8 Finishing the indoor unit installation

Installation Manual

11

FTXF20~42C5V1B 
Daikin room air conditioners
3P519299-9X – 2020.12

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

7.1

Specifications of standard wiring
components

Component

Power supply cable Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

Must comply with

applicable legislation

Interconnection cable

Minimum cable section of

2.5 mm² and applicable

for 220~240 V

Recommended field fuse

20 A

Earth leakage circuit breaker

Must comply with

applicable legislation

7.2

To connect the electrical wiring to
the indoor unit

Electrical  work  should  be  carried  out  in  accordance  with  the
installation manual and the national electrical wiring rules or code of
practice.

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

b

a

c

a

Mounting plate (accessory)

b

Interconnection cable

c

Wire guide

2

Open  the  front  panel,  and  then  the  service  cover.  Refer  to

"5.2 Opening the indoor unit"

 [

4

 6].

3

Pass  the  interconnection  cable  from  the  outdoor  unit  through
the  feed-through  wall  hole,  through  the  back  of  the  indoor  unit
and through the front side.

Note: 

  In  case  the  interconnection  cable  was  stripped  in  advance,

cover the ends with insulating tape.

4

Bend the end of the cable up.

NOTICE

▪ Be  sure  to  keep  the  power  line  and  transmission  line

apart  from  each  other.  Transmission  wiring  and  power
supply wiring may cross, but may NOT run parallel.

▪ In order to avoid any electrical interference the distance

between  both  wirings  should  ALWAYS  be  at  least
50 mm.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

a
b

c

a

Terminal block

b

Electrical component block

c

Cable clamp

5

Strip the wire ends approximately 15 mm.

6

Match  wire  colours  with  terminal  numbers  on  the  indoor  unit
terminal blocks and firmly screw the wires to the corresponding
terminals.

7

Connect the earth wire to the corresponding terminal.

8

Firmly fix the wires with the terminal screws.

9

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the wire retainer.

10

Shape  the  wires  so  that  the  service  cover  fits  securely,  then
close the service cover.

8

Finishing the indoor unit
installation

8.1

To insulate the drain piping,
refrigerant piping and
interconnection cable

1

After the drain piping, refrigerant piping and the electrical wiring
are  finished.  Wrap  refrigerant  pipes,  interconnection  cable  and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

Summary of Contents for FTXF20C5V1B

Page 1: ...Installation Manual Daikin room air conditioners English Installation Manual Daikin room air conditioners FTXF20C5V1B FTXF25C5V1B FTXF35C5V1B FTXF42C5V1B...

Page 2: ...vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbils...

Page 3: ...m a test run in winter season 14 11 Disposal 14 12 Technical data 15 12 1 Wiring diagram 15 12 1 1 Unified wiring diagram legend 15 1 About the documentation 1 1 About this document INFORMATION Make s...

Page 4: ...ay cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Cha...

Page 5: ...witch box cover before turning on the power supply Commissioning see 10 Commissioning 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING CAUTION Do NOT perform the test operation while w...

Page 6: ...oor and keep the following requirements in mind for distances from the walls and the ceiling 50 50 30 mm 5 1 2 Additional installation site requirements of the outdoor unit in cold climates Protect th...

Page 7: ...the centres of the drilling points on the wall using a tape measure Position the end of tape measure at symbol 4 Finish the installation by securing the mounting plate on the wall using M4 25L screws...

Page 8: ...a field supplied hose with inner 16 mm Do NOT forget to use a heat insulation tube on the indoor section of the extension hose a a b c 16 16 a Drain hose supplied with the indoor unit b Heat insulatio...

Page 9: ...check for water leaks 6 Piping installation 6 1 Preparing refrigerant piping 6 1 1 Refrigerant piping requirements NOTICE The piping and other pressure containing parts shall be suitable for refriger...

Page 10: ...ection cable d Liquid pipe e Liquid pipe insulation f Finishing tape g Drain hose NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 3 Checking the refri...

Page 11: ...ning the indoor unit 46 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Note In case the interc...

Page 12: ...Note Take care that the interconnection cable does NOT get caught in the indoor unit 3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4...

Page 13: ...matches the voltage on the identification label of the unit The specified wires are used for the interconnection cable The indoor unit receives the signals of the user interface There are NO loose con...

Page 14: ...automatically restarts immediately after power is restored For FTXF ATXF CTXF units 1 Press to switch the system on 2 Press the centre of and simultaneously 3 Press twice Result will appear on the dis...

Page 15: ...D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode Symb...

Page 16: ...on Manual 16 FTXF20 42C5V1B Daikin room air conditioners 3P519299 9X 2020 12 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferri...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P519299 9X 2020 12 Copyright 20...

Reviews: