1-1  TECHNICAL SPECIFICATIONS

FXAQ20MAVE9

FXAQ25MAVE9

FXAQ32MAVE9

FXAQ40MAVE9

FXAQ50MAVE9

FXAQ63MAVE9

Capacity

Cooling

kW

2.2

2.8

3.6

4.5

5.6

7.1

Heating

kW

2.5

3.2

4.0

5.0

6.3

8.0

Power Input (50Hz) Cooling

kW

0.016

0.022

0.027

0.020

0.027

0.050

Heating

kW

0.024

0.027

0.032

0.020

0.032

0.060

Power Input (60Hz) Cooling

kW

0.016

0.022

0.027

0.020

0.027

0.050

Heating

kW

0.024

0.027

0.032

0.020

0.032

0.060

Casing

Colour

white (3.0Y8.5/0.5)

Dimensions

Unit

Height

mm

290

Width

mm

795

795

795

1,050

1,050

1,050

Depth

mm

230

Weight

Unit

kg

11

11

11

14

14

14

Heat Exchanger

Dimensions

Nr of Rows

2

Fin Pitch

mm

1.40

Face Area

0.161

0.161

0.161

0.213

0.213

0.213

Nr of Stages

14

Fan

Type

Cross flow fan

Quantity

1

Cooling

High

m³/min

7.5

8

9

12

15

19

Low

m³/min

4.5

5

5.5

9

12

14

Fan

Motor

Quantity

1

Model

QCL9661M

QCL9661M

QCL9661M

QCL9686M

QCL9686M

QCL9686M

Output  (high)

W

40

40

40

43

43

43

Drive

Direct drive

Refrigerant

Name

R-410A

Cooling

Sound Pressure

High

dBA

35.0

36.0

37.0

39.0

42.0

46.0

Low

dBA

29.0

29.0

29.0

34.0

36.0

39.0

Piping connections

Liquid (OD)

Type

Flare connection

Diameter

mm

6.35

6.35

6.35

6.35

6.35

9.52

Gas

Type

Flare connection

Diameter

mm

12.7

12.7

12.7

12.7

12.7

15.9

Drain

Diameter

mm

VP13 (I.D. 13/O.D. 18)

Heat Insulation

Foamed polystyrene/foamed polyethylene

Air Filter

Washable resin net

Refrigerant control

Electronic expansion valve

Temperature control

Microprocessor thermostat for cooling and heating

Safety devices

PC board fuse

Standard Accessories

Installation and operation manual

Installation panel

Paper pattern for installation

Insulation tape

Clamps

Screws

Notes

Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB,  outdoor temperature 

: 35°CDB,  equivalent refrigerant piping : 5m (horizontal)

Nominal heating capacities are based on : indoor temperature : 20°CDB,  outdoor temperature : 7°CDB, 

6°CWB,  equivalent refrigerant piping : 5m (horizontal)

Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Summary of Contents for FXAQ-MAVE9 Series

Page 1: ...Wall Mounted Unit FXAQ MAVE9 air conditioning systems technical data...

Page 2: ...fications 60Hz 3 2 Safety device settings 4 3 Options 4 4 Control systems 4 5 Capacity tables 5 Cooling capacity tables 5 Heating capacity tables 7 6 Dimensional drawing centre of gravity 9 Dimensiona...

Page 3: ...L9661M QCL9661M QCL9686M QCL9686M QCL9686M Output high W 40 40 40 43 43 43 Drive Direct drive Refrigerant Name R 410A Cooling Sound Pressure High dBA 35 0 36 0 37 0 39 0 42 0 46 0 Low dBA 29 0 29 0 29...

Page 4: ...ller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse use a circuit breaker 1 3 ELECTRICAL SPECIFICATIONS 60HZ FXAQ20MAVE9 FXAQ2...

Page 5: ...FXAQ32MV FXAQ40MV FXAQ50MV FXAQ63MV Wired remote control BRC1D52 Infrared remote control Heat pump BRC7E618 Cooling only BRC7E619 FXAQ20MV FXAQ25MV FXAQ32MV FXAQ40MV FXAQ50MV FXAQ63MV Remote control...

Page 6: ...1 8 2 3 2 0 2 6 2 2 2 8 2 2 3 0 2 2 3 1 2 2 3 2 2 1 33 0 1 9 1 8 2 3 2 0 2 6 2 2 2 8 2 2 3 0 2 2 3 1 2 2 3 1 2 1 35 0 1 9 1 8 2 3 2 0 2 6 2 2 2 8 2 2 3 0 2 2 3 0 2 2 3 1 2 1 37 0 1 9 1 8 2 3 2 0 2 6 2...

Page 7: ...3 2 4 5 3 7 5 2 4 1 5 6 4 2 6 0 4 3 6 2 4 2 6 4 3 9 33 0 3 8 3 2 4 5 3 7 5 2 4 1 5 6 4 2 6 0 4 3 6 1 4 2 6 3 3 9 35 0 3 8 3 2 4 5 3 7 5 2 4 1 5 6 4 2 5 9 4 3 6 0 4 1 6 2 3 8 37 0 3 8 3 2 4 5 3 7 5 2 4...

Page 8: ...8 3 0 2 2 3 1 3 1 3 1 3 1 3 0 2 8 5 0 4 1 3 3 3 2 3 2 3 1 3 0 2 8 7 0 6 0 3 4 3 4 3 2 3 1 3 0 2 8 9 0 7 9 3 5 3 4 3 2 3 1 3 0 2 8 11 0 9 8 3 6 3 4 3 2 3 1 3 0 2 8 13 0 11 8 3 6 3 4 3 2 3 1 3 0 2 8 15...

Page 9: ...5 3 0 2 2 6 2 6 2 6 2 6 1 5 9 5 5 5 0 4 1 6 4 6 4 6 3 6 1 5 9 5 5 7 0 6 0 6 6 6 6 6 3 6 1 5 9 5 5 9 0 7 9 6 8 6 7 6 3 6 1 5 9 5 5 11 0 9 8 7 0 6 7 6 3 6 1 5 9 5 5 13 0 11 8 7 1 6 7 6 3 6 1 5 9 5 5 15...

Page 10: ...nnection 5 Liquid pipe 6 4 Flare connection 6 Drain hose VP13 External dia 18 7 Grounding terminal M4 8 Right side pipe connection hole 9 Left side pipe connection hole FXAQ40 50MV 3D038539B Approx 40...

Page 11: ...r more required space 2 500 or more For installation in high places Filter part Filter part Name plate Note 2 Approx 475 Approx 460 Approx 415 Piping and wiring intake Mounting location NOTES 1 Name p...

Page 12: ...ping diagram 3 7 FXAQ MV DU220 602J Liquid pipe connection port Filter Filter Electronic expansion valve Fan Gas pipe connection port Refrigerant flow Cooling Heating Heat exchanger Piping connection...

Page 13: ...Fuse 3A 250V Receiver display unit attached to infrared remote control SS1 Selector switch main sub HAP Light emitting diode service monitor green A2P Printed circuit board Connector for optional par...

Page 14: ...ic pressure 0 dB 20 Pa 2 Measuring place anechoic chamber 3 Operating noise differs with operation and ambient conditions Data were not available at the time of publication Model Sound pressure level...

Page 15: ...LOW Approximate treshold hearing for continuous noise Ocatve band sound pressure level dB 0dB 0 0002 bar Scale Mode Hi Low A 36 0 29 0 C 40 5 34 0 Mike 1m 1m NOTES 1 Over all dB B G N is already recti...

Page 16: ...LOW Approximate treshold hearing for continuous noise Ocatve band sound pressure level dB 0dB 0 0002 bar Scale Mode Hi Low A 42 0 36 0 C 44 0 39 0 Mike 1m 1m NOTES 1 Over all dB B G N is already recti...

Page 17: ...m or bigger When directly connecting a hard vinyl chloride pipe joint nominal diameter 13mm to the drain hose connected to the indoor unit i e for embedded piping etc use a commercially available hard...

Page 18: ...ible within the allowable limit Refer to the installation manual of the outdoor unit Keep the indoor and outdoor units power cable and transmission wiring at least 1 m from TVs and radios to prevent d...

Page 19: ...Indoor Units Wall Mounted Unit FXAQ MAVE9 VRV Systems Indoor Units 18 10 Installation 10 2 Service space 3 10...

Page 20: ...ithout prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publicat...

Reviews: