Installation and operation manual

7

FMCQ50~125A8VEB

Air conditioning system

4PW56204-1

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring 

(See figure 10)

Power supply wiring
Remove the control box lid (1) and connect the wires to the
power supply terminal block inside (L, N) and connect the
ground wire to the grounding terminal. While doing this, pull the
wires inside through the hole in the casing and clamp the wires
along with other wires using a clamp as indicated in the figure.

Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the terminal block for unit
transmission wiring (F1, 

F2) and remote controller wiring

(P1, P2). Securely fix the wiring using a clamp as indicated in
the figure.

After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.

Attach the control box lid.

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal block.

-

Use a round crimp-style terminal for insulation sleeve for 
connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When clamping wiring, use the clamps (delivered with the 
unit) to prevent outside pressure being exerted on the wiring 
connections. Tie up firmly. When doing the wiring, make sure 
the wiring is neat and does not cause the control box to stick 
up. Close the cover firmly.

-

When connecting wires of the same gauge, connect them 
according to the figure.

Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.

-

When attaching the control box lid, make sure not to pinch 
any wires.

-

After all wiring connections are done, fill in any gaps in the 
casing wiring holes with putty or insulation material (field 
supply) thus to prevent small animals or dirt from entering the 
unit from outside and causing short circuits in the control box.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal block of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller wiring and unit transmission wiring should be
located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal block for
transmission wiring. This mistake could damage the entire system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire. 

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 14

.

Tightening torque (N•m)

Terminal block for unit transmission and 
remote controller

0.79~0.97

Terminal block for power supply

1.18~1.44

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

NOTE

The customer has the ability to select the remote
controller thermistor.

1

Power supply

2

Main switch

3

Power supply wiring

4

Unit transmission wiring

5

Switch

6

Fuse

7

Indoor unit

8

Remote controller

Summary of Contents for FMCQ100A8VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMCQ50A8VEB FMCQ60A8VEB FMCQ71A8VEB FMCQ100A8VEB FMCQ125A8VEB Air conditioning system...

Page 2: ...0 860 910 840 780 710 840 860 910 950 4 125 130 3 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 90 mm 7 mm 80...

Page 3: ...lecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B...

Page 4: ...lastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines gene...

Page 5: ...t the distance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as...

Page 6: ...see figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measure ments of the ceiling opening Consult the builder for details...

Page 7: ...tightening torque Overtightening may damage the flare and cause leaks Table 1 When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns...

Page 8: ...ose to insulate and fix it with clamps Insulate the complete drain piping inside the building field supply If the drain hose cannot be sufficiently set on a slope fit the hose with drain raising pipin...

Page 9: ...nit A unit B and be sure the terminal block wiring to the outdoor unit is matching properly If wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfu...

Page 10: ...es according to the table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insu...

Page 11: ...the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter...

Page 12: ...ining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and inju...

Page 13: ...panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How...

Page 14: ...H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector ada...

Page 15: ...1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1...

Page 16: ...4PW56204 1 Copyright Daikin...

Reviews: