4 Preparation

Installation manual

6

(A)(F)TXP20~3 FTXF20~3 FTXF20~25B5V1B

Daikin room air conditioner

3P519299-1H – 2019.09

(a)

A safety device might stop the operation of the system.

(b)

Condensation might occur on the indoor unit and drip.

4

Preparation

4.1

Preparing the installation site

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

4.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

Air flow.

 Make sure nothing blocks the air flow.

Drainage.

  Make  sure  condensation  water  can  be  evacuated

properly.

Wall insulation

. When conditions in the wall exceed 30°C and a

relative  humidity  of  80%,  or  when  fresh  air  is  inducted  into  the
wall,  then  additional  insulation  is  required  (minimum  10  mm
thickness, polyethylene foam).

Wall  strength. 

Check  whether  the  wall  or  the  floor  is  strong

enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥30

(mm)

4.2

Preparing refrigerant piping

4.2.1

Refrigerant piping requirements

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Class

L1 liquid piping

L1 gas piping

20~35

Ø6.4

Ø9.5

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

4.2.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

5

Installation

5.1

Opening the units

5.1.1

To open the indoor unit

To remove the front panel

1

Hold the front panel by the panel tabs on both sides and open
it.

a

a

Panel tabs

2

Remove  the  front  panel  by  sliding  it  to  the  left  or  the  right  and
pulling it toward you.

Result: 

The front panel shaft on 1 side will be disconnected.

3

Disconnect  the  front  panel  shaft  on  the  other  side  in  the  same
manner.

a

Summary of Contents for FTXP35L5V1B

Page 1: ...l Daikin room air conditioner English Installation manual Daikin room air conditioner FTXP20L5V1B FTXP25L5V1B FTXP35L5V1B ATXP20L5V1B ATXP25L5V1B ATXP35L5V1B FTXF20A5V1B FTXF25A5V1B FTXF35A5V1B FTXF20...

Page 2: ...atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem un...

Page 3: ...odytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem un citiem normat vie...

Page 4: ...na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus normi...

Page 5: ...ep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial...

Page 6: ...horic acid deoxidised seamless copper for refrigerant Foreign materials inside pipes including oils for fabrication must be 30 mg 10 m Refrigerant piping diameter Use the same diameters as the connect...

Page 7: ...s 20 35 back on the front grille 3 Install the air filter and then mount the front panel To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring...

Page 8: ...Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a wall cover into the wall pipe 65 a b c a Wall embedde...

Page 9: ...arly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electric...

Page 10: ...ory f Bottom frame 5 5 2 To pass the pipes through the wall hole 1 Shape the refrigerant pipes along the pipe path marking on the mounting plate a b c c d e a Drain hose b Caulk this hole with putty o...

Page 11: ...tallation of the unit first check the items listed below Once all checks are fulfilled the unit must be closed Power up the unit after it is closed You read the complete installation instructions as d...

Page 12: ...ng the air conditioner in Cooling mode in winter set it to test run operation using the following method For FTXP and ATXP units 1 Press and simultaneously 2 Press 3 Select 4 Press 5 Press to switch t...

Page 13: ...DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE...

Page 14: ......

Page 15: ......

Page 16: ...TEMLER SAN T C A STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P519299 1H 2...

Reviews: