• Remove the pipe port cover as shown below.

1) Cut off the pipe port cover from inside the front grille using a copping 

saw. 
Apply the blade of the copping saw to the notch, and cut off the pipe 
port cover along the slit.

2) After cutting off the pipe port cover, perform filing. Remove the burrs 

along the cut section using a half round needle file.

CAUTION

• If the pipe port cover is cut off using nippers, the front grille will be damaged. Please do not use nippers.
• Wear gloves during the pipe port cover removal.

3-1. Right-side, right-back, or right-bottom piping

1) Attach the drain hose to the underside of the refrigerant pipes with 

adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with insulation 

tape.

Right-bottom 
piping

Right-back piping

Bind coolant pipe 
and drain hose 
together with 
insulating tape.

Remove pipe port cover 
here for right-side piping.

Remove pipe port cover 
here for right-bottom piping.

3) Pass the drain hose and refrigerant pipes through the wall hole, 

then set the indoor unit on the mounting plate hooks by using the 
markings at the top of the indoor unit as a guide.

Mounting plate

A

4) Open the front panel, then open the service lid.  

(Refer to preparation before installation.)

5) Pass the inter-unit wire from the outdoor unit through the 

feed-through wall hole and then through the back of the indoor 
unit. Pull them through the front side. Bend the ends of tie 
wires upward for easier work in advance. (If the inter-unit wire 
ends are to be stripped first, bundle wire ends with adhesive 
tape.)

6) Press the bottom frame of the indoor unit with both hands to 

set it on the mounting plate hooks. Make sure the wires do not 
catch on the edge of the indoor unit.

Wire guide

When stripping the 
ends of inter-unit wire 
in advance, bind right ends 
of wires with insulating tape.

Hang indoor unit’s hook here.

Inter-unit wire

Mounting plate

A

01_EN_3P297034-1.indd   6

10/12/2011   11:37:02 AM

Summary of Contents for FTXS20K2V1B

Page 1: ...1B DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Installationsanleitung Manuel dinstallation Installatiehandleiding Manual de instalaci n Manuale dinstallazion...

Page 2: ...ltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 1 FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Ce...

Page 3: ...ldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B 3SB65451 2 Shinri Sada Manager Quality Control Department 3SB65451 2 fm Page 1 Thursday October 2...

Page 4: ...3SB65451 2 fm Page 2 Thursday October 27 2011 4 43 PM...

Page 5: ...iring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or ove...

Page 6: ...t in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shorten indoor unit life 6 cool warm air is circulated througho...

Page 7: ...mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand Upper hook mark area 3 locations...

Page 8: ...Service lid is opening closing type Opening method 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be ins...

Page 9: ...ll hole 65mm 2 Boring a wall hole and installing wall embedded pipe For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the feed through hole to preve...

Page 10: ...ere for right side piping Remove pipe port cover here for right bottom piping 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by...

Page 11: ...g the pipe path marking on the mounting plate 4 Pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the top of indoor uni...

Page 12: ...locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to...

Page 13: ...the connection cord as shown in Figure 3 5 8 Install the electrical component box in its original position 1 Install the electrical component box 1 screw 2 Install the thermistor in its original posit...

Page 14: ...ly available rigid polyvinyl chloride pipe nominal diameter 13mm Drain hose supplied with the indoor unit 18 Refrigerant Piping Work 1 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remo...

Page 15: ...rotect the open end of the pipe against dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no are cap is available cover the are mouth with tape t...

Page 16: ...original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the system 2 Press TEMP button 2 locations and MODE button at...

Page 17: ...Two dimensional bar code is a code for manufacturing 3P297034 1 M11B099 1111 HT 00_CV_3P297034 1 indd 2 10 31 2011 2 09 38 PM...

Reviews: