![Daikin FHA100AVEB8 User Reference Manual Download Page 68](http://html.mh-extra.com/html/daikin/fha100aveb8/fha100aveb8_user-reference-manual_2460428068.webp)
18
|
Electrical installation
Installer and user reference guide
68
FHA-A(9)
Split system air conditioner
4P708119-1 – 2022.11
WARNING
▪
If the power supply has a missing or wrong N-phase, equipment might break
down.
▪
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
▪
Install the required fuses or circuit breakers.
▪
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪
Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
Use an all-pole disconnection type breaker with at least 3 mm between the contact
point gaps that provides full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
18.1.2 Guidelines when connecting the electrical wiring
Keep the following in mind:
NOTICE
We recommend using solid (single-core) wires. If stranded wires are used, slightly
twist the strands to consolidate the end of the conductor for either direct use in the
terminal clamp or insertion in a round crimp-style terminal.
To prepare stranded conductor wire for installation
Method 1: Twisting conductor
1
Strip insulation (20 mm) from the wires.
2
Slightly twist the end of the conductor to create a "solid-like" connection.
Method 2: Using round crimp-style terminal
1
Strip insulation from wires and slightly twist the end of each wire.
2
Install a round crimp-style terminal on the end of the wire. Place the round
crimp-style terminal on the wire up to the covered part and fasten the
terminal with the appropriate tool.