background image

EDUS041111_a

Installation Manual

Room Air Conditioners K-Series

61

Summary of Contents for FTXN09KEVJU

Page 1: ...EDUS041111_a K Series Cooling Only Heat Pump SEER 18 Models...

Page 2: ...Unit 15 6 Piping Diagrams 16 6 1 Indoor Unit 16 6 2 Outdoor Unit 17 7 Capacity Tables 19 7 1 Cooling Only 19 7 2 Heat Pump 24 7 3 Capacity Correction Factor by the Length of Refrigerant Piping Referen...

Page 3: ...ass 81 12 Operation Manual 93 12 1 Safety Considerations 09 12 Class 93 12 2 Safety Considerations 15 18 24 Class 122 13 Optional Accessories 149 13 1 Option List 149 13 2 BRC944B2 Wired Remote Contro...

Page 4: ...Indoor Unit Outdoor Unit Power Supply Single Split Duct Free System FTXN09KEVJU RKN09KEVJU 1 208 230 V 60 Hz FTXN12KEVJU RKN12KEVJU FTXN15KVJU RKN15KEVJU FTXN18KVJU RKN18KEVJU FTXN24KVJU RKN24KEVJU F...

Page 5: ...o Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check Function COMFORT AIRFLOW Operation Anti Corrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan...

Page 6: ...Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display COMFORT AIRFLOW Operation Wiring Error Check Function Comfort Control Auto Fan Speed Anticorrosion Treatment of Outdoor Heat...

Page 7: ...Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 20 0 18 0 20 0 18 Power Consumption Rated W 40 40 Power Factor 96 2 96 6 96 2 96 6 Temperature Con...

Page 8: ...ble Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 0 17 0 15 Power Consumption Rated W 34 34 34 34 Power Factor 96 2 98 6 96 2 98 6 Temperature Control Microco...

Page 9: ...Control Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 Power Consumption Rated W 34 34 Power Factor 96 2 98 6 Temperature Control Microcomp...

Page 10: ...eps Quiet Auto Air Direction Control Right Left Horizontal Downward Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0...

Page 11: ...orizontal Downward Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 0 18 0 16 0 17 0 15 0 18 0 16 Power Consu...

Page 12: ...Direction Control Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 0 18 0 16 Power Consumption Rated W 34 34 36 36 Power Factor 96 2 98 6 96...

Page 13: ...m FAN WALL HOLE FOR EMBEDDED PIPING RIGHT LEFT MANUAL 2 9 16 65mm HOLE WALL HOLE 5 2 9 16 65mm HOLE STANDARD LOCATIONS OF WALL HOLES WIRELESS REMOTE CONTROLLER 45 45 45 ARC452A19 3D065951C AIR FLOW IN...

Page 14: ...E 3 8 9 5 CuT 5 7 8 150 5 7 8 150 3 15 16 100 1 15 16 50 3 15 16 100 1 15 16 50 1 15 16 50 1 15 16 50 UNIT INCH mm 11 13 16 300 3D071564A WALL HEIGHT ON AIR OUTLET SIDE MINIMUM SPACE FOR AIR PASSAGE L...

Page 15: ...1 PCB3 R1T R2T NOTE S6 S602 S21 S1W 1 PCB3 SHOWS THE CASE OF X1M OPTION CONNECTION PCB 3 OPTION FRAME GROUND FUSE HARNESS PILOT LAMP FAN MOTOR SWING MOTOR PRINTED CIRCUIT BOARD THERMISTOR CONNECTOR OP...

Page 16: ...LK 1 3 BLK GRY BLK BLK BLK BLK BLK BLK YEL RED BLU BRN RED ORG ORG WHT S80 BLU 3 1 RED YLW t t t S80 Q1L MS NOTE M V 3 IN CASE OF 1 REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS U R1T R3T R2T W RE...

Page 17: ...9 32CuT 3 16CuT 9 32CuT THERMISTOR ON HEAT EXCH 9 32CuT 9 32CuT CROSS FLOW FAN FIELD PIPING 1 4CuT M FAN MOTOR 3 8CuT FIELD PIPING 3 8CuT REFRIGERANT FLOW COOLING HEATING 4D066211A INDOOR UNIT 5 16CuT...

Page 18: ...OUTDOOR AIR TEMPERATURE 5 16CuT THERMISTOR 5 16CuT 16 0 5 8CuT 5 16CuT 12 0 15 32CuT CAPILLARY TUBE 1 5 16CuT 5 16CuT 5 32CuT 8 0 4 0 5 16CuT CAPILLARY TUBE 2 6 0 6 0 REFRIGERANT FLOW 5 16CuT 5 32CuT...

Page 19: ...R UNIT 8 0 HEAT EXCHANGER OUTDOOR AIR TEMPERATURE 5 16CuT THERMISTOR 5 16CuT 16 0 5 8CuT 5 16CuT 12 0 15 32CuT CAPILLARY TUBE 1 5 16CuT 5 32CuT 5 16CuT 4 0 8 0 5 16CuT CAPILLARY TUBE 2 6 0 6 0 REFRIGE...

Page 20: ...68 8 21 5 62 0 71 7 96 5 42 0 74 7 54 5 09 0 75 60 8 71 6 9 64 6 43 0 58 9 22 6 07 0 63 8 80 5 73 0 69 8 63 5 59 0 71 8 38 5 40 0 75 7 96 5 08 0 75 64 4 77 0 10 05 6 48 0 58 9 63 6 14 0 64 9 21 5 81 0...

Page 21: ...0 98 7 94 5 44 1 03 60 8 71 6 10 62 7 44 0 81 10 62 7 44 0 92 10 62 7 44 1 04 10 62 7 44 1 09 10 62 7 44 1 16 10 61 7 43 1 21 64 4 77 0 13 40 9 95 0 94 12 84 9 31 1 03 12 28 8 70 1 12 12 06 8 47 1 15...

Page 22: ...1 19 13 84 10 50 1 24 13 14 10 20 1 25 64 4 77 0 16 63 12 06 0 97 15 93 11 76 1 06 15 23 11 46 1 15 14 95 11 34 1 19 14 53 11 17 1 25 13 83 10 88 1 26 67 0 80 0 17 11 12 12 0 97 16 41 11 84 1 07 15 71...

Page 23: ...1 42 16 60 11 92 1 49 15 77 11 53 1 50 64 4 77 0 19 95 13 70 1 16 19 11 13 32 1 27 18 27 12 95 1 38 17 94 12 81 1 43 17 43 12 59 1 50 16 60 12 23 1 51 67 0 80 0 20 53 13 73 1 17 19 69 13 38 1 28 18 85...

Page 24: ...2 43 20 28 13 67 2 54 17 81 12 48 2 38 64 4 77 0 24 37 15 75 1 98 23 35 15 26 2 17 22 32 14 78 2 36 21 91 14 59 2 44 21 30 14 31 2 55 18 74 13 16 2 38 67 0 80 0 25 08 15 74 1 99 24 06 15 28 2 18 23 03...

Page 25: ...08 0 75 64 4 77 0 10 05 6 48 0 58 9 63 6 14 0 64 9 21 5 81 0 69 9 04 5 68 0 72 8 79 5 49 0 75 8 37 5 18 0 76 67 0 80 0 10 26 6 56 0 58 9 84 6 23 0 64 9 42 5 91 0 69 9 25 5 78 0 72 9 00 5 60 0 75 8 58...

Page 26: ...tables Figures out of the tables should not be used for calculation 4 About SHC which are not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are base...

Page 27: ...0 13 40 9 95 0 94 12 84 9 31 1 03 12 28 8 70 1 12 12 06 8 47 1 15 11 72 8 13 1 21 11 16 7 58 1 22 67 0 80 0 13 68 10 04 0 94 13 12 9 41 1 03 12 56 8 81 1 12 12 34 8 58 1 16 12 00 8 24 1 21 11 44 7 70...

Page 28: ...tables Figures out of the tables should not be used for calculation 4 About SHC which are not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are base...

Page 29: ...12 06 0 97 15 93 11 76 1 06 15 23 11 46 1 15 14 95 11 34 1 19 14 53 11 17 1 25 13 83 10 88 1 26 67 0 80 0 17 11 12 12 0 97 16 41 11 84 1 07 15 71 11 56 1 16 15 43 11 45 1 19 15 00 11 28 1 25 14 31 11...

Page 30: ...not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level differe...

Page 31: ...70 1 16 19 11 13 32 1 27 18 27 12 95 1 38 17 94 12 81 1 43 17 43 12 59 1 50 16 60 12 23 1 51 67 0 80 0 20 53 13 73 1 17 19 69 13 38 1 28 18 85 13 03 1 39 18 52 12 89 1 43 18 00 12 68 1 50 17 18 12 34...

Page 32: ...not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level differe...

Page 33: ...1 98 23 35 15 26 2 17 22 32 14 78 2 36 21 91 14 59 2 44 21 30 14 31 2 55 18 74 13 16 2 38 67 0 80 0 25 08 15 74 1 99 24 06 15 28 2 18 23 03 14 82 2 37 22 62 14 64 2 45 22 00 14 37 2 56 19 40 13 25 2...

Page 34: ...not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level differe...

Page 35: ...ordance with the length of refrigerant piping the distance between the indoor unit and the outdoor unit line cooling capacity line heating capacity 7 3 1 09 12 Class 7 3 2 15 18 Class Capacity correct...

Page 36: ...Conditioners K Series 35 7 3 3 24 Class Note The graphs show the factor when additional refrigerant of the proper quantity is charged 1 16 4 32 8 49 2 65 6 82 0 R 410A 24 class Piping length ft Range...

Page 37: ...nt piping length 25ft Level difference 0m Air flow rate High 4D071134 Note Operation can be extended to 0 F in cooling with use of the optional wind baffle Cooling 122 114 8 104 86 68 50 Outdoor temp...

Page 38: ...length 25ft Level difference 0m Air flow rate High Note Operation can be extended to 0 F in cooling with use of the optional wind baffle 3D072084a Heating 68 64 4 59 50 41 32 Outdoor temp FWB 23 Conti...

Page 39: ...und is measured in an anechoic chamber 2 The data are based on the conditions shown in the table below Indoor Unit Single Split Duct Free System Outdoor Unit 3 3 ft 2 6 ft R5162 3 3 ft R4796 Cooling H...

Page 40: ...H 60Hz 208 230V L 208 230V 41 60Hz H 208 230V 60Hz 208 230V 29 60Hz L POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED STANDARD EXTERNAL STATIC PRESSURE S...

Page 41: ...40 NC 30 NC 20 Cooling 60Hz 208 230V 208 230V 60Hz POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED 60Hz 53 208 230V H OCTAVE BAND SOUND PRESSURE LEVEL dB...

Page 42: ...g POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED 60Hz 53 208 230V H 208 230V 60Hz 60Hz 208 230V 3D071283 NC 60 NC 60 NC 50 NC 50 NC 40 NC 40 NC 30 NC 30...

Page 43: ...U RXN09KEVJU 60 208 MAX 60 Hz 253 V MIN 60 Hz 187 V 4 8 15 4 1 33 0 19 16 0 20 60 230 3 7 0 17 0 18 FTXN12KEVJU RXN12KEVJU 60 208 MAX 60 Hz 253 V MIN 60 Hz 187 V 7 0 15 6 1 33 0 19 16 0 20 60 230 5 5...

Page 44: ...materials used for transportation may cause injuries or death by suffocation Only qualified personnel must carry out the installation work Installation must be done in accordance with this installatio...

Page 45: ...rmal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or ra...

Page 46: ...sound 9 no laundry equipment is located Mounting plate 1 Remote controller holder 1 Operation manual 1 Mounting plate fixing screw 3 16 1 M4 25mm 6 Fixing screw for remote controller holder 1 8 13 16...

Page 47: ...n there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you In...

Page 48: ...the mounting plate If the claws are difficult to hook remove the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is...

Page 49: ...ting plate retention spots and dimensions The removed pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate Use tape measure as shown Position the end of a...

Page 50: ...e 2 Wrap the refrigerant pipes and drain hose together with insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by us...

Page 51: ...on fixing screws on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing scr...

Page 52: ...nduit Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire 5 When connecting to a wired remote controller If work space is available on the right side of the indo...

Page 53: ...accessory separate product into the indoor unit electrical component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position...

Page 54: ...mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use part...

Page 55: ...pipe s surface temperature reaches 230 F 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation...

Page 56: ...he air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power con...

Page 57: ...must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the...

Page 58: ...t transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possibl...

Page 59: ...Installation Manual EDUS041111_a 58 Room Air Conditioners K Series Accessories...

Page 60: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 59...

Page 61: ...Installation Manual EDUS041111_a 60 Room Air Conditioners K Series...

Page 62: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 61...

Page 63: ...Installation Manual EDUS041111_a 62 Room Air Conditioners K Series...

Page 64: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 63...

Page 65: ...Installation Manual EDUS041111_a 64 Room Air Conditioners K Series...

Page 66: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 65...

Page 67: ...Installation Manual EDUS041111_a 66 Room Air Conditioners K Series...

Page 68: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 67 3P276866 2...

Page 69: ...must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the...

Page 70: ...t transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possibl...

Page 71: ...Manual EDUS041111_a 70 Room Air Conditioners K Series Accessories Accessories Accessories supplied with the outdoor unit A Installation manual 1 B Drain plug Heat pump models There is on the bottom pa...

Page 72: ...e may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle plate on the air discharge side of the outdoor unit In heavy snowfall areas select an installation s...

Page 73: ...ace Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is...

Page 74: ...e torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them...

Page 75: ...h 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressu...

Page 76: ...oam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 230 F 110 C max Choose heat insulation materials that will...

Page 77: ...terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close the gas stop valve within 3 minutes then stop the forced operation Facility Setting...

Page 78: ...e screws The screws are packed with the terminal board Work before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection pl...

Page 79: ...C to 28 C 3 For protection the system disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functi...

Page 80: ...l must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing th...

Page 81: ...t transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possibl...

Page 82: ...E Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent expo...

Page 83: ...Installation Manual EDUS041111_a 82 Room Air Conditioners K Series...

Page 84: ...tion drawing fi foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their length are 3 4 inch 20mm from the foundation surface 3...

Page 85: ...e Liquid side 1 4 inch 6 4mm 15 9 20 2ft Ibf 21 6 27 4N m Gas side 1 2 inch 12 7mm 35 5 44 0ft Ibf 48 1 59 7N m Service port cap tightening torque 7 9 10 8ft lbf m N 7 4 1 8 0 1 Do not apply refrigera...

Page 86: ...g 0 1MPa 1 3 Close gauge manifold s low pressure valve Lo and stop vacuum pump 4 Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 Remove ca...

Page 87: ...s 7 2 When using commercial copper pipes and fi Insulation material Polyethylene foam 1 Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Refrigerant gas pipe s sur...

Page 88: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 87...

Page 89: ...rminal screws securely We recommend a fl screwdriver be used to tighten the screws Work before wiring A protection plate is fi Before staring wiring work dismount the protection plate by removing the...

Page 90: ...art back up once the temperature rises again Remove the 3 screws on the side and remove the top plate of the outdoor unit 1 Remove the drip proof cover 2 Cut the jumper J6 of the PCB inside 3 J5 J7 J8...

Page 91: ...accordance with the operation manual to ensure that all functions and parts 1 3 such as fi The air conditioner requires a small amount of power in its standby mode If the system is not to be used for...

Page 92: ...serious injury or death Be sure to ventilate the room sufficiently to avoid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may caus...

Page 93: ...as they can cut and cause injury Do not place objects in direct proximity of the outside unit Do not let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which...

Page 94: ...t there are no obstacles close to the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dea...

Page 95: ...Operation Manual EDUS041111_a 94 Room Air Conditioners K Series...

Page 96: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 95...

Page 97: ...Operation Manual EDUS041111_a 96 Room Air Conditioners K Series...

Page 98: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 97...

Page 99: ...Operation Manual EDUS041111_a 98 Room Air Conditioners K Series...

Page 100: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 99...

Page 101: ...Operation Manual EDUS041111_a 100 Room Air Conditioners K Series...

Page 102: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 101 14 115 14 115...

Page 103: ...Operation Manual EDUS041111_a 102 Room Air Conditioners K Series...

Page 104: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 103...

Page 105: ...Operation Manual EDUS041111_a 104 Room Air Conditioners K Series...

Page 106: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 105...

Page 107: ...Operation Manual EDUS041111_a 106 Room Air Conditioners K Series...

Page 108: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 107...

Page 109: ...Operation Manual EDUS041111_a 108 Room Air Conditioners K Series...

Page 110: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 109...

Page 111: ...Operation Manual EDUS041111_a 110 Room Air Conditioners K Series...

Page 112: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 111...

Page 113: ...Operation Manual EDUS041111_a 112 Room Air Conditioners K Series...

Page 114: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 113...

Page 115: ...Operation Manual EDUS041111_a 114 Room Air Conditioners K Series...

Page 116: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 115...

Page 117: ...Operation Manual EDUS041111_a 116 Room Air Conditioners K Series...

Page 118: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 117...

Page 119: ...Operation Manual EDUS041111_a 118 Room Air Conditioners K Series...

Page 120: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 119 3P272441 1...

Page 121: ...oid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging ba...

Page 122: ...ot let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which can enter the unit Once inside the unit animals can cause the unit to malfunction and cause smoke...

Page 123: ...the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dealer if the air conditioner or heat...

Page 124: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 123...

Page 125: ...Operation Manual EDUS041111_a 124 Room Air Conditioners K Series...

Page 126: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 125...

Page 127: ...Operation Manual EDUS041111_a 126 Room Air Conditioners K Series...

Page 128: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 127...

Page 129: ...Operation Manual EDUS041111_a 128 Room Air Conditioners K Series...

Page 130: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 129...

Page 131: ...Operation Manual EDUS041111_a 130 Room Air Conditioners K Series 14 115 F 14 115 F...

Page 132: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 131...

Page 133: ...Operation Manual EDUS041111_a 132 Room Air Conditioners K Series...

Page 134: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 133...

Page 135: ...Operation Manual EDUS041111_a 134 Room Air Conditioners K Series...

Page 136: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 135...

Page 137: ...Operation Manual EDUS041111_a 136 Room Air Conditioners K Series When it is dirty wipe it gently with a water soaked cloth...

Page 138: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 137...

Page 139: ...Operation Manual EDUS041111_a 138 Room Air Conditioners K Series...

Page 140: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 139...

Page 141: ...Operation Manual EDUS041111_a 140 Room Air Conditioners K Series...

Page 142: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 141...

Page 143: ...Operation Manual EDUS041111_a 142 Room Air Conditioners K Series...

Page 144: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 143...

Page 145: ...Operation Manual EDUS041111_a 144 Room Air Conditioners K Series...

Page 146: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 145...

Page 147: ...Operation Manual EDUS041111_a 146 Room Air Conditioners K Series 3P276856 2...

Page 148: ...ontroller Kit 26 ft 1 BRC944B2 A08 2 Interface Adaptor for Wired Remote Controller KRP980B1 3 Centralized Control Board Up to 5 Rooms 2 KRC72 4 Wiring Adapter for Timer Clock Remote Controller 3 Norma...

Page 149: ...oard or the adapter board 5 Keep the wiring away from any other power source lines to avoid electric noise external noise 6 Select a flat surface wherever possible to mount the remote controller To pr...

Page 150: ...tape Double face adhesive tape Attached five wire cord Remote controller cord Note 1 Connector Connector Connector Tie band to secure the cord Tie band to secure the cord Tie band to secure the cord U...

Page 151: ...Adjusts the temperature setting Airflow rate button Adjusts the airflow rate Time setting button for the timer Display Timer select button Displays the operating conditions Clock setting button page...

Page 152: ...energy Clean the air filter monthly every two weeks as required or so Please take note of the following points Electric power is consumed even when the air conditioner is not in operation When the un...

Page 153: ...dication is changed to Celsius one the temperature value 0 5 C will be rounded up Thus the preset temperature may be changed Example A preset temperature of 65 F equivalent to 18 5 C will be changed t...

Page 154: ...een Automatic DRY Heating Cooling DRY Cooling Cooling only model Heat pump model To stop the operation Press again The run indicator lamp goes out In Automatic the temperature setting and operation mo...

Page 155: ...uring heating operation the heating capacity is decreased In this case the unit starts defrosting operation No hot air comes out of the indoor unit during defrosting operation To adjust the temperatur...

Page 156: ...ntroller Do not forcibly adjust louvers by hand or a malfunction may occur Adjusting Airflow Direction 1 Press during operation Each time the button is pressed the airflow direction louvers change the...

Page 157: ...ight and left The vertical airflow direction louvers stop just when the button is pressed Swing horizontally Swing vertically Airflow direction louvers stop The vertical and horizontal louvers cannot...

Page 158: ...inute has passed before making any timer setting the previous timer settings are reintroduced and the timer is on standby In this case use the time setting button and make your desired timer settings...

Page 159: ...or decrement Hold the button down to advance quickly When the ON timer is not used save the setting as 4 Press 5 Press to make the OFF timer setting 6 Press The ONE TIME timer is now programmed Both...

Page 160: ...ammed ONE TIME timer DAILY timer TIMER OFF The timer lamp lights up 1 2 1 2 ON time 24 hour timer display OFF time Timers The settings of timers and can be seen at a glance Two pairs of ON and OFF tim...

Page 161: ...pears lights up 3 Press The DAILY timer is now programmed Note If the following appears on the display the timer must be reprogrammed The 24 hour timer display is blinking The 24 hour timer display is...

Page 162: ...When the unit is not used for a long time On a sunny day keep the system running for half a day in the FAN mode to dry it up inside 3 1 2 FAN mode 1 Press to select the cooling mode 2 Press to adjust...

Page 163: ...lure Group control i e the control a number of indoor units through a single remote controller Monitoring of the following items Indoor temperature and operating conditions of thermo compressor indoor...

Page 164: ...tabs Place both hands under the center of the front grille and while pushing up pull it toward you Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of...

Page 165: ...grille 3 Remove the service lid of the indoor unit 4 Remove the cover of the electrical component cover 1 Remove the flap in control of wind directions upward and downward 2 Disconnect the communicati...

Page 166: ...rough the cut out of the set and mount the electrical component cover to the original position 4 Insert the connector of the set into the S403 in the indoor unit electrical component connector Then ro...

Page 167: ...Optional Accessories EDUS041111_a 166 Room Air Conditioners K Series 13 4 KRP413AB1S Wiring Adaptor for Timer Clock Remote Controller...

Page 168: ...EDUS041111_a Optional Accessories Room Air Conditioners K Series 167...

Page 169: ...Optional Accessories EDUS041111_a 168 Room Air Conditioners K Series...

Page 170: ...EDUS041111_a Optional Accessories Room Air Conditioners K Series 169 3P248024 2...

Page 171: ...Optional Accessories EDUS041111_a 170 Room Air Conditioners K Series 13 5 KRP928BB2S Interface Adaptor for DIII NET Residential Air Conditioner...

Page 172: ...EDUS041111_a Optional Accessories Room Air Conditioners K Series 171 3P248024 1A...

Page 173: ...Optional Accessories EDUS041111_a 172 Room Air Conditioners K Series Connection to Remote Control PC board 3P248024 3B...

Page 174: ...ing conditions When installing near the border to a neighbor s house If exhaust blows directly on passers by because outdoor unit is installed facing a road Changing the fan direction of the outdoor u...

Page 175: ...airflow direction to prevent exhaust blowing directly onto passersby or garden plants M4 x 30 Screw 4 pcs 4 pcs Installation manual One sheet this sheet Seal 1 pc Spacer 1 Install the air direction a...

Page 176: ...le aligning the center of each part s hole At 4 positions Be careful that the spacer does not come off before it is fixed to the front panel with screws 1 Remove the 4 outlet grille fixing screws 2 Af...

Page 177: ...Optional Accessories EDUS041111_a 176 Room Air Conditioners K Series...

Page 178: ...is product conforms tot he applicable standards and is suitable for use in the region where the product will be used This statement does not purport to exclude restrict or modify the application of an...

Reviews: