FXDQ-SPV1 EDTFVN391825
38
3P347455-11H
13
(3) Please carry out test run in accordance with the
installation manual for the outdoor unit.
SETTING
MODE No.
FIELD SET
MODE
11. FIELD SETTING AND TEST RUN
(The field setting of the following items shall be
completed with the operation of the remote control
in accordance with the on site installation conditions.
(In case that the remote control is Type BRC1E62,
please refer to the installation manual for the remote
control.))
(1) Please confirm whether the electrical box cover
of the indoor unit and the outdoor unit have been
firmly covered.
The field setting is carried out with the remote control,
and whether it is required to carry out setting
depends on the on site installation situations.
(2) According to the installation situations, when the
power supply is switched on, use the remote control
to carry out the field setting, and please follow
Section “FIELD SETTING” in the operation manual
for the remote control to carry out setting.
·
When setting, the “MODE No.”, “FIRST CODE No.”
and “SECOND CODE No.” can be changed.
·
In Section “FIELD SETTING”, the setting sequences
and the operating methods which can be carried out
with the remote control are listed.
·
Finally, ask the user to keep the “FIELD SETTING”
operation manual and the installation manual well.
11-1 Conversion of the static pressure outside the unit
·
The Second Code No. can be converted in accordance
with the resistance force of the pipe.
(The second code number is set “01” when delivered
from the factory.)
·
For details, please refer to the technical documents.
Static pressure outside the unit MODE No.
Standard
Set to high static pressure
01
02
01
02
13 (23)
5
11-2 Setting the remote operated control
·
To carry out the input switching of forced off or on/off,
the settings can be the ones as shown in the following
table, and the settings can be carried out by changing
the second code number.
(The second code number is set to “01” when delivered
from the factory.)
External ON/OFF input
MODE No. FIRST CODE No. SECOND CODE No.
Forced off
ON/OFF operation
12 (22)
1
·
The functions of Forced off and ON/OFF operation input
signal A are shown in the following table.
Forced off
ON/OFF operation
When the input signal A is “ON”, force off
(not controlled by the remote control)
Input signal A “OFF”
→
“ON”,
turn on the air conditioner.
When the input signal A is “OFF”,
the remote control can be used.
Input signal A “ON”
→
“OFF”,
turn off the air conditioner.
11-3 Setting the time to display the clean air filter
element signal
·
To change the “Setting for contamination level of the
air filter element”, tell the following contents to the user.
·
The factory setting to display the clean air filter element
signal is 2500 hours (about 1 year).
·
It can be set not to display the signal.
·
When installed in a dusty place, the setting time to
display the clean air filter element signal should be set
to the low position.
·
Please tell the user :
To prevent the air filter element
meshes from being blocked, the air filter element must
be regularly cleaned ;
The cleaning intervals set.
MODE
No.
FIRST
CODE No.
10(20)
0
1
3
Description on setting
SECOND CODE No.
01
02
Minor / serve
filter element
contamination
Ultra long
life type
Long life
type
Minor
About
10000 hours
About
2500 hours
Severe
About
5000 hours
About
1250 hours
Time interval to display the
clean air filter element signal Long life type
Ultra long
life type
Display the clean air filter
element signal
Display
Do not
display
11-4 Setting when any optional part is installed
·
Please refer to the installation manual supplied with
the optional part, so as to carry out the necessary
setting.
(Cases in which the wireless remote control is used)
·
When the remote control used is a wireless remote
control, the address shall be set for the wireless remote
control. For detailed steps for setting, please refer to
the installation instruction manual for the wireless
remote control.
·
When any abnormality happens, the run indicator
on the remote control will flash. Confirm the error
code on the LCD display and locate the error.
In the “Key points for repair” for the indoor unit,
there are error code explanations and error
descriptions.
In case that the following signals are displayed on
the display, there may be wiring errors or discontinuity
of the power supply. Please check again.
Display on the
remote control
Error content
Display “ ”
• Forced off terminal (T
1
and T
2
) is short circuited.
• Test run is not carried out.
•
The power supply for the outdoor unit is disconnected.
•
The power cable for the outdoor unit is not connected.
• The transmission cable and/or the forced off cable
are incorrectly connected.
• The transmission cable is broken.
• The connection cables between the air conditioner
are reversed.
•
The power supply for the outdoor unit is disconnected.
•
The power cable for the outdoor unit is not connected.
• The remote control cable, the transmission cable
and/or the forced off cable are incorrectly connected.
• The remote control cable is broken.
Display “ ”
Display “ ”
Display “ ”
Display “ ”
No display
SECOND
CODE No.
FIRST
CODE No.
SECOND CODE No.
FIRST CODE No.
1
2
Summary of Contents for FXDQ-SPV1
Page 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...
Page 2: ......
Page 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...
Page 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...
Page 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...
Page 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...
Page 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...
Page 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...
Page 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...
Page 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...
Page 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...
Page 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...
Page 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...
Page 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...
Page 41: ......
Page 42: ......
Page 43: ......