Field Settings
SiBE041213E
109
Tips for Servicing
42 Class
You can expand the operation range to –15°C by cutting the jumper on the outdoor unit PCB. If
the outdoor temperature falls to –20°C or lower, the operation stops. If the outdoor temperature
rises, the operation starts again.
50 Class
You can expand the operation range to –10°C by cutting the jumper (J6) on the outdoor unit
PCB. If the outdoor temperature falls to –18°C or lower, the operation stops. If the outdoor
temperature rises, the operation starts again.
Caution
1. If the outdoor unit is installed where the outdoor heat exchanger of the unit is exposed to
direct wind, provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew condensation from the indoor unit outlet vent.
4. Cutting the jumper sets the indoor fan tap to the highest position.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
J3
J4
J5
J7
PCB
Hook
Fan motor lead wire
(R18346)
Remove the
electrical box
cover from the
hook.
Cut the jumper J4.
(You can cut the
jumper with the
PCB mounted.)
(R18276)
GND
Cut the jumper J6.
J5
J7
J8
J6
Summary of Contents for FTXS35K2V1B
Page 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49...
Page 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition...