background image

9

English

Refrigerant Piping Work

WARNING

• 

Do not apply mineral oil to the flare.

•  Prevent mineral oil from getting into the system as this would reduce the service life of the units.
•  Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
•  Never install a dryer to this R410A unit in order to guarantee its service life.
•  The drying material may dissolve and damage the system.
• 

Improper flaring may result in refrigerant gas leakage.

1� 

Flaring the pipe end

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward, 

so that the filings do not enter the pipe.

 Remove burrs.

Cut exactly at
right angles.

3) 

Put the flare nut on the pipe.

4) Flare the pipe.
5) 

Check that the flaring has been done correctly.

Set exactly at the position shown below.

Flaring

A

A

0-0.020 inch 

(0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch 

(1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch 

(1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Check

The flare's inner 

surface must be 

flaw-free.

The pipe end must 

be evenly flared in 

a perfect circle.

Make sure that the 

flare nut is fitted.

Die

2� 

Refrigerant piping

CAUTION

• 

Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)

• 

To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)

• 

Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• 

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a 

torque wrench.

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration 

oil only to the inner 

surface of the flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 

with excessive torque.

Apply oil

Torque wrench

Piping union

Flare nut

Spanner

Tighten

Gas side

Piping size

O.D. 

3/8 inch

 (9.5mm)

O.D. 

1/2 inch

 (12.7mm)

O.D. 

5/8 inch

 (15.9mm)

O.D. 

1/4 inch

 (6.4mm)

24-1/8 – 29-1/2Ibf • ft

(32.7-39.9N • m)

36-1/2 – 44-1/2lbf • ft

(49.5-60.3N • m)

45-5/8 – 55-5/8Ibf • ft

(61.8-75.4N • m)

10-1/2 – 12-3/4lbf • ft

(14.2-17.2 N • m)

Flare nut tightening torque

Liquid side

Caution on piping handling

•  Protect the open end of the pipe against dust and moisture.
•  All pipe bends should be as gentle as possible. Use a pipe bender  for bending.

Wall

If no flare cap is 

available, cover 

the flare mouth 

with tape to keep 

dirt and water out.

Be sure to 

place a cap.

Rain

01_EN_3P654325-1B.indd   9

2021/08/27   13:37:34

Summary of Contents for FTX09NMVJUA

Page 1: ...ran ais Espa ol DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n MODELS FTX09NMVJUA FTX12NMVJUA FTX15NMVJUA Manuel dins...

Page 2: ...nce with federal state local laws or ordinances Packing materials such as nails and other metal or wood parts including plastic packing materials used for transportation may cause injuries or death by...

Page 3: ...terials including mineral oils such as SUNISO oil or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not...

Page 4: ...Indoor Unit Installation Diagram on page 4 are met 2 both the air inlet and air outlet are unobstructed 3 the unit is not exposed to direct sunlight 4 Install so that drainage occurs easily 5 the uni...

Page 5: ...release the hooks If it is dif cult to release remove the front grille 1 3 16 30mm or more from ceiling Front panel 1 15 16 50mm or more from walls on both sides Air lters A A The 15 class model has 3...

Page 6: ...etention spots 7 spots in all Place a leveler on these tabs 1 3 4 44 5 1 3 4 44 5 1 7 8 48 11 1 4 286 11 1 4 285 6 11 16 170 1 7 8 48 1 15 16 50 6 11 16 170 4 5 8 116 5 4 5 8 117 13 1 4 337 Drain hose...

Page 7: ...grille either 3 1 Right side right back or right bottom piping 1 Attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape 2 Wrap the refrigerant pipes and drain hose to...

Page 8: ...vinyl tape If any gap is left or if the refrigerant pipe is bound too tightly condensation and dripping may result 5 Open the front panel Refer to Installation Tips on page 10 then open the service li...

Page 9: ...trical wiring box Shape wires so that the service lid ts securely Use the speci ed wire type Illustration may differ from some models Conduit mounting plate Lock nut Conduit Claw Seat the claw onto th...

Page 10: ...ie 2 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a result of deterioration over time To prevent gas leakage apply refrigeratio...

Page 11: ...16 20mm I D 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid side Use separate thermal insulation pipes for g...

Page 12: ...r filters and then mount the front panel 3 How to set the different addresses When 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change...

Page 13: ...ration will stop automatically after about 30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode HEAT PUMP model The air conditioner draws a small amo...

Page 14: ...The two dimensional bar code is a manufacturing code 3P654325 1B M20B289A 2108 HT...

Reviews: