Indoor Unit Installation

3-2. Left-side, left-back, or left-bottom piping

How to replace the drain plug and drain hose

• 

Replacing onto the left side

1) Remove the insulation fixing screw on the right 

and remove the drain hose.

2) Remove the drain plug on the left side and 

attach it to the right side.

3) Insert the drain hose and tighten with included 

insulation fixing screw.
* (Forgetting to tighten this may cause water 

leakages.)

Drain hose attachment position

* The drain hose is on the back of the unit.

Front side of unit

Attachment on the right side (factory default)

Attachment on the left side

Drain hose

Drain hose

Insulation 

fixing screw

Insulation 

fixing screw

Right side

Left side

1) Attach the drain hose to the underside of the refrigerant pipes 

with adhesive vinyl tape.

Remove pipe port cover here for left-bottom piping.

Remove pipe 
port cover 
here for left-
side piping.

Left-bottom piping

Left-side 
piping
Left-back 
piping

2) Be sure to connect the drain hose to the drain port in place of a 

drain plug.

How to set drain plug

No gap.

Do not apply lubricating 
oil (refrigeration oil) 
when inserting.
Application of causes 
deterioration and drain 
leakage of the plug.

Insert a hexagonal wrench (4mm).

3) Shape the refrigerant pipe along the pipe 

path marking on the mounting plate.

4) Pass drain hose and refrigerant pipes 

through the wall hole, then set the indoor 
unit on mounting plate hooks, using the   
markings at the top of indoor unit as a 
guide.

5) Pull in the inter-unit wire.
6) Connect the inter-unit pipes.

Drain 

hose

Caulk this hole 

with putty or 

caulking material.

Bind with adhesive 
vinyl tape.

 A Mounting plate

Wrap insulating tape around the 
bent portion of refrigerant pipe. 
Overlap at least half the width of 
the tape with each turn.

7) Wrap the refrigerant pipes and drain hose together with insulation tape 

as right figure, in case of setting the drain hose through the back of the 
indoor unit.

8) While exercising care so that the inter-unit wire do not catch indoor unit, 

press the bottom edge of indoor unit with both hands until it is firmly 
caught by the mounting plate hooks. Secure indoor unit to the mounting 
plate with indoor unit fixing screws (M4 × 12L).

Refrigerant
pipes

Drain hose

Bottom frame

F  Indoor unit fixing screw

  (M4 × 12L) (2 points)

Mounting
plate

A

Inter-unit wire

3-3. Wall embedded piping

Follow the instructions given under left-side, left-back, or left-bottom piping.
1) Insert the drain hose to this depth so it won’t be pulled out of the drain 

pipe.

Inner wall

Vinyl chloride 
drain pipe 
(VP-30)

Drain hose

50mm 
or more

Insert drain hose 
to this depth so 
it won’t be pulled 
out of drain pipe.

Outer wall

01_EN_3P297034-1.indd   7

10/12/2011   11:37:03 AM

Summary of Contents for FTXS20K2V1B

Page 1: ...1B DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Installationsanleitung Manuel dinstallation Installatiehandleiding Manual de instalaci n Manuale dinstallazion...

Page 2: ...ltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 1 FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Ce...

Page 3: ...ldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B 3SB65451 2 Shinri Sada Manager Quality Control Department 3SB65451 2 fm Page 1 Thursday October 2...

Page 4: ...3SB65451 2 fm Page 2 Thursday October 27 2011 4 43 PM...

Page 5: ...iring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or ove...

Page 6: ...t in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shorten indoor unit life 6 cool warm air is circulated througho...

Page 7: ...mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand Upper hook mark area 3 locations...

Page 8: ...Service lid is opening closing type Opening method 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be ins...

Page 9: ...ll hole 65mm 2 Boring a wall hole and installing wall embedded pipe For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the feed through hole to preve...

Page 10: ...ere for right side piping Remove pipe port cover here for right bottom piping 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by...

Page 11: ...g the pipe path marking on the mounting plate 4 Pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the top of indoor uni...

Page 12: ...locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to...

Page 13: ...the connection cord as shown in Figure 3 5 8 Install the electrical component box in its original position 1 Install the electrical component box 1 screw 2 Install the thermistor in its original posit...

Page 14: ...ly available rigid polyvinyl chloride pipe nominal diameter 13mm Drain hose supplied with the indoor unit 18 Refrigerant Piping Work 1 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remo...

Page 15: ...rotect the open end of the pipe against dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no are cap is available cover the are mouth with tape t...

Page 16: ...original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the system 2 Press TEMP button 2 locations and MODE button at...

Page 17: ...Two dimensional bar code is a code for manufacturing 3P297034 1 M11B099 1111 HT 00_CV_3P297034 1 indd 2 10 31 2011 2 09 38 PM...

Reviews: