FWF
Fan coil units
4PW64524-1 – 09.2010
Installation manual
29
5 Commission the fan coil unit
Activating forced OFF and ON/OFF operation
The following table explains “forced OFF” and “ON/OFF operations” in response to the input
signal.
Table 5.4: Forced OFF and ON/OFF operation
1
Turn the power on and then use the remote controller to select operation.
2
Set the remote controller to the field set mode.
Table 5.5: Forced OFF and ON/OFF selection
Test the installation
5.3
Test the installation
After installation, the installer is obliged to verify correct operation. Therefore a test run must
be performed according to the procedures described below.
In case something is wrong with the unit and it does not operate, contact your local DAIKIN
dealer.
Forced OFF
ON/OFF operations
Protective equipment input
Input “ON” stops operation
Input OFF
→
ON: turns on the
unit (impossible by remote
controllers)
Input ON: enables abnormal
system stop (an error code
will be displayed)
Input “OFF” enables control
Input ON
→
OFF: turns off
the unit (by remote
controller)
Input OFF: enables normal
operation
Setting
Mode No.
First code No.
Second code No.
Forced OFF
12(22)
8
01
ON/OFF operation
12(22)
8
02
Protective
equipment input
12(22)
8
03
Notice
For FWF models, the “forced OFF” setting is as indicated in table
“Forced OFF and
ON/OFF selection” on page 29
and NOT 12(22)-1-01/02 as mentioned in some
option manuals.
Information
When using a wireless remote controller, conduct a test operation after installing the
decoration panel.
Summary of Contents for FWF02B7TV1B