background image

3

1

2

• Split - Sky Air

®

 • Indoor Unit

3

• Indoor Unit • Floor standing unit • FVQ-C

2

Specifications

Standard Accessories : Remote control wiring;
Standard Accessories : Dew proof material;
Standard Accessories : Installation pattern;
Standard Accessories : Screws;
Standard Accessories : Clamps;
Standard Accessories : Cover;
Standard Accessories : Insulation for fitting;
Standard Accessories : Bush;
Standard Accessories : Hole protection rubber;
Standard Accessories : Bracket for installation;
Standard Accessories : Installation manual;
Standard Accessories : Operation manual;

2-1 Technical Specifications

FVQ71CVEB

FVQ100CVEB

FVQ125CVEB

FVQ140CVEB

Power input

Cooling

Nom.

kW

0.117

0.238

0.276

Heating

Nom.

kW

0.117

0.238

0.276

Casing

Colour

Fresh White

Dimensions

Unit

Height/Width/
Depth

mm

1,850/600/270

1,850/600/350

Packed unit

Height/Width/
Depth

mm

1,996/732/389

1,996/732/469

Weight

Unit

kg

39

47

Packed unit

kg

61

70

Heat exchanger

Inside length

mm

476

Rows

Quantity

2

3

Fin pitch

mm

1.75

Passes

Quantity

6

10

11

Face area

0.40

0.22

Stages

Quantity

40

22

Empty tubeplate 
hole

Quantity

0

14

4

Fin

Type

Cross fin coil (multi louver fins and Hi-XSS tubes)

Heat exchanger 2

Rows

Quantity

-

3

Fin pitch

mm

-

1.75

Face area

-

0.22

Stages

Quantity

-

22

Fan

Type

Sirocco fan

Quantity

1

Air flow rate

Cooling High

m³/min

18

28

30

Nom.

m³/min

16

25

26

28

Low

m³/min

14

22

24

26

Heating High

m³/min

18

28

30

Nom.

m³/min

16

25

26

28

Low

m³/min

14

22

24

26

Fan motor

Model

QS33A1AM

Speed

Steps

3

Output

High

W

64

152

Sound power level

Cooling

High/Nom./Low

dBA

55/53/50

62/59/56

63/60/58

65/63/60

Heating

High/Nom./Low

dBA

55/53/50

62/59/56

63/60/58

65/63/60

Sound pressure level

Cooling

High/Nom./Low

dBA

43/41/38

50/47/44

51/48/46

53/51/48

Heating

Super high/High/
Nom./Low

dBA

-/43/41/38

-/50/47/44

-/51/48/46

-/53/51/48

Refrigerant

Type

R-410A

Piping connections

Liquid

Type/OD

mm

Flare connection/9.52

Gas

Type/OD

mm

Flare connection/15.9

Drain

I.D. 20/O.D. 26

Heat insulation

Foamed polystyrene / Foamed polyethylene

Summary of Contents for FVQ-C

Page 1: ...FVQ C Technical Data Air Conditioners E E D E N 1 2 1 0 0 F l o o r s t a n d i n g u n i t ...

Page 2: ...3 Electrical Specifications 4 3 Safety device settings 5 Safety Device Settings 5 4 Options 6 Options 6 5 Dimensional drawings 7 Dimensional Drawings 7 6 Piping diagrams 8 Piping Diagrams 8 7 Wiring diagrams 9 Wiring Diagrams Single Phase 9 8 External connection diagrams 10 External Connection Diagrams 10 9 Sound data 11 Sound Pressure Spectrum 11 ...

Page 3: ...ng buildings Ideal solution for shops restaurants or offices without false ceilings Very efficient for use in rooms with high ceilings Better air flow distribution is achieved via individual blow up and down swing mechanism or air volume control class 71 100 Compact design No optional adapter needed for DIII connection standard plug and play connection with centralised control systems intelligent ...

Page 4: ...t kg 61 70 Heat exchanger Inside length mm 476 Rows Quantity 2 3 Fin pitch mm 1 75 Passes Quantity 6 10 11 Face area m 0 40 0 22 Stages Quantity 40 22 Empty tubeplate hole Quantity 0 14 4 Fin Type Cross fin coil multi louver fins and Hi XSS tubes Heat exchanger 2 Rows Quantity 3 Fin pitch mm 1 75 Face area m 0 22 Stages Quantity 22 Fan Type Sirocco fan Quantity 1 Air flow rate Cooling High m min 1...

Page 5: ...it FVQ C 1 2 Split Sky Air Indoor Unit 4 2 Specifications 2 2 Electrical Specifications FVQ71CVEB FVQ100CVEB FVQ125CVEB FVQ140CVEB Power supply Phase 1 Frequency Hz 50 60 Voltage V 220 240 220 Current 60Hz Nominal running current A ...

Page 6: ...3 1 3 Split Sky Air Indoor Unit 5 Indoor Unit Floor standing unit FVQ C 3 Safety device settings 3 1 Safety Device Settings ...

Page 7: ... Indoor Unit Floor standing unit FVQ C 1 4 Split Sky Air Indoor Unit 6 4 Options 4 1 Options ...

Page 8: ...3 1 5 Split Sky Air Indoor Unit 7 Indoor Unit Floor standing unit FVQ C 5 Dimensional drawings 5 1 Dimensional Drawings ...

Page 9: ... Indoor Unit Floor standing unit FVQ C 1 6 Split Sky Air Indoor Unit 8 6 Piping diagrams 6 1 Piping Diagrams ...

Page 10: ...3 1 7 Split Sky Air Indoor Unit 9 Indoor Unit Floor standing unit FVQ C 7 Wiring diagrams 7 1 Wiring Diagrams Single Phase ...

Page 11: ... Indoor Unit Floor standing unit FVQ C 1 8 Split Sky Air Indoor Unit 10 8 External connection diagrams 8 1 External Connection Diagrams ...

Page 12: ...3 1 9 Split Sky Air Indoor Unit 11 Indoor Unit Floor standing unit FVQ C 9 Sound data 9 1 Sound Pressure Spectrum ...

Page 13: ...t is copyrighted by Daikin Europe N V Daikin s unique position as a manufacturer of air conditioning equipment compressors and refrigerants has led to its close involvement in environmental issues For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment This challenge demands the eco design and development of a wide ...

Reviews: