background image

8

English

MOVEMENT OF THE AIR FLOW FLAP

For the following conditions, micro computer con-
trols the air flow direction so it may be different from 
the display.

Operation mode includes automatic operation.

B. LEFT AND RIGHT DIRECTION

Adjusting air flow direction in the left and right 
direction.

 (Refer to Fig. 1)

NOTE

Only make adjustments after you have stopped 
the air flow direction swing in a position where 
adjustments are possible. Your hand may get 
caught if you attempt to make adjustments while 
the unit is swinging.

Operate in the following order.

The timer is operated in the following two ways.

Programming the stop time  (

)                             

.... The system stops 
operating after the set time has elapsed.

Programming the start time (

)                             

.... The system starts 
operating after the set time has elapsed. 

The timer can be programmed a maximum of 72 
hours.

The start and the stop time can be simultaneously 
programmed.

TIMER MODE START/STOP

Press the TIMER MODE START/STOP button 
several times and select the mode on the 
display.

The display flashes.
For setting the timer stop .... “

For setting the timer start .... “

Operation 

mode

Cooling

Heating

Operation 

condition

When room 
temperature is 
lower than the 
set temperature

When room 
temperature is 
higher than the 
set temperature

At defrost opera-
tion

When operating continuously at 
downward air flow direction

PROGRAM TIMER OPERATION

1

PROGRAMMING TIME

Press the PROGRAMMING TIME button and 
set the time for stopping or starting the sys-
tem.

When this button is pressed, the time
advances by 1 hour.

When this button is pressed, the time
goes backward by 1 hour.

TIMER ON/OFF

Press the TIMER ON/OFF BUTTON.

The timer setting procedure ends. 
The display “ 

 or 

 ” changes from flash-

ing light to a constant light.

 Refer to figure 4 on page [1] 

NOTE

When setting the timer Off and On at the same 
time, repeat the above procedure from  

 to 

 

once again.

When the timer is programmed to stop the system 
after 3 hours and start the system after 4 hours, the 
system will stop after 3 hours and then 1 hour later 
the system will start.

After the timer is programmed, the display shows 
the remaining time.

Press the TIMER ON/OFF BUTTON once again 
to cancel programming. The display vanishes.

Observe the following precautions to ensure the 
system operates.

Adjust the room temperature properly for a com-
fortable environment. Avoid excessive heating or 
cooling.

Prevent direct sunlight from entering a room dur-
ing cooling operation by using curtains or blinds.

Ventilate the room regularly.
Using the unit for long periods of time requires 
attentive ventilation of the room.

Keep doors and windows closed. If the doors and 
windows remain open, room air will flow out and 
cause to decrease the effect of cooling and heating.

Do not place other heaters directly below the 
indoor unit.
They may deform due to the heat.

Never place objects near the air inlet and the air 
outlet of the unit. It may cause deterioration in the 
effect or stop in the operation.

2

3

7. OPTIMUM OPERATION

1

3

01_EN_3P303408-1C.fm  Page 8  Tuesday, January 10, 2012  8:01 PM

Summary of Contents for FHQ35BWV1B

Page 1: ...ATION MANUAL MODELS Ceiling suspension type FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ35BWV1B FHQ50BWV1B FHQ60BWV1B English Deutsch Fran ais Espa ol Italiano Nederlands Portugues 00_CV1_3P303408 1C fm Page...

Page 2: ...cuidadosamente el manual de funcionamiento antes de utilizar el acondicionador de aire Dicho manual le indi car c mo utilizar adecuadamente la m quina y le ayudar en caso de aver a Despu s de leer el...

Page 3: ...1 3 4 2 TEST C hr hr TEST NOT AVAILABLE L H 2 10 11 3 1 4 5 6 7 8 14 15 16 17 18 19 20 21 22 12 9 13 b d e k j a k i h f f c e e d d g C hr H 00_CV2_3P303408 1C fm Page 1 Tuesday January 10 2012 7 52...

Page 4: ...ntes debe ser efectuado por un instalador competente de acuerdo con las normas locales y nacionales aplicables Los acondicionadores de aire deben ser tratados en instalaciones especial izadas para su...

Page 5: ...oor unit Pair system or Simultaneous operation system NOTE If the unit you purchased is controlled by a wire less remote controller also refer to the wireless remote controller s operation manual If y...

Page 6: ...contact your local dealer Continued operation under such circumstances may result in a failure electric shocks or fire haz ards Consult your local dealer about installation work Doing the work yourse...

Page 7: ...leaning may cause breakage of plas tic parts water leakage and other damage as well as electric shocks CAUTION Do not use the air conditioner for purposes other than those for which it is intended Do...

Page 8: ...cumulation Never touch the internal parts of the remote controller Do not remove the front panel Touching certain internal parts will cause electric shocks and damage to the unit Please consult your d...

Page 9: ...electrician To do wiring ask your dealer Never do it by your self Make sure that a separate power supply circuit is provided for this air conditioner and that all electrical work is carried out by qua...

Page 10: ...maintenance purposes 17 PROGRAMMING TIME BUTTON Use this button for programming START and or STOP time hr hr C Refer to figure 1 on page 1 Operating procedure varies with heat pump type and cooling on...

Page 11: ...commend that you use a circulator a fan to circulate the air inside the room For details consult your dealer For programming TEMPERATURE FAN SPEED and AIR FLOW DIRECTION follow the procedure shown bel...

Page 12: ...time for stopping or starting the sys tem When this button is pressed the time advances by 1 hour When this button is pressed the time goes backward by 1 hour TIMER ON OFF Press the TIMER ON OFF BUTTO...

Page 13: ...TO TERMINAL DEVICES ALL POWER SUPPLY CIRCUITS MUST BE INTERRUPTED To clean the air conditioner be sure to stop oper ation and turn the power switch off Otherwise an electric shock and injury may resul...

Page 14: ...d neutral deter gent or water and dry throughly When very grimy Directly apply the type of detergent used for cleaning ventilation fans or ovens wait 10 min utes and then rinse with water NOTE Do not...

Page 15: ...ow flaps become horizontal The unit will go into the above mode if either cool ing dry or fan operation mode are set together with heating mode NOTE Normally the operation mode in the room where the u...

Page 16: ...tion This continues temporary X DOES NOT COOL VERY WELL Program dry operation Program dry operation is designed to lower the room temperature as little as possible Refer to page 6 I If one of the foll...

Page 17: ...le and make it well venti lated If the air filter is clogged Ask a qualified service person to clean the air filters Refer to MAINTENANCE If the set temperature is not proper Refer to ADJUSTMENT If th...

Page 18: ...3P303408 1C EM11A063A 1201 HT 00_CV1_3P303408 1C fm Page 2 Tuesday January 10 2012 7 09 PM...

Reviews: