6 Piping installation

Installation manual

6

FTXTA30C2V1B(W)(B)

Daikin room conditioner

3P697375-7H – 2023.09

5.2.3

To remove the pipe port cover

INFORMATION

To  connect  the  piping  on  right-side,  right-bottom,  left-side
or left-bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.3

Connecting the drain piping

5.3.1

To connect the piping on right side, right-
back, or right-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.

2

Wrap  the  drain  hose  and  the  refrigerant  pipes  together  using
insulation tape.

A

B

a b

A

Right-side piping

B

Right-bottom piping

C

Right-back piping

a

Remove the pipe port cover here for right side piping

b

Remove the pipe port cover here for right-bottom piping

5.3.2

To connect the piping on left side, left-
back, or left-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Remove  the  insulation  fixing  screw  on  the  right  side  and
remove the drain hose.

2

Remove the drain plug on the left side and attach it to the right
side.

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant piping bottom side using
adhesive vinyl tape.

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping

b

Remove the pipe port cover here for left-bottom piping

5.3.3

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

Summary of Contents for FTXTA30C2V1BB

Page 1: ...Installation manual Daikin room conditioner English Installation manual Daikin room conditioner FTXTA30C2V1BW FTXTA30C2V1BB...

Page 2: ...mote control 10 11 Disposal 10 12 Technical data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 10 1 About the documentation 1 1 About this document WARNING Make sure installation serv...

Page 3: ...n site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NO...

Page 4: ...rsons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause faulty be...

Page 5: ...a a a a h 610 605 555 k j i a Recommended mounting plate fixing spots g Value for tape measure b Pocket for the pipe port cover h Position for tape measure at symbol c Use tape measure as shown i Drai...

Page 6: ...side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fi...

Page 7: ...as possible 1 Connect refrigerant piping to the unit using flare connections 2 Wrap the refrigerant piping connection using vinyl tape overlapping at least half the width of the tape with each turn Ke...

Page 8: ...ce between both wirings should ALWAYS be at least 50 mm Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice 1...

Page 9: ...the pipe path marking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT...

Page 10: ...the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 10...

Page 11: ...KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of pas...

Page 12: ...3P697375 7H 2023 09 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Reviews: