VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY PRECAUTIONS................................................ 1
2. BEFORE INSTALLATION................................................ 2
3. SELECTING INSTALLATION SITE ................................. 3
4. PREPARATIONS BEFORE INSTALLATION ................... 4
5. INDOOR UNIT INSTALLATION....................................... 5
6. REFRIGERANT PIPING WORK ..................................... 5
7. DRAIN PIPING WORK .................................................... 7
8. INSTALLING THE DUCT................................................. 8
9. ELECTRIC WIRING WORK ............................................ 9

10. WIRING EXAMPLE ....................................................... 10

11. FIELD SETTING AND TEST RUN ................................ 13

12. WIRING DIAGRAM

 

.......................................................

 

1

4

The original instructions are written in English. All other lan-
guages are translations of the original instructions.

1. SAFETY PRECAUTIONS

Please read these “SAFETY PRECAUTIONS” carefully before 
installing air conditioning equipment and be sure to install it cor-
rectly.
After completing installation, conduct a trial operation to check 
for faults and explain to the customer how to operate the air con-
ditioner and take care of it with the aid of the operation manual. 
Ask the customer to store the installation manual along with the 
operation manual for future reference.

This air conditioner comes under the term “appliances not 
accessible to the general public”.

Meaning of WARNING and CAUTION notices

WARNING

............. Failure to follow these instructions 

properly may result in personal injury 

or loss of life. 

CAUTION

.............. Failure to observe these instructions 

properly may result in property dam-
age or personal injury, which may be 
serious depending on the circum-
stances.

WARNING

Ask your dealer or qualified personnel to carry out installation 
work.
Do not attempt to install the air conditioner yourself. Improper
installation may result in water leakage, electric shocks or
fire.

Install the air conditioner in accordance with the instructions
in this installation manual.
Improper installation may result in water leakage, electric
shocks or fire.

Consult your local dealer regarding what to do in case of
refrigerant leakage. When the air conditioner is to be
installed in a small room, it is necessary to take proper mea-
sures so that the amount of any leaked refrigerant does not
exceed the concentration limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen deple-
tion.

Be sure to use only the specified accessories and spare
parts for installation work.
Failure to use the specified parts may result in the unit falling, 
water leakage, electric shocks or fire.

Install the air conditioner on a foundation strong enough to
withstand the weight of the unit.

A foundation of insufficient strength may result in the equip-
ment falling and causing injury.

Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit
falling and causing accidents.

Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by qual-
ified personnel according to local laws and regulations and
this installation manual.
An insufficient power supply capacity or improper electrical
construction may lead to electric shocks or fire.

Make sure that all wiring is secured, the specified wires are used, 
and that there is no strain on the terminal connections or wires.
Improper connections or securing of wires may result in
abnormal heat build-up or fire.

When wiring the power supply and connecting the remote
controller wiring and transmission wiring, position the wires
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in elec-
tric shocks, fire or the terminals overheating.

If the supply cord is damaged, it must be replaced by the

manufacturer, a service agent or similarly qualified persons
in order to avoid a hazard.

If refrigerant gas leaks during installation, ventilate the area
immediately.
Toxic gas may be produced if the refrigerant comes into con-
tact with fire.

After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into
the room and comes into contact with a source of fire, such
as a fan heater, stove or cooker.

Be sure to switch off the unit before touching any electrical
parts.

Do not touch the switch with wet fingers.
Touching the switch with wet fingers can cause electric shock.

Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or
telephone earth lead.
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may
cause damage to the air conditioner.

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in elec-
tric shocks or fire.

CAUTION

While following the instructions in this installation manual,
install drain piping to ensure proper drainage and insulate
piping to prevent condensation.
Improper drain piping may result in indoor water leakage and 
property damage.

Install the indoor and outdoor units, power cord and connect-
ing wires at least 1 meter away from televisions or radios to
prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of
1 meter may not be sufficient to eliminate noise.)

Remote controller (wireless kit) transmitting distance can be
shorter than expected in rooms with electronic fluorescent
lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as
possible.

Only handle the indoor unit with gloves.

4PEN325876-1F.book  Page 1  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ20A2VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A2VEB FXDQ20A2VEB FXDQ25A2VEB FXDQ32A2VEB FXDQ40A2VEB FXDQ50A2VEB FXDQ63A2VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM...

Page 2: ...por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acord...

Page 3: ...lation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified pers...

Page 4: ...the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an...

Page 5: ...ould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If ther...

Page 6: ...prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anch...

Page 7: ...a ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the t...

Page 8: ...Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluo...

Page 9: ...Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipi...

Page 10: ...on area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use a...

Page 11: ...o not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of p...

Page 12: ...ower sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring...

Page 13: ...stem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 1...

Page 14: ...achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to th...

Page 15: ...n man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote...

Page 16: ...GHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THE...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM...

Page 18: ...4P489744 1 2017 04 Copyright 2012 Daikin 4P489744 1 book Page 1 Thursday April 27 2017 4 42 PM...

Reviews: