5 Unit installation

Installation manual

5

FTXTA30C2V1B(W)(B)
Daikin room conditioner
3P697375-7H – 2023.09

Note: 

Make  sure  that  there  are  no  obstacles  within  500  mm  under

the  infrared  signal  receiver.  They  may  influence  reception
performance of the wireless remote control.

5.2

Mounting the indoor unit

5.2.1

To install the mounting plate

1

Install the mounting plate temporarily.

2

Level the mounting plate.

3

Mark  the  centres  of  the  drilling  points  on  the  wall  using  a  tape
measure. Position the end of tape measure at symbol " ".

4

Finish the installation by securing the mounting plate on the wall
using M4×25L screws (field supply).

INFORMATION

The removed pipe port cover can be kept in the mounting
plate pocket.

(mm)

44.5

605

17

110

798

150

155

44.5

 

Ø65

Ø65

d

g

g

a

e

d

a

f

f

b

c

a

a

a

a

a

a

h

± 610

± 605

± 555

k

j

i

a

Recommended mounting plate fixing spots

g

Value for tape measure

b

Pocket for the pipe port cover

h

Position for tape measure at symbol " "

c

Use tape measure as shown

i

Drain hose

d

Tabs for placing a spirit level

j

Liquid pipe

e

Unit center

k

Gas pipe

f

Hole for embedded piping Ø65 mm

5.2.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

Summary of Contents for FTXTA30C2V1BB

Page 1: ...Installation manual Daikin room conditioner English Installation manual Daikin room conditioner FTXTA30C2V1BW FTXTA30C2V1BB...

Page 2: ...mote control 10 11 Disposal 10 12 Technical data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 10 1 About the documentation 1 1 About this document WARNING Make sure installation serv...

Page 3: ...n site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NO...

Page 4: ...rsons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause faulty be...

Page 5: ...a a a a h 610 605 555 k j i a Recommended mounting plate fixing spots g Value for tape measure b Pocket for the pipe port cover h Position for tape measure at symbol c Use tape measure as shown i Drai...

Page 6: ...side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fi...

Page 7: ...as possible 1 Connect refrigerant piping to the unit using flare connections 2 Wrap the refrigerant piping connection using vinyl tape overlapping at least half the width of the tape with each turn Ke...

Page 8: ...ce between both wirings should ALWAYS be at least 50 mm Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice 1...

Page 9: ...the pipe path marking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT...

Page 10: ...the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 10...

Page 11: ...KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of pas...

Page 12: ...3P697375 7H 2023 09 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Reviews: