background image

12

English

Indoor Unit Installation

6.

Drain piping.

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water flows 

smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of hose front end]

4) When extending the drain hose, use a commercially available 

extension hose with an inner diameter of 16mm. Be sure to 
thermally insulate the indoor section of the extension hose.

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with 
embedded piping work, use any commercially 
available drain socket (nominal diameter 13mm) 
as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

ø18

ø16

ø16

The drain hose provided 
to indoor unit.

Indoor unit 
drain hose

ø16

Extension drain hose

Heat insulation tube
(Field supply)

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe 
(nominal diameter 13mm)

The drain hose provided 
to indoor unit.

ø18

A

A

(Cut exactly at 
right angles.)

Remove burrs.

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

(Ri

d

gid-type)

1.5-2.0mm

(Imperial-type)

Conventional flare tool

Summary of Contents for FTXL25J2V1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models FTXL25J2V1B FTXL35J2V1B ATXL25J2V1B ATXL35J2V1B DAIKIN...

Page 2: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 3: ...may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections o...

Page 4: ...ite where remote controller signals are properly received by the indoor unit within 7 metres CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In...

Page 5: ...d push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the centr...

Page 6: ...panel 50mm or more from walls on both sides Air filters Titanium apatite deodorizing filter 2 Air filter Titanium apatite deodorizing filter Filter frame Tab Service lid Opening service lid The servi...

Page 7: ...the wall with screws Recommended mounting plate retention spots and Dimensions Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liqu...

Page 8: ...pes keep the following precautions in mind Abnormal sound may be generated if improper work is conducted 1 Do not strongly press the refrigerant pipes onto the bottom frame 2 Do not strongly press the...

Page 9: ...the back of the indoor unit Pull them through the front side Bend the ends of tie wires upward for easier work in advance If the interconnecting wire ends are to be stripped first bundle wire ends wi...

Page 10: ...to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it to the...

Page 11: ...IRCUIT BREAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER...

Page 12: ...e 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps inv...

Page 13: ...ct into the indoor unit electrical component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Ins...

Page 14: ...rly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous...

Page 15: ...Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide i...

Page 16: ...cessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P377527 2D 2017 02 Copyright 2014 Daikin...

Reviews: