background image

16

WARNING

Never connect power supply wiring to the terminal block for remote controller wiring as this could damage 
the entire system.

Use only specified wire and connect wires to the terminal tightly. Be careful wires do not place external 
stress on terminals. Keep wires in neat order so as not to obstruct other equipment. Make sure that the 
electric box lid fits tightly. Incomplete connections could result in overheating and, in worse case, result in 
electric shock or fire.

To avoid a short circuit in the electric parts box, be sure to apply sealing material or putty (not included) to 
the wiring hole to prevent the infiltration of water as well as insects or other small creatures. Otherwise a 
short-circuit may occur inside the electric parts box.

CAUTION

When clamping the wirings, be sure no tension is applied to the wire connections by using the included 
clamp. Also, when wiring, make sure the lid on the electric parts box fits snugly by arranging the wirings 
neatly and attaching the service lid firmly. When attaching the service lid, make sure no wirings get caught 
in the edges. Pass wiring through holes to prevent damage to them. 

Make sure the remote controller wiring and transmission wiring between the units, and other electrical wir-
ing do not pass through the same locations outside the unit, separating them by at least 5”, otherwise elec-
trical noise (external static) could cause incorrect operation or breakage.
Use only specified wire and tightly connect wires to terminals. Be careful wires do not place external stress 
on terminals. Keep wiring in neat order and so as not to obstruct other equipment such as popping open the 
service cover. Make sure the cover closes tight. Incomplete connections could result in overheating, and in 
worse case, electric shock or fire.

REMOTE

CNTRL

FORCED

OFF

TRANSMISSION

WIRING

F1 F2 T1 T2

P1 P2

Terminal block (6P)

Ground terminal

Ground wiring

Power supply wiring

Power supply
terminal block (3P)

In the case of using the power
supply terminal together with
the other connecting wirings

     Make sure to process 
the insulation at the wire 
terminal part properly so that 
the terminals do not get in 
contact each other.

Fig. 22

Remote 
controller wiring

Ground wiring

Power supply wiring

Transmission  wiring

Transmission wiring

< Wiring clamp method >

Clamp small 
(accessory) (5)

Clamp small 
(accessory) (5)

Clamp small 
(accessory) (5)

Remote controller 
wiring

Insulating tube

(3 places)

Cut off any excess 
material after tightening.

L1

L2

Insulating tube

01_EN_3PN07521-1.fm  Page 16  Monday, June 19, 2006  5:05 PM

Summary of Contents for FXAQ07MVJU

Page 1: ...4MVJU INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner SYSTEM Invert...

Page 2: ...n how to operate the unit and keep it maintained Also inform customers that they should store this installation manual along with the operation manual for future reference This air conditioner comes u...

Page 3: ...ater leakage electric shocks or fire Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in water leakage electric shocks fire o...

Page 4: ...electrical parts can cause malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting...

Page 5: ...r is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electromagnetic interference WARNING Entrust installation to the pl...

Page 6: ...s the air passage Where condensate can be properly drained Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly The units may drop vibrat...

Page 7: ...fore proceeding with the installation Also reinforce the place to prevent vibration and noise before installing The installation pitch can be found on the paper pattern for installation 3 so refer to...

Page 8: ...at least a 3 1 2 gap between the ceiling and the main unit b Temporarily attach the installation panel 1 at the temporary securing position on the paper pattern for installation 3 and use a level to m...

Page 9: ...and back left piping Remove the front grill Refer to Fig 7 How to remove the front grill Remove the front grill as described below when securing the indoor unit with screws or when attaching Optional...

Page 10: ...e refrigerant piping to the wall 7 Pass power supply wiring and ground wiring threaded through conduit For connecting the con duit to the unit see 8 1 HOW TO CONNECT WIRINGS and remote controller wiri...

Page 11: ...p to approximately 250 F so use insulation which is sufficiently resistant Also in cases where the temperature and humidity of the refrigerant piping sections might exceed 86 F or RH80 reinforce the r...

Page 12: ...nt to leak Use the flare nut included with the unit Refer to Table 1 for tightening torque Table 1 Not recommended but in case of emergency You must use a torque wrench but if you are obliged to insta...

Page 13: ...ould be set to 2 9 psi with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 14 After checking for gas leaks be sure to insulate the pipe connections using th...

Page 14: ...eter of drain piping which adapts to the capacity of the unit connected 2 Make sure the drain works properly After drain work is complete perform a drain check by opening the front panel removing the...

Page 15: ...it for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner DANGER Do not ground u...

Page 16: ...22 Transmission wiring and remote controller wiring Unscrew and remove the service lid Thread the remote controller wiring and transmission wiring through the included insulating tube long 7 and secur...

Page 17: ...oller wiring and transmission wiring between the units and other electrical wir ing do not pass through the same locations outside the unit separating them by at least 5 otherwise elec trical noise ex...

Page 18: ...e terminal screws 3 Do not connect wires of different gauge to the same ground terminal Looseness in the connection may lessen protection 4 Keep transmission wiring at least 5 away from power supply w...

Page 19: ...D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 Outdoor unit No 2 System Indoor unit A Indoor unit B Indoor unit C Most downst...

Page 20: ...other remote controller set to M Refer to Fig 29 Wiring Method See 7 ELECTRIC WIRING WORK 3 Remove the service lid 4 Add remote control 2 slave to the terminal block 6P for remote controller P1 P2 in...

Page 21: ...NO and SECOND CODE NO Refer to the installation manual attached to the remote controller The Field Settings included with the remote controller lists the order of the settings and method of oper ation...

Page 22: ...onding trouble is provided in the installation manual of the outdoor unit If any of the items in Table 5 are displayed there may be a problem with the wiring or power so check the wiring again Table 5...

Page 23: ...0609 HT 3PN07521 1 EM04A013B 00_CV_3PN07521 1 fm Page 2 Monday June 19 2006 2 30 PM...

Reviews: