TROUBLE SHOOTING

Trouble Shooting

These cases are not troubles.

The following cases are not air conditioner troubles but have some reasons. You may just continue using it.

Case

Explanation

Operation does not start soon.

When ON/OFF button was pressed soon 
after operation was stopped.

When the mode was reselected.

This is to protect the air conditioner.
You should wait for about 3 minutes.

Hot air does not flow out soon after the 
start of heating operation.

The air conditioner is warming up. 
You should wait for 1 to 4 minutes.

Makes a noise.

Clicking sound can be heard either when the unit is running or stopped

This is either the sound of the valves regulating the refrigerant or the electrical parts working.

Sound of running water

Refrigerant is flowing through the air conditioner.

Blowing sound

The flow of refrigerant through the air conditioner is switching.

Creaking sound

The air conditioner itself is expanding or shrinking due to a change in the humidity.

Clopping sound

Can be heard coming from inside the air conditioner when the ventilator is on and the room 
is shut. Open a window or turn off the ventilator.

Clicking sound can be heard either when the unit is running or stopped

This is the sound of the electrical parts working when the front panel opens or closes.

Blowing, cracky or burning sound

This is the sound of streamer discharging.

Fizzes during HUMIDIFYING or 
VENTILATING operation.

This is the sound of humidified or ventilated air being discharged.

The operation noise may change depending on the outdoor temperature and humidity.

Makes a sound during HUMIDIFYING 
operation.

Operation noise changes

This is because the fan for humidification moves or stops.

The indoor unit makes a noise even after 
HUMIDIFYING operation is stopped.

The fan for humidification rotates for about 3 minutes after the operation stops for product pro-
tection.

Units stops during HEATING and the 
sound of running water can be heard.

The frost on the outdoor unit is being removed. You should wait for about 3 to 10 minutes.

The outdoor unit emits water or steam.

In HEATING operation

The frost on the outdoor unit melts into water or steam when the air conditioner is in defrost operation.

In COOLING operation

Moisture in the air condenses into water on the cool surface of outdoor unit piping and drips.

Mist comes out of the indoor unit.

This happens when the air in the room is cooled into mist by the cold air flow during COOLING operation.

This is because moisture on the heat exchanger evaporates when “SARARA” DRYING opera-
tion is run after COOLING or DRY COOLING operation.

The indoor unit gives out odor.

This happens when smells of the room, furniture, or cigarettes are absorbed into the unit and 
discharged with the air flow.
(If this happens, we recommend you to have the indoor unit washed by a technician. Consult 
the service shop where you bought the air conditioner.)

The outdoor odor may be captured. Stop the “URURU” HUMIDIFYING operation to eliminate 
the cause of odor.

Cold air blows at the start of “SARARA” 
DRYING operation.

This is because the air conditioner is not warmed up.

The outdoor fan rotates while the air con-
ditioner is not in operation.

After operation is stopped:

The outdoor fan continues rotating for another 60 seconds for system protection.

While the air conditioner is not in operation:

When the outdoor temperature is very high, the outdoor fan starts rotating for system protection.

The operation stopped suddenly.
(Multi-colored indicator lamp is on.)

For system protection, the air conditioner may stop operating on a sudden large voltage fluctu-
ation. It automatically resumes operation in about 3 minutes.

Unit stops suddenly (when in ON TIMER 
mode).

Reserving the on timer will cause the unit to start running up 1 hour before, in order to make 
sure the temperature reaches the temperature set on the remote controller by the set time. 
Using the remote controller during this time (other than the operation/stop button) will stop the 
unit. Restart the unit with the remote controller.

Unit operates even though the multi-
colored indicator lamp is off.

The multi-colored indicator lamp will go off if “Monitor OFF” is set using the remote controller.

Unit continues to operate even after 
“SARARA” DRYING, DRY COOLING or 
COOLING operation is stopped.

The MOLD PROOF operation will start. (If you don’t want it, set to “MOLD PROOF OFF” using 
the remote controller. (page 15.))

Room lamp flickers during HUMIDIFYING 
operation.

It might happen the flickers of lighting in the case of insufficient power supply.

01_EN_3P190650-1D.fm  Page 25  Tuesday, March 6, 2007  6:26 PM

Summary of Contents for FTXR50EV1B9

Page 1: ...Deutsch Fran ais Nederlands Espa ol Italiano Portugues English T rk e FTXR28EV1B9 FTXR42EV1B9 FTXR50EV1B9 MODELS DAIKIN ROOM AIR CONDITIONER Operation Manual...

Page 2: ...TURIZING Operation 9 ADJUSTING AIRFLOW DIRECTION COMFORT AIRFLOW MODE COOLING BREEZE AIRFLOW RATE 10 FLASH STREAMER AIR PURIFYING FRESH AIR SUPPLY VENTILATION Operation 11 HOME LEAVE VENTILATION 11 TI...

Page 3: ...jury do not remove the fan guard Do not place anything under the indoor or outdoor unit that must be kept away from moisture In certain conditions moisture in the air may condense and drip After a lon...

Page 4: ...cording to the optional function FLASH STREAMER AIR PURIFYING FRESH AIR SUPPLY VENTILATION White Only for the first 2 seconds during operation of the air conditioner 17 TIMER lamp Orange page 12 18 MO...

Page 5: ...humidity setting 10 FLASH STREAMER AIR PURIFYING FRESH AIR SUPPLY VENTILATION button Cleans the room air page 11 11 AIRFLOW DIRECTION AIRFLOW RATE COMFORT AIRFLOW COOLING BREEZE button Adjusts air di...

Page 6: ...peration i e when the panel is open or being opened or closed do not touch the panel with your hands ATTENTION PRECAUTION Wrap the terminals with tape to insulate them before discarding batteries Mixi...

Page 7: ...When the outdoor temperature is below 15 C turn on the breaker more than 1 hour before starting the operation This is to warm up the compressor Operating conditions Running the unit under conditions...

Page 8: ...Yellow 18 C 32 C 3 C STD OFF HIGH STD LOW CONT HIGH STD LOW CONT DRY COOLING DRY NOTE Note on ON OFF button Pressing will start the same operation as the last time Note on COOLING operation This air c...

Page 9: ...on it takes some time before the room gets warmer In HEATING operation frost may occur on the outdoor unit and lower the HEATING capacity In that case the system switches into defrost ing operation to...

Page 10: ...page 7 8 Humidity and airflow rate cannot be changed To change the airflow direction page 10 The recommended airflow direction is COMFORT AIRFLOW MODE but it can be changed To cancel the MOISTURIZING...

Page 11: ...plays COOLING BREEZE operation Indication disappears Operating mode SARARA DRYING DRY COOLING MOISTURIZING AUTO COOLING HEATING HUMID HEATING URURU HUMIDIFYING FLASH STREAMER AIR PURIFYING FRESH AIR S...

Page 12: ...FYING operation The streamer discharge energy and Titanium apatite photocatalytic air purifying fil ter clean the air in the room Note on FRESH AIR SUPPLY VENTILATION operation Fresh air is taken from...

Page 13: ...nit to automatically change the set temperature 1 hour later to prevent the room from becoming too cold or too hot Turns up 0 5 C during COOLING or DRY COOLING and turns down 2 C during HEATING or HUM...

Page 14: ...ORT SLEEP operation Can be used for COOLING DRY COOLING MOISTURE COOLING HEATING HUMID HEATING and MOISTURE HEATING Cannot be used with TIMER operation How to use COMFORT SLEEP operation effectively S...

Page 15: ...dren See NOTE If the unit is set to MOLD PROOF ON it may automatically enter MOLD PROOF operation mode after operating in DRYING DRY COOLING or COOLING operation mode depending on the amount of time i...

Page 16: ...alternately Purple Blue Blinks alternately Blue Light blue Blinks alternately Light blue White White In case of manual operation 1 2 The MOLD PROOF operation will start The display will return to nor...

Page 17: ...uced when the humidity is below 60 Note on INFORMATION DISPLAY The signal from the air conditioner is not being received properly if Reception Failed is displayed when you press Repeat aiming the remo...

Page 18: ...e the unit is not operating the filter cleaning indicator may be displayed on the remote controller depending the amount of time the unit had been operating This sign indicates the cleaning timing for...

Page 19: ...ning for each case Wipe it with a soft cloth soaked in water Only neutral detergent may be used In case of washing the front panel with water dry it with cloth dry it up in the shade after washing CAU...

Page 20: ...s with water or clean them with vacuum cleaner If the dust does not come off easily wash them with neutral detergent thinned with lukewarm water then dry them up in the shade 4 Set the air filter as i...

Page 21: ...er in a downward direction 5 Replace the streamer unit to its original position Attach the streamer unit in opposite procedure to removing 3 6 Attach the deodorizing filter for streamer Insert the deo...

Page 22: ...queeze the filter to drain away water 1 Soak in warm water with mild liq uid detergent for about 1 hour Observe the volume of mild liquid detergent specified in the instruction Do not use powder or al...

Page 23: ...another hand Disassemble the streamer unit into the plastic cover and the discharge plate Match up the securing parts of the various parts of the streamer unit and assemble as it was CAUTION The deod...

Page 24: ...nal position 5 Set the Titanium apatite photocatalytic air purifying filter and the air filter as they were and close the front panel page 19 20 CAUTION Cleaning the indoor unit and the remote control...

Page 25: ...utdoor unit are not decayed or corroded Check that nothing blocks the air inlets and the outlets of the indoor unit and the outdoor unit Check that the drain comes smoothly out of the drain hose durin...

Page 26: ...air conditioner is in defrost operation In COOLING operation Moisture in the air condenses into water on the cool surface of outdoor unit piping and drips Mist comes out of the indoor unit This happen...

Page 27: ...d the outdoor units Is the temperature setting appropriate Are the windows and doors closed Are the air flow rate and the air direction set appropriately Is the ventilator fan spinning An abnormal fun...

Page 28: ...Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation In certain operating conditions the inside of the air conditi...

Page 29: ...AULTY SUCTION AIR TEMPERATURE SENSOR UA HOSE LENGTH NOT SET OUTDOOR UNIT EA COOLING HEATING SWITCHING FAULT E1 CIRCUIT BOARD FAULT E5 OL STARTED E6 FAULTY COMPRESSOR START UP E7 DC FAN MOTOR FAULT E8...

Page 30: ...3P190650 1D M06B102D 0704 HT Two dimensional bar code is a code for manufacturing...

Reviews: