Specifications
Notes
(1) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m (horizontal)
(2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m (horizontal)
(3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(4) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(5) Maximum allowable voltage range variation between phases is 2%.
(6) MCA/MFA: MCA = 1.25 x FLA
(7) MFA
≤
4 x FLA
(8) Next lower standard fuse rating minimum 16A
(9) Select wire size based on the value of MCA
(10) Use a circuit breaker instead of a fuse.
1-2 Electrical Specifications
FXAQ20P
FXAQ25P
FXAQ32P
FXAQ40P
FXAQ50P
FXAQ63P
Power supply
Name
V1
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz Minimum circuit amps (MCA)
A
0.3
0.4
0.5
0.6
Maximum fuse amps (MFA)
A
16
Full load
amps (FLA)
Total
A
0.2
0.3
0.4
0.5