background image

 

FMCQ50~125A8VEB
Air conditioning system
4PW56204-1

Installation and operation manual

8

Complete system example (2 systems)

See figures 

13

 and 

15

When using 1 remote controller for 1 indoor unit. (Normal
operation) 

(See figure 13)

.

For group control or use with 2 remote controllers 

(See figure 15)

.

Precautions

1.

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

I

NSTALLATION

 

OF

 

THE

 

DECORATION

 

PANEL

Refer to the installation manual delivered with the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.

F

IELD

 

SETTING

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.

Summary of field settings

When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.

1

Outdoor unit

2

Indoor unit

3

Remote controller (Optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is automati-
cally set when the power is activated.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light

= Setting to define 

time between 2 filter 

cleaning display 

indications. (When 

contamination is 

high, setting can be 

changed to half the 

time inbetween 2 

filter cleaning 

display indications.)

Long-life 
filter

Light ±2,500 hrs.

Hea

vy

±1,250 hrs.

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only.
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

5

Information to I-manager, 
I-touch controller

Only unit sensor 
value (or remote 
sensor value if 
installed).

Sensor value as 
set by 10-2-0X 
or 10-6-0X.

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on + 
compressor run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

2

Thermostat differential 
changeover = Setting when 
remote sensor is used.

1°C

0.5°C

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

13 

(23)

0

Setting for air outlet 
velocity 
This setting is to be 
changed in function 
of ceiling height.

other 
models

2.7 m

>2.7 

3.0 m

>3.0 

3.5 m

FMCQ125 
only

3.2 m

>3.2 

3.6 m

>3.6 

4.2 m

1

Selection for air flow direction
This setting is to be changed 
when blocking pad optional kit 
is used.

4-way flow

3-way flow

2-way flow

4

Airflow direction range setting
This setting is to be changed 
when range of swing flap 
movement needs to be 
changed.

Upper

Medium

Lower

Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 

indoor units can also be set individually.

Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 

10-2-02 or 10-2-03 have priority.

Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 

connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have priority.

Note 7 : More settings for Differential automatic change over temperatures are:

Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

Summary of Contents for FMCQ100A8VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMCQ50A8VEB FMCQ60A8VEB FMCQ71A8VEB FMCQ100A8VEB FMCQ125A8VEB Air conditioning system...

Page 2: ...0 860 910 840 780 710 840 860 910 950 4 125 130 3 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 90 mm 7 mm 80...

Page 3: ...lecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B...

Page 4: ...lastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines gene...

Page 5: ...t the distance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as...

Page 6: ...see figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measure ments of the ceiling opening Consult the builder for details...

Page 7: ...tightening torque Overtightening may damage the flare and cause leaks Table 1 When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns...

Page 8: ...ose to insulate and fix it with clamps Insulate the complete drain piping inside the building field supply If the drain hose cannot be sufficiently set on a slope fit the hose with drain raising pipin...

Page 9: ...nit A unit B and be sure the terminal block wiring to the outdoor unit is matching properly If wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfu...

Page 10: ...es according to the table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insu...

Page 11: ...the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter...

Page 12: ...ining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and inju...

Page 13: ...panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How...

Page 14: ...H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector ada...

Page 15: ...1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1...

Page 16: ...4PW56204 1 Copyright Daikin...

Reviews: