Piping Works And Flaring Technique

Do not use contaminated or damaged copper tubing. If 
any piping, evaporator or condenser had been exposed or 
had been opened for 15 seconds or more, the system must 
be vacuumed. Generally do not remove plastic, rubber 
plugs and brass nuts from the valves, fittings, tubing and 
coils until it is ready to connect suction or liquid line into 
valves or fittings.
If any brazing work is required, ensure that nitrogen gas 
is passed through coil and joints while the brazing work 
is being done. This will eliminate soot formation on the 
inside wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of pipe 
cutter slowly. Extra force and a deep cut will cause more 
distortion of pipe and therefore extra burr. See Figure I.
Remove burrs from cut edges of the pipes with remover. See 
Figure II. Hold the pipe on top position and burr remover 
at lower position to prevent metal chips from entering the 
pipe. This will avoid unevenness on the flare faces which 
will cause gas leak.
Insert the flare nuts, mounted on the connection parts 
of both the indoor unit and outdoor unit, into the copper 
pipes.
The exact length of pipe protruding from the top surface 
of the swaging block is determined by the flaring tool. 
See Figure III.
Fix the pipe firmly on the swaging block. Match the centers 
of both the swaging block and the flaring punch, then 
tighten the flaring punch fully.
The refrigerant pipe connection are insulated by closed 
cell polyurethane.

Piping Connection To The Units

Align the center of the piping and tighten the flare nut 
sufficiently with fingers. See Figure IV.
Finally, tighten the flare nut with torque wrench until the 
wrench clicks.
When tightening the flare nut with the torque wrench, 
ensure that the tightening direction follows the arrow 
indicated on the wrench.
The refrigerant pipe connection are insulated by closed 
cell polyurethane.

1/4t

Cutting Copper Tube

Copper Tube

Swaging Block

Remove Burr

Figure I

D

A

Pipe Size, mm (in)

Torque, Nm/(ft-lb)

6.35 (1/4")

18 (13.3)

9.52 (3/8")

42 (31.0)

12.70 (1/2") 

55 (40.6)

15.88 (5/8") 

65 (48.0)

19.05 (3/4") 

78 (57.6)

Flared Tube

Flare Joint

Flare Nut

Indoor Piping

Torque Wrench

Spanner

Ø Tube, D

A (mm)

Inch

mm

Imperial 

(Wing-nut Type)

Rigid 

(Clutch Type)

1/4"

6.35

1.3

0.7

3/8"

9.52

1.6

1.0

1/2"

12.70

1.9

1.3

5/8"

15.88

2.2

1.7

3/4"

19.05

2.5

2.0

REFRIGERANT PIPING

Figure II

Figure III

Figure IV

1 IM-5WMYJ-1113(2)DK_EN-39396B.i11   11

1 IM-5WMYJ-1113(2)DK_EN-39396B.i11   11

4/23/14   12:02:15 PM

4/23/14   12:02:15 PM

Summary of Contents for FTXN25MV1B

Page 1: ...FTK35JXV1 RK35FXV1 FTK50JXV1 RK50CXV1 FTK60JXV1 RK60CXV1 Installation Manual R410A Split Series Manuale d installazione Serie Multiambienti R410A Installationsanleitung Split Baureihe R410A Manual de...

Page 2: ...CVR IM 5WMYJ 1113 2 DK EN 39396B2 2 CVR IM 5WMYJ 1113 2 DK EN 39396B2 2 4 23 14 12 07 15 PM 4 23 14 12 07 15 PM...

Page 3: ...R INSIDE NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL F E J G G L D B K M A Gas pipe end INSTALLATION PLATE 25 35 Liquid pipe end Through the wall hole 65mm All dimensions are in mm Drain hose positi...

Page 4: ...mm Drain hose position Liquid pipe end Gas pipe end INSTALLATION PLATE 50 60 Recommended mounting plate retention spots 7 spots in all All dimensions are in mm Recommended mounting plate retention spo...

Page 5: ...XN RK All dimensions are in mm Dimension Model A B C D E F G H I J K L M N 50 60 855 730 328 520 179 46 93 149 101 113 603 126 164 15 All dimensions are in mm Dimension Model O P Q R S T U V 50 60 34...

Page 6: ...melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep flouraway from going into suction of the unit This unit is not suitable for factory used where...

Page 7: ...the inside of the service cover factory refrigerant charge of the product see unit name plate 2 additional refrigerant amount charged in the field total refrigerant charge contains fluorinated greenho...

Page 8: ...ove the service lid screws 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down 500mm from wall Where a wall or other obstacle is in the path of outdoor unit s intake o...

Page 9: ...the upper part of the unit please allow more space than the figure indicated in the above table Dimension A B C D Minimum Distance mm 300 1000 300 500 Condensed Water Disposal Of Outdoor Unit Heat Pum...

Page 10: ...the side and bottom out hold the bottom of the piping and then position it to the required direction The condensation drain hose can be taped to the pipes Right side right back or right bottom piping...

Page 11: ...25 35 FTK 25 35 When stripping the ends of interconnecting wires in advance bind right ends of wires with insulating tape Hand indoor unit s hook here Mounting plate Interconnecting wires Wire guide...

Page 12: ...IGERANT PIPING Additional Charge The refrigerant is pre charged in the outdoor unit If the piping length is less than 7 5m then additional charge after vacuuming is not necessary If the piping length...

Page 13: ...pes The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool See Figure III Fix the pipe firmly on the swaging block Match the centers of both th...

Page 14: ...terminal connectors and wires Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal block Connect the wires by...

Page 15: ...from the valve and the service port Connect the center of the charging gauge to the vacuum pump Connect the charging gauge to the service port of the 3 way valve Start the vacuum pump Evacuate for app...

Page 16: ...ows the LED indicator lights for the air conditioner unit under normal operation and fault conditions The LED indicator lights are located at the side of the air conditioner unit The heat pump units a...

Page 17: ...EMP CWB Heat Pump Model INDOOR TEMP CDB OPERATING RANGE DB Dry bulb WB Wet bulb DB Dry bulb WB Wet bulb Model FTXN 25 35 RXN 25 35 20 15 0 3 7 2 5 2 0 1 20 18 10 0 10 15 20 50 46 43 40 30 20 10 10 14...

Page 18: ...hildren If you keep this Bio Filter for a long time please keep it unopened and store in a cool place avoiding direct sunlight Please dispose the old Bio Filter as nonflammable garbage after use Opera...

Page 19: ...Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water below 40 C 104 F with a neutral cleaning detergent Rinse the filter well and dry before placing it back onto...

Page 20: ...h might have adhered onto the coil Condensation on the front air grille of the indoor unit 5 This is caused by air humidity after an extended long period of operation The set temperature is too low in...

Page 21: ...de este manual y en su traducci n a cualquier idioma prevalecer la versi n inglesa El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y dise os contenidos en el present...

Reviews: