5 Unit installation

Installation Manual

7

FTXF20~42C5V1B 
Daikin room air conditioners
3P519299-9X – 2020.12

1

2

5.2.4

To re-install the front grille

1

Install the front grille and firmly engage the 3 upper hooks.

2

Install 2 screws (class 20~42) back on the front grille.

3

Install the air filter and then mount the front panel.

5.2.5

To remove the electrical wiring box cover

1

Remove the front grille.

2

Remove 1 screw from the electrical wiring box.

3

Open  the  electrical  wiring  box  cover  by  pulling  the  protruding
part on the top of the cover.

4

Unhook the tab on the bottom and remove the electrical wiring
box cover.

a

a

c

b

a

1

3

2

a

Tab

b

Protruding part on the top of the cover

c

Screw

5

To  re-install  the  cover,  first  hook  the  bottom  tab  onto  the
electrical wiring box, and slide the cover into the 2 upper tabs.

5.2.6

To open the service cover

1

Remove 1 screw from the service cover.

2

Pull out the service cover horizontally away from the unit.

a

b

a

Service cover screw

b

Service cover

5.3

Mounting the indoor unit

5.3.1

To install the mounting plate

1

Install the mounting plate temporarily.

2

Level the mounting plate.

3

Mark  the  centres  of  the  drilling  points  on  the  wall  using  a  tape
measure. Position the end of tape measure at symbol " ".

4

Finish the installation by securing the mounting plate on the wall
using M4×25L screws (field supply).

INFORMATION

The removed pipe port cover can be kept in the mounting
plate pocket.

337

770

A

285

44.5

170

48

48

44.5

116.5

117

337

50

213

237

170

A

d

e

(mm)

a

a

f

h g

a

a

b

a

c

a c

a

d

e

A

A

Mounting plate for class 20~42

a

Recommended mounting plate fixing spots

b

Pocket for the pipe port cover

c

Tabs for placing a spirit level

d

Through-the-wall hole Ø65 mm

e

Drain hose position

f

Position for the tape measure at symbol " "

g

Gas pipe end

h

Liquid pipe end

5.3.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

Summary of Contents for FTXF20C5V1B

Page 1: ...Installation Manual Daikin room air conditioners English Installation Manual Daikin room air conditioners FTXF20C5V1B FTXF25C5V1B FTXF35C5V1B FTXF42C5V1B...

Page 2: ...vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbils...

Page 3: ...m a test run in winter season 14 11 Disposal 14 12 Technical data 15 12 1 Wiring diagram 15 12 1 1 Unified wiring diagram legend 15 1 About the documentation 1 1 About this document INFORMATION Make s...

Page 4: ...ay cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Cha...

Page 5: ...witch box cover before turning on the power supply Commissioning see 10 Commissioning 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING CAUTION Do NOT perform the test operation while w...

Page 6: ...oor and keep the following requirements in mind for distances from the walls and the ceiling 50 50 30 mm 5 1 2 Additional installation site requirements of the outdoor unit in cold climates Protect th...

Page 7: ...the centres of the drilling points on the wall using a tape measure Position the end of tape measure at symbol 4 Finish the installation by securing the mounting plate on the wall using M4 25L screws...

Page 8: ...a field supplied hose with inner 16 mm Do NOT forget to use a heat insulation tube on the indoor section of the extension hose a a b c 16 16 a Drain hose supplied with the indoor unit b Heat insulatio...

Page 9: ...check for water leaks 6 Piping installation 6 1 Preparing refrigerant piping 6 1 1 Refrigerant piping requirements NOTICE The piping and other pressure containing parts shall be suitable for refriger...

Page 10: ...ection cable d Liquid pipe e Liquid pipe insulation f Finishing tape g Drain hose NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 3 Checking the refri...

Page 11: ...ning the indoor unit 46 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Note In case the interc...

Page 12: ...Note Take care that the interconnection cable does NOT get caught in the indoor unit 3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4...

Page 13: ...matches the voltage on the identification label of the unit The specified wires are used for the interconnection cable The indoor unit receives the signals of the user interface There are NO loose con...

Page 14: ...automatically restarts immediately after power is restored For FTXF ATXF CTXF units 1 Press to switch the system on 2 Press the centre of and simultaneously 3 Press twice Result will appear on the dis...

Page 15: ...D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode Symb...

Page 16: ...on Manual 16 FTXF20 42C5V1B Daikin room air conditioners 3P519299 9X 2020 12 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferri...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P519299 9X 2020 12 Copyright 20...

Reviews: