Electrical

DANGER: RISK OF ELECTROCUTION

▪ Turn  OFF  all  power  supply  before  removing  the

switch  box  cover,  connecting  electrical  wiring  or
touching electrical parts.

▪ Disconnect  the  power  supply  for  more  than  1  minute,

and measure the voltage at the terminals of main circuit
capacitors  or  electrical  components  before  servicing.
The  voltage  MUST  be  less  than  50  V  DC  before  you
can touch electrical components. For the location of the
terminals, see the wiring diagram.

▪ Do NOT touch electrical components with wet hands.

▪ Do  NOT  leave  the  unit  unattended  when  the  service

cover is removed.

WARNING

If  NOT  factory  installed,  a  main  switch  or  other  means  for
disconnection,  having  a  contact  separation  in  all  poles
providing  full  disconnection  under  overvoltage  category  III
condition, MUST be installed in the fixed wiring.

WARNING

▪ ONLY use copper wires.

▪ Make sure the field wiring complies with the applicable

legislation.

▪ All field wiring MUST be performed in accordance with

the wiring diagram supplied with the product.

▪ NEVER  squeeze  bundled  cables  and  make  sure  they

do  NOT  come  in  contact  with  the  piping  and  sharp
edges. Make sure no external pressure is applied to the
terminal connections.

▪ Make sure to install earth wiring. Do NOT earth the unit

to  a  utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earth may cause electrical shock.

▪ Make  sure  to  use  a  dedicated  power  circuit.  NEVER

use a power supply shared by another appliance.

▪ Make  sure  to  install  the  required  fuses  or  circuit

breakers.

▪ Make sure to install an earth leakage protector. Failure

to do so may cause electric shock or fire.

▪ When installing the earth leakage protector, make sure

it  is  compatible  with  the  inverter  (resistant  to  high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.

NOTICE

Precautions when laying power wiring:

▪ Do  NOT  connect  wiring  of  different  thicknesses  to  the

power  terminal  block  (slack  in  the  power  wiring  may
cause abnormal heat).

▪ When  connecting  wiring  which  is  the  same  thickness,

do as shown in the figure above.

▪ For wiring, use the designated power wire and connect

firmly,  then  secure  to  prevent  outside  pressure  being
exerted on the terminal board.

▪ Use  an  appropriate  screwdriver  for  tightening  the

terminal  screws.  A  screwdriver  with  a  small  head  will
damage  the  head  and  make  proper  tightening
impossible.

▪ Over-tightening the terminal screws may break them.

WARNING

▪ After  finishing  the  electrical  work,  confirm  that  each

electrical  component  and  terminal  inside  the  electrical
components box is connected securely.

▪ Make sure all covers are closed before starting up the

unit.

NOTICE

Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.

If  there  exists  the  possibility  of  reversed  phase  after  a
momentary black out and the power goes on and off while
the  product  is  operating,  attach  a  reversed  phase
protection  circuit  locally.  Running  the  product  in  reversed
phase can break the compressor and other parts.

2

About the documentation

2.1

About this document

INFORMATION

Make sure that the user has the printed documentation and
ask him/her to keep it for future reference.

Target audience

Authorised installers

INFORMATION

This appliance is intended to be used by expert or trained
users  in  shops,  in  light  industry,  and  on  farms,  or  for
commercial and household use by lay persons.

Documentation set

This  document  is  part  of  a  documentation  set.  The  complete  set
consists of:

General safety precautions:

▪ Safety instructions that you MUST read before installing

▪ Format: Paper (in the box of the indoor unit)

Indoor unit installation manual:

▪ Installation instructions

▪ Format: Paper (in the box of the indoor unit)

Summary of Contents for FTXP20L2V1B

Page 1: ...kin room air conditioner English Installer reference guide Daikin room air conditioner FTXP20L2V1B FTXP25L2V1B FTXP35L2V1B ATXP20L2V1B ATXP25L2V1B ATXP35L2V1B FTXF20A2V1B FTXF25A2V1B FTXF35A2V1B FTXF50A2V1B FTXF60A2V1B FTXF71A2V1B ...

Page 2: ...nt piping to the indoor unit 17 6 4 Connecting the electrical wiring 17 6 4 1 About connecting the electrical wiring 17 6 4 2 Precautions when connecting the electrical wiring 17 6 4 3 Guidelines when connecting the electrical wiring 17 6 4 4 Specifications of standard wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 18 7 Commissioning 18 7 1 Overview Commissioning 18...

Page 3: ...lace at the product Instructions for shutting down the system in case of an emergency Name and address of fire department police and hospital Name address and day and night telephone numbers for obtaining service In Europe EN378 provides the necessary guidance for this logbook 1 2 2 Installation site Provide sufficient space around the unit for servicing and air circulation Make sure the installat...

Page 4: ...0 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 400 410 420 430 440 450 460 470 480 490 500 510 520 530 540 550 1 1 2 1 4 1 6 1 8 2 2 2 2 4 2 6 2 8 3 3 2 3 4 3 6 3 8 4 4 2 4 4 4 6 4 8 5 5 2 5 4 5 6 5 8 6 6 2 6 4 6 6 6 8 7 7 2 7 4 7 6 7 8 7 956 Amin m2 F l o o r s t a n d i n g u n i t c Wall mounted unit b ...

Page 5: ...opened refrigerant MUST be treated according to the applicable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe si...

Page 6: ...ith the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do NOT connect wiring of different thicknesses to the power terminal block slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as shown in the figure above For wiring use the designate...

Page 7: ... over to the user What to give and explain to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This chapter describes what you have to do after the box with the indoor unit is delivered on site It contains information about Unpacking and handling the units Removing the accessories from...

Page 8: ...heater 5 2 1 Installation site requirements of the indoor unit INFORMATION Also read the precautions and requirements in the General safety precautions chapter INFORMATION The sound pressure level is less than 70 dBA Air flow Make sure nothing blocks the air flow Drainage Make sure condensation water can be evacuated properly Wall insulation When conditions in the wall exceed 30 C and a relative h...

Page 9: ...lyethylene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter Øp Insulation inner diameter Øi Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm 12 7 mm 1 2 14 16 mm 15 9 mm 5 8 16 20 mm Øi Øi t Øp Øp If the temperature is higher than 30 C and...

Page 10: ...afety precautions Preparation 6 2 2 To open the indoor unit To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Indentation on the unit 2 Remove the front panel by sliding it to the left or the right and pulling it toward you Result The front panel shaft on 1 side will be disconnected 3 Disconnect the front panel shaft on the other side in the same mann...

Page 11: ...late 3 Finish the installation by securing the mounting plate on the wall using screws 4 Use a tape measure Position the end of tape measure at symbol INFORMATION The removed pipe port cover can be kept in the mounting plate pocket 337 770 A A 285 44 5 170 48 48 44 5 116 5 117 337 50 213 237 170 a h a a g a a d c b c e a f 990 295 170 60 170 44 5 44 5 122 121 5 56 5 56 5 404 475 PIPING HOLE CENTER...

Page 12: ... any burrs along the cut section using a half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this would damage the front grille 7 Remove the drain plug from the drain port and connect the drain hose to the port NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug a ...

Page 13: ...ge 10 6 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side In case the interconnection cable was stripped in advance cover the ends with insulating tape 7 Bend the end of the cable up 8 Press the bottom frame of the unit with both hands to set it on the bottom hooks of the mounting Make sure that th...

Page 14: ... for water leaks 1 Remove the air filters 2 Gradually pour approximately 1 l of water in the drain pan and check for water leaks 6 2 6 To connect optional accessories wired user interface central user interface wireless adapter etc 1 Remove the electrical wiring box cover refer to To remove the electrical wiring box cover on page 10 2 Attach the connection cable to the S21 connector and pull the w...

Page 15: ...Model Button FTXP L and ATXP L FTXF A ON OFF a b a Operation lamp b Indoor unit ON OFF switch 8 Press the indoor unit ON OFF switch while the operation lamp is blinking Jumper Address Factory setting 1 After cutting with nippers 2 INFORMATION If the setting could NOT be completed while the operation lamp was blinking repeat the setting process from the beginning 9 When the setting is complete pres...

Page 16: ...refrigerant piping Take the following guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten 3 or 4 turns by hand before tightening firmly ALWAYS use 2 wrenches together when loosening a flare nut ALWAYS use a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut...

Page 17: ...G ALWAYS use multicore cable for power supply cables WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts inside the product Do NOT branch t...

Page 18: ...tions as described in the installer reference guide The indoor units are properly mounted The outdoor unit is properly mounted Air inlet outlet Check that the air inlet and outlet of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Make sure drainage flows ...

Page 19: ...NFORMATION Some of the functions CANNOT be used in the test run operation mode If a power failure occurs during operation the system automatically restarts immediately after power is restored 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure the following is clear for the user Make sure that the user has the printed documentation and ask him her ...

Page 20: ... EARTH LEAKCIRCUIT BREAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PIL...

Page 21: ...roduct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories Labels m...

Page 22: ......

Page 23: ......

Page 24: ...4P513661 1 2017 10 Copyright 2017 Daikin ...

Reviews: