English

6

2.

Boring a wall hole and installing wall embedded pipe.

• For walls containing metal frame or metal board, be sure to use a wall 

embedded pipe and wall cover in the feed-through hole to prevent possible 
heat, electrical shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material to prevent 

water leakage.
1) Bore a feed-through hole of 65mm in the wall so it has a down slope 

toward the outside.

2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole 

gap with putty.

3.

Installing indoor unit.

• In the case of bending or curing refrigerant pipes, keep the following 

precautions in mind. 
Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.

3-1. Right-side, right-back, or right-bottom piping. 

1) Attach the drain hose to the underside of the refrigerant pipes with 

an adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with an 

insulation tape.

3) Pass the drain hose and refrigerant pipes through the wall hole, 

then set the indoor unit on the mounting plate hooks by using the   
markings at the top of the indoor unit as a guide.

4) Open the front panel, then open the service lid. 

(Refer to Installation tips)

5) Pass the interconnecting wires from the outdoor unit through the 

feed-through wall hole and then through the back of the indoor 
unit. Pull them through the front side.  Bend the ends of tie wires 
upward for easier work in advance. (If the interconnecting wire 
ends are to be stripped first, bundle wire ends with adhesive 
tape.)

6) Press the bottom frame of the indoor unit with both hands to set 

it on the mounting plate hooks. Make sure the wires do not 
catch on the edge of the indoor unit.

 

  

 

  

 

  

 

φ

1)

2)

Right-bottom 
piping

Right-back piping

Bind coolant pipe 
and drain hose 
together with 
insulating tape.

Remove pipe port cover 
here for right-side piping.

Remove pipe port cover 
here for right-bottom piping.

Mounting plate

A

Wire guide

When stripping the 
ends of interconnecting 
wires in advance, bind 
right ends of wires with 
insulating tape.

Hang indoor unit’s hook here.

Interconnecting
wires

Mounting plate

A

01_EN_3P207973-1D.fm  Page 6  Friday, September 4, 2009  10:44 AM

Summary of Contents for FTX20GV1B

Page 1: ...e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systee...

Page 2: ...TK25GV1B FTK35GV1B FTX20JV1B FTX25JV1B FTX35JV1B DAIKIN INDUSTRIES LTD Shinri Sada Manager Quality Control Department 11th of Sep 2009 Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC...

Page 3: ...lamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Ins...

Page 4: ...ctronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cause in...

Page 5: ...When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you...

Page 6: ...pe hole gap with putty Mounting plate Clip Mark rear side Bottom frame Front grille How to attach the indoor unit Hook the claws of the bottom frame to the mounting plate If the claws are difficult to...

Page 7: ...nting plate retention spots and Dimensions 770 Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liquid pipe end Gas pipe end The rem...

Page 8: ...pipes and drain hose together with an insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at t...

Page 9: ...ove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it to the right...

Page 10: ...n be performed with the electrical component box attached Omit the steps involved with removing and installing the electrical component box in order to perform the work more efficiently 5 1 Remove the...

Page 11: ...omponent box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Install the electrical component box 1...

Page 12: ...vent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with t...

Page 13: ...035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid...

Page 14: ...small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit break...

Page 15: ...0911 HT 3P207973 1D M07B030C Two dimensional bar code is a code for manufacturing 00_CV_3P207973 1D fm Page 2 Friday September 4 2009 10 41 AM...

Reviews: