background image

14

CAUTION

Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the 
sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

7. ELECTRIC WIRING WORK

7-1 GENERAL INSTRUCTIONS

All field supplied parts and materials and electric works must conform to local codes.

Use copper wire only.

For electric wiring work, refer to also “WIRING DIAGRAM” attached to the unit.

For remote controller wiring details, refer to the installation manual attached to the remote controller.

All wiring must be performed by an authorized electrician.

This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the 
terminal block wiring to the outdoor unit and BS unit is properly matched. If wiring and piping between the 
outdoor unit and indoor unit are mismatched, the system may cause a malfunction.

A circuit breaker capable of shutting down power supply to the entire system must be installed.

Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected 
to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.

Be sure to ground the air conditioner.

DANGER

Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could 
cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could 
result in an explosion which could lead to severe injury or death.

7-2 ELECTRICAL CHARACTERISTICS

MCA:  Min. Circuit Amps (A);

MFA: Max. Fuse Amps (A)

W:  Fan Motor Rated Output (W);

FLA: Full Load Amps (A)

7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE

Allowable length of transmission wiring and remote controller wiring are as follows.
(1) Outdoor unit - Indoor unit:Max.3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit - Remote controller:Max.1640ft.

Insulated thickness: 1/16” or more.

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage range

MCA

MFA

W

FLA

FXAQ07MVJU

60

208-230

Max. 253

Min.  187

0.3

15

40

0.2

FXAQ09MVJU

0.3

15

40

0.2

FXAQ12MVJU

0.4

15

40

0.3

FXAQ18MVJU

0.4

15

43

0.3

FXAQ24MVJU

0.6

15

43

0.5

Model

Power supply wiring

Remote controller wiring 
Transmission wiring

Field fuses 

Size

Wire

Size

FXAQ07MVJU

15A

Size must 
comply with 
local codes.

Sheathed wire (2 wire)

AWG18-16

FXAQ09MVJU

FXAQ12MVJU

FXAQ18MVJU

FXAQ24MVJU

01_EN_3PN07521-1.fm  Page 14  Monday, June 19, 2006  5:05 PM

Summary of Contents for FXAQ07MVJU

Page 1: ...4MVJU INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner SYSTEM Invert...

Page 2: ...n how to operate the unit and keep it maintained Also inform customers that they should store this installation manual along with the operation manual for future reference This air conditioner comes u...

Page 3: ...ater leakage electric shocks or fire Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in water leakage electric shocks fire o...

Page 4: ...electrical parts can cause malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting...

Page 5: ...r is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electromagnetic interference WARNING Entrust installation to the pl...

Page 6: ...s the air passage Where condensate can be properly drained Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly The units may drop vibrat...

Page 7: ...fore proceeding with the installation Also reinforce the place to prevent vibration and noise before installing The installation pitch can be found on the paper pattern for installation 3 so refer to...

Page 8: ...at least a 3 1 2 gap between the ceiling and the main unit b Temporarily attach the installation panel 1 at the temporary securing position on the paper pattern for installation 3 and use a level to m...

Page 9: ...and back left piping Remove the front grill Refer to Fig 7 How to remove the front grill Remove the front grill as described below when securing the indoor unit with screws or when attaching Optional...

Page 10: ...e refrigerant piping to the wall 7 Pass power supply wiring and ground wiring threaded through conduit For connecting the con duit to the unit see 8 1 HOW TO CONNECT WIRINGS and remote controller wiri...

Page 11: ...p to approximately 250 F so use insulation which is sufficiently resistant Also in cases where the temperature and humidity of the refrigerant piping sections might exceed 86 F or RH80 reinforce the r...

Page 12: ...nt to leak Use the flare nut included with the unit Refer to Table 1 for tightening torque Table 1 Not recommended but in case of emergency You must use a torque wrench but if you are obliged to insta...

Page 13: ...ould be set to 2 9 psi with a pressure reducing valve if brazing while inserting nitrogen into the piping Refer to Fig 14 After checking for gas leaks be sure to insulate the pipe connections using th...

Page 14: ...eter of drain piping which adapts to the capacity of the unit connected 2 Make sure the drain works properly After drain work is complete perform a drain check by opening the front panel removing the...

Page 15: ...it for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner DANGER Do not ground u...

Page 16: ...22 Transmission wiring and remote controller wiring Unscrew and remove the service lid Thread the remote controller wiring and transmission wiring through the included insulating tube long 7 and secur...

Page 17: ...oller wiring and transmission wiring between the units and other electrical wir ing do not pass through the same locations outside the unit separating them by at least 5 otherwise elec trical noise ex...

Page 18: ...e terminal screws 3 Do not connect wires of different gauge to the same ground terminal Looseness in the connection may lessen protection 4 Keep transmission wiring at least 5 away from power supply w...

Page 19: ...D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 Outdoor unit No 2 System Indoor unit A Indoor unit B Indoor unit C Most downst...

Page 20: ...other remote controller set to M Refer to Fig 29 Wiring Method See 7 ELECTRIC WIRING WORK 3 Remove the service lid 4 Add remote control 2 slave to the terminal block 6P for remote controller P1 P2 in...

Page 21: ...NO and SECOND CODE NO Refer to the installation manual attached to the remote controller The Field Settings included with the remote controller lists the order of the settings and method of oper ation...

Page 22: ...onding trouble is provided in the installation manual of the outdoor unit If any of the items in Table 5 are displayed there may be a problem with the wiring or power so check the wiring again Table 5...

Page 23: ...0609 HT 3PN07521 1 EM04A013B 00_CV_3PN07521 1 fm Page 2 Monday June 19 2006 2 30 PM...

Reviews: