3
General features and technical data
Their quiet operation, compact dimensions and particularly low height, make units ideal for false ceiling
installation even in vintage buildings with narrow ceiling spaces. Units are standard supplied with sound
proofed suction plenum, air filter and extra-long drain pan. Centrifugal fans, with forwards curved blades, are
statically and dynamically balanced and moved by single-phase motor with three speeds (standard) plus one
(optional).
The availability of 2&4 pipe versions, the possibility to change connection side on field and accessories like
electronic thermostat and water on/
off valves, provides the maximum flexibility and ease of installation.
02JT
03JT
04JT
05JT
06JT
07JT
08JT
09JT
10JT
11JT
S.High
m³/
h
331
548
715
667
982
1241
1238
1323
1837
1695
High
m³/
h
262
428
431
428
757
945
950
1066
1463
1341
Medium
m³/
h
219
357
323
325
596
756
764
882
1171
1210
Low
m³/
h
187
304
248
255
476
628
633
733
946
1093
Pa
W
41
61
76
73
106
144
140
157
201
203
kW
2.18
3.10
4.13
4.59
5.79
6.42
7.56
8.55
9.84
10.66
kW
1.38
2.27
2.94
3.08
4.22
5.21
5.54
6.08
7.65
7.82
kW
2.94
4.32
5.71
5.92
7.69
9.15
10.09 11.52 13.73 14.13
Cooling
l/
h
386
549
739
803
1022
1109
1338
1523
1764
1910
Cooling
kPa
11
8
16
11
31
13
8
10
22
17
Heating
kPa
9
7
13
9
26
11
7
9
19
14
1
1
2
2
2
3
3
3
4
4
MODELS FWB (2 PIPES)
Nominal Air Flow
External static pressure
30
Power Input
Cooling
capacity
Total capacity
Sensible capacity
Direct driven centrifugal fan (forward-curved blades);
hot-galvanised steel
4 steps:super high, high, medium, low
Water pressure drop
Heating capacity
Fan
Water flow
Type
Fan Speed
Quantity
220-240 /
1 /
50
Single phase capacitor running
Air filter
Washable Nylon in 8mm Aluminium frame
Type
Motor
Power supply
V /
Ph /
Hz
Rating Conditions:
The nominal air flow, power input and capacity test is under the power supply of 220V/
1Ph/50Hz.
Nominal Air Flow:
with plenum and filter, no water supply, ambient air temperature between 10 and 30
ć
Power input:
S.High fan speed
Cooling capacity
: 7/12
ć
inlet/
outlet water temperature, 27
ć
DB/
19
ć
WB air temperature, S.High fan speed
Heating capacity
: 50
ć
inlet water temperature, 20
ć
DB inlet air temperature, water flow rate same as for the cooling test, S.High fan speed
Heating capacity
for additional heat exchanger: 70
ć
inlet water temperature, water temperature decrease 10
ć
, 20
ć
DB inlet air temperature, S.High fan speed