1-8
Operating Limits:
Thermal carrier : Water
Water temperature : 4° ~ 10°C (Cooling), 35°C ~ 70°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Heat Pump Unit
Cooling Unit
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
19.0 / 66.2
14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6
23.0 / 73.4
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
15.0 / 59.0
-
Maximum indoor
temperature
27.0 / 80.6
-
OPERATING RANGE
All wires must be
Þ
rmly connected.
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord
anchorage.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly
Þ
xed to avoid any gap.
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
•
•
•
•
•
•
•
Attach insulation sleeve
Round crimp-style terminal
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screws.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
•
•
•
•
Electric wire