Insulation Procedure

Gas Piping Insulation Procedure

Insulation for fitting (4)

Mid. sealing pad (6)

Turn seams up

Flare nut connection

Attach to base

Piping insulation 
material (main unit)

Gas pipe

Pipe size

Further tightening angle

Recommended arm 
length of tool

Ø6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

Ø9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

Ø2.7 (1/2”)

30 to 60 degrees

Approx. 250mm

Ø15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

Fig. 9

Nitrogen

Nitrogen

Hands 
valve

Pressure-reducing valve

Taping

Part to be brazed

Refrigerant piping

4PEN325876-1F.book  Page 6  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ20A2VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A2VEB FXDQ20A2VEB FXDQ25A2VEB FXDQ32A2VEB FXDQ40A2VEB FXDQ50A2VEB FXDQ63A2VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM...

Page 2: ...por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acord...

Page 3: ...lation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified pers...

Page 4: ...the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an...

Page 5: ...ould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If ther...

Page 6: ...prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anch...

Page 7: ...a ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the t...

Page 8: ...Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluo...

Page 9: ...Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipi...

Page 10: ...on area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use a...

Page 11: ...o not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of p...

Page 12: ...ower sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring...

Page 13: ...stem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 1...

Page 14: ...achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to th...

Page 15: ...n man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote...

Page 16: ...GHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THE...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM...

Page 18: ...4P489744 1 2017 04 Copyright 2012 Daikin 4P489744 1 book Page 1 Thursday April 27 2017 4 42 PM...

Reviews: