FXDQ-SPV1 EDTFVN391825

35

3P347455-11H

10

[Connection of the power cable, remote control 

cable and transmission cable]

(Please refer to Fig. 15)

O F F

W I R I N G

F O R C E D

R E M O T E

C O N T R L

T R A N S M I S S I O N

P 1 P 2 F 1 F 2 T 1 T 2

L

N

OFF

WIRING

FORCED

REMOTE

CONTROL

TRANSMISSION

P

1

P

2

F

1

F

2

T

1

T

2

OFF

WIRING

FORCED

REMOTE

CONTROL

TRANSMISSION

P

1

P

2

F

1

F

2

T

1

T

2

10. WIRING EXAMPLE

10-1 Connection of the power cables

· 

As shown in the Fig. 14, please open the electrical box 

   cover and then connect the cables.

   (Please refer to Fig. 14)

Electrical box cover

Power cable

Grounding cable

Wiring diagram

(Inside)

(One side of the electrical box)

* Transmission cable

* Remote control cable

* Never connect the 

  power cable here, 

  otherwise fault will 

  occur.

Power cable

Grounding cable

Banding tie (for fixing)
Use the anti-slip banding 

tie on the power supply side 

to tie up the cable protection 

sleeve and the fixing part 

together (Accessory (9)). 

Fixing part
Fixing part
Remove the fixing part with a 

screwdriver. Put the cable though 

the fixing part, and connect the 

fixing part to the electrical box.

Fixing part

Banding tie (prevent slipping)
Fix the cable protection sleeve (Accessory (10))

CAUTION

• The cables must be routed through the cable routing section.

• When the cables are connected, to prevent water and small 

  animals from entering, please take protection measures for 

  the cables and the cable routing section.

• Follow the below figure to wrap the seal (12) onto the strong 

  current cable and the weak current cable. (In case that water 

  enters into the unit or small animals as insects enter into the

  unit, short circuit can occur in the electrical box.)

  Close firmly, and no gap can be left. 

Seal (12)

(Accessory)

Cable routing 

section

Cable

Outer side of 

air conditioner

Inner side of 

air conditioner

[Method for sealing the seal]

Fig. 14

CAUTION

· 

When fixing the cables, note to follow the method in 

   Fig. 14 to clamp with the banding tie (9) and (10), so 

   that the connection section will not be tensioned.

· 

Please use the fixing part to connect the power cable 

   and the grounding cable to the electrical box.

· 

When connecting the cables, the cables shall be routed 

   orderly and placed even, and the electrical box cover 

   shall not be supported up, and the electrical box cover 

   shall be covered firmly.

   When covering the electrical box cover, be careful not 

   to clamp any cable.

· 

Outside the air conditioner, the weak current cables 

   (the remote control cable and the transmission cable) 

   shall not be routed with the strong current cables 

   (the grounding cable and the power cable), but shall be 

   separated for a distance of over 50 mm. Otherwise 

   misoperation and fault can happen due to electrical 

   interference (foreign noise).

[Notes]

· 

For the installation and wiring of the remote control, 

   please refer to the “Installation manual for the remote 

   control” supplied with the remote control.

· 

When connecting the power supply for the air conditioner, 

   please refer to the “Wiring Diagram” on the nameplate 

   at the same time.

· 

In any circumstances, the power cable shall not be 

   connected to the terminal block of the remote control 

   cable or the transmission cable.

   Otherwise the whole air conditioning system will be 

   damaged.

· 

Please connect the remote control cable and the 

   transmission cable to the corresponding terminal block.

PC board (ASSY) 

of the indoor unit

 Terminal block (3P)

Power cable

Grounding cable

Please route the 

cables through the 

cable routing section

Terminal block (6P)

Remote control cable

Transmission cable

Please route the cables through 

the cable routing section

•  Cases that the cooling capacity 

   of the connected outdoor unit is 

   24 kW or below

•  Cases that the cooling capacity of 

   the connected outdoor unit is above 

   24 kW

Shielded cable

Fig. 15

· 

Dimensions of the shielded cable processed 

   (indoor connection cable)

50-70 mm

± 

1mm

· 

Power cable and grounding cable

   Open the electrical box cover.

   Then, route the cables through the cable routing 

   section into the air conditioner, and connect them to 

   the terminal board (3P). In addition, the sleeve of the 

   cables shall be always put into the electrical box.

· 

Remote control cable and transmission cable

   Route the cables through the cable routing section 

   into the air conditioner, and connect them to the 

   terminal board (6P). In addition, the sleeve of the 

   cables shall be always put into the electrical box.

Summary of Contents for FXDQ-SPV1

Page 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...

Page 2: ......

Page 3: ...ams 10 6 Electric Characteristics 11 7 Safety Devices Setting 12 8 Capacity Tables 13 8 1 Cooling Capacity for Te Auto 13 8 2 Cooling Capacity for Te 6 C 13 8 3 Cooling Capacity for Te 9 C 14 8 4 Heat...

Page 4: ...5 2 1 Lineup Capacity range 2 2 kW 2 8 kW 3 6 kW 4 5 kW 5 6 kW 7 1 kW 0 8 HP 1 HP 1 25 HP 1 6 HP 2 HP 2 5 HP Capacity index 20 25 31 25 40 50 62 5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 1 p...

Page 5: ...tion manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wa...

Page 6: ...manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Washers...

Page 7: ...on manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wash...

Page 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...

Page 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...

Page 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...

Page 11: ...iagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 12...

Page 12: ...FXDQ SPV1 EDTFVN391825 10 5 Wiring Diagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 3D099151...

Page 13: ...FXDQ SPV1 EDTFVN391825 11 6 Electric Characteristics FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 4D090515...

Page 14: ...50 V 5 A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse A1P 250 V 5 A...

Page 15: ...gth Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 C...

Page 16: ...These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and pip...

Page 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...

Page 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...

Page 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...

Page 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...

Page 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...

Page 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...

Page 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...

Page 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...

Page 25: ...FXDQ SPV1 EDTFVN391825 23 11 Centre of Gravity FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D072718G Unit mm 4D072719G Unit mm...

Page 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...

Page 27: ...s Item Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Remote controller Wireless Cooling Only BRC4C66 Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller Wired remote...

Page 28: ...ctrical shock or fire Use cables with the specified specifications and all the cables shall be reliably connected and the wiring terminals and the cables are not tensioned by any external force Poor w...

Page 29: ...ting methods of the various functions as well as the temperature adjustment methods of the air conditioner to the user and ask the user to read the operation manual and carry out operations at the sam...

Page 30: ...y drained off The strength of the ceiling can withstand the weight of the indoor unit The ceiling is not obviously tilted There is no hazard of possible leakage of combustible gas There is enough spac...

Page 31: ...an be built in the new ceiling and other items purchased in the market can be used Please refer to Fig 3 Fig 3 Top ceiling Pile anchor screw Long nut or screw thread device Hoisting bolt Note The leng...

Page 32: ...r air exchange 1 Connect the pipe Refrigerant has been filled in the outdoor unit Align the connecting section of the refrigerant pipe to the center of the flare section and firstly turn 3 4 operation...

Page 33: ...pipe of the air supply side The flare nut section The pipe supplied on site must be heat insulated to the connecting section of the pipe In case that the pipe is exposed condensate can occur and inju...

Page 34: ...ng band Water drainage hose 2 Large seal 5 Accessory Metal clip 1 Accessory 4mm Precautions on installing the water drainage riser pipe Case for Model FXDQ SPV1 Please confirm that the height of the w...

Page 35: ...e air conditioner Point 12 14 or 16 Use sealing materials such as aluminum adhesive tape to seal the connection section between the flange and the air pipe on the air inlet side so as to prevent air l...

Page 36: ...is within a place easily in contact with people please install an electricity leakage circuit breaker to prevent electrical shock 4 When an electricity leakage circuit breaker is used please use a dev...

Page 37: ...ng cable to the electrical box When connecting the cables the cables shall be routed orderly and placed even and the electrical box cover shall not be supported up and the electrical box cover shall b...

Page 38: ...auses as loosened cables When connected to the terminal board please use round wiring terminal with insulated sleeve In case that round wiring terminal with insulated sleeve cannot be used connect the...

Page 39: ...Electrical Wiring Work 3 Remove the electrical box cover 4 Connect remote control 2 Slave to the terminal board of the remote control cable in the electrical box P1 and P2 No polarity 1 P 2 P 1 F 2 F...

Page 40: ...Setting the time to display the clean air filter element signal To change the Setting for contamination level of the air filter element tell the following contents to the user The factory setting to d...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...rts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of...