background image

11

English

Indoor Unit Installation (1)

6.

Connecting the refrigerant pipe

 CAUTION

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A or R32.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches. 

6-1. Caution on piping handling 

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

6-2. Selection of copper and heat insulation 

materials

• When using commercial copper pipes and fittings, observe the following: 
1) Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/(mh°C))
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Flare nut tightening torque

Gas side

Liquid side

25/35 class

50 class

25/35/50 class

3/8 inch

1/2 inch

1/4 inch

32.7-39.9N·m

(333-407kgf·cm)

49.5-60.3N·m

(505-615kgf·cm)

14.2-17.2N·m

(144-175kgf·cm)

Gas side

Liquid side

Gas pipe thermal insulation

Liquid pipe 

thermal 

insulation

25/35 class

50 class

25/35 class

50 class

O.D. 9.5mm

O.D. 12.7mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 14-16mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more 40mm or more 30mm or more

Thickness 0.8mm (C1220T-O)

Torque wrench

Piping union

Flare nut

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration oil to 

the inner surface of the 

flare.

Do not apply refrigeration 

oil to the flare nut avoid 

tightening with over torque.

Spanner

[Apply oil]

[Tighten]

Wall

If no flare cap is 
available, cover 
the flare mouth 
with tape to keep 
dirt or water out.

Be sure to 
place a cap.

Rain

Liquid pipe

Gas pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finis

h

ing tape

Inter-unit 
wiring

3PEN477070-1A.book  Page 11  Tuesday, March 28, 2017  10:01 AM

Summary of Contents for FVXM35FV1B

Page 1: ...INSTALLATION MANUAL R410A R32 Split Series Models FVXS25FV1B FVXM25FV1B FVXS35FV1B FVXM35FV1B FVXS50FV1B FVXM50FV1B 3PEN477070 1A book Page 1 Tuesday March 28 2017 10 01 AM...

Page 2: ...3PEN477070 1A book Page 1 Tuesday March 28 2017 10 01 AM...

Page 3: ...o estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk...

Page 4: ...re Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of wires may result in abnormal h...

Page 5: ...ctrically powered safety measures To be effective the unit must be electrically powered at all times after installation other than short service intervals only for R32 refrigerant Do not install in pl...

Page 6: ...0 46 C DB 15 24 C DB 10 46 C DB Indoor temperature 18 32 C DB 10 30 C DB 18 32 C DB 2MK X S52 Outdoor temperature 10 46 C DB 15 24 C DB 10 46 C DB Indoor temperature 18 32 C DB 10 30 C DB 18 32 C DB 3...

Page 7: ...nly for R32 refrigerant 10 The unit shall not be installed more than 1 5 m above the floor only for R32 refrigerant 11 Pipework shall be protected from physical damage and shall not be installed in un...

Page 8: ...e dipswitch settings Set according to the type of unit purchased by the customer The default settings are on the heat pump side For cooling only Set the dipswitches on the cooling only side For heat p...

Page 9: ...osed Half concealed Floor Installation Wall Installation Concealed Grid Field supply Mounting plate A Molding 64 644 134 700 600 574 26 140 230 250 35 35 210 160 150 Unit mm Mounting plate A The mount...

Page 10: ...l position 3 How to set the different addresses When two indoor units are installed in one room the two wireless remote controllers can be set for different addresses 1 Remove the front grille 2 Live...

Page 11: ...the installation manual for the multi outdoor unit 2 Boring a wall hole and installing wall embedded pipe For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall...

Page 12: ...he front panel remove the 4 screws and dismount the front grille while pulling it forward Follow the procedure below when removing the slit portions For Moldings Remove the pillars Remove the slit por...

Page 13: ...Check that the flaring is properly made WARNING 1 Do not use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use pi...

Page 14: ...hat will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrig...

Page 15: ...butt joint with the included insulation sheet making sure there are no gaps CAUTION 1 Insulate the joint of the pipes securely Incomplete insulation may lead to water leakage 2 Push the pipe inside so...

Page 16: ...burst connections as they may cause overheating electrical shock or fire 2 Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the term...

Page 17: ...l hole Drill a wall hole of the size shown in the illustration on the right 2 Installation of supplemental plate for attaching main unit The rear of the unit can be fixed with screws at the points sho...

Page 18: ...e indoor unit 2 Install the indoor unit flush against wall NOTE For refrigerant piping Boring a wall hole and installing wall embedded pipe drain piping installing indoor unit flaring the pipe end con...

Page 19: ...the flow of cool warm air 2 Place a partition plate between outlet and inlet sections 3 Place a partition plate on the right side 4 Change the upward blow limit switch 5 Use a movable lattice at the...

Page 20: ...refrigerant piping Boring a wall hole and installing wall embedded pipe drain piping installing indoor unit flaring the pipe end connecting the refrigerant pipe checking for gas leakage attaching the...

Page 21: ...H R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECTOR FRAMEGROUND S L FLOATSWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L...

Page 22: ...the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 1 4 After trial operation when the f...

Page 23: ...3PEN477070 1A book Page 1 Tuesday March 28 2017 10 01 AM...

Page 24: ...1703 3P477070 1A Two dimensional bar code is a code for manufacturing 3PEN477070 1A book Page 1 Tuesday March 28 2017 10 01 AM...

Reviews: