8

4.

Wiring.

1) Strip wire ends (15mm).
2) Match wire colours with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the corre-

sponding terminals.

3) Connect the earth wires to the corresponding terminals.
4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer.
5) In case of connecting to an adapter system. Run the remote control cable and attach the S21. (Refer to 5. When connecting to a 

wired remote controller.)

6) Shape the wires so that the service lid fits securely, then close service lid.

WARNING

1) Do not use tapped wires, strand wires, extensioncords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

5.

When connecting to a wired remote controller.

* If work space is available on the right side of the indoor unit, the work 

can be performed with the electrical component box attached. Omit the 
steps involved with removing and installing the electrical component 
box in order to perform the work more efficiently.

5-1. Remove the front grille (2 screws).
5-2. Remove the service lid (1 screw).
5-3. Remove the cover from the indoor unit electrical 

component box [Figure 1].

* 5-4. Remove the indoor unit electrical component box.

1) Remove the flap.
2) Disconnect the communication wiring.
3) Disconnect the connector (S200).
4) Remove the thermistor from the heat exchanger.
5) Remove the electrical component box installation screw (1 screw).

1

2

3

Terminal block

Electrical component box

Wire retainer

Use the specified 
wire type.

Shape wires so that the 
service lid will fit securely.

Firmly secure wire retainer so that 
wires sustain no external stress.

1
2
3

1 2 3

L N

When wire length exceeds 
10m, use 2.0mm diameter wires.

H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Firmly fix the wires with 
the terminal screws.

Disengage the tab.

Figure 1: Removing the cover from 

the indoor unit electrical 
component box

Disengage the tab.

Cover of the indoor unit 
electrical component box

01_EN_3P207973-1D.fm  Page 8  Friday, September 4, 2009  10:44 AM

Summary of Contents for FTX20GV1B

Page 1: ...e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systee...

Page 2: ...TK25GV1B FTK35GV1B FTX20JV1B FTX25JV1B FTX35JV1B DAIKIN INDUSTRIES LTD Shinri Sada Manager Quality Control Department 11th of Sep 2009 Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC...

Page 3: ...lamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Ins...

Page 4: ...ctronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cause in...

Page 5: ...When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you...

Page 6: ...pe hole gap with putty Mounting plate Clip Mark rear side Bottom frame Front grille How to attach the indoor unit Hook the claws of the bottom frame to the mounting plate If the claws are difficult to...

Page 7: ...nting plate retention spots and Dimensions 770 Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liquid pipe end Gas pipe end The rem...

Page 8: ...pipes and drain hose together with an insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at t...

Page 9: ...ove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it to the right...

Page 10: ...n be performed with the electrical component box attached Omit the steps involved with removing and installing the electrical component box in order to perform the work more efficiently 5 1 Remove the...

Page 11: ...omponent box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Install the electrical component box 1...

Page 12: ...vent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with t...

Page 13: ...035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid...

Page 14: ...small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit break...

Page 15: ...0911 HT 3P207973 1D M07B030C Two dimensional bar code is a code for manufacturing 00_CV_3P207973 1D fm Page 2 Friday September 4 2009 10 41 AM...

Reviews: