Installation and operation manual

5

FDYMP71~125L7V1

Split System air conditioners

4PW14036-1B

Precautions

1.

A single switch can be used to supply power to units on the same
system. However, branch switches and branch circuit breakers must
be selected carefully.

2.

Do not ground the equipment on gas pipes, water pipes, lightning
rods or crossground with telephones. Improper grounding could
result in electric shock.

F

IELD

 

SETTING

Field setting must be made from the remote controller in accordance
with the installation condition. 

Refer to the manual of the remote

controller.

Setting of static pressure

Change the SECOND CODE No. according to 

Table 2

depending on the resistance of the connection duct.

Table 2

The unit is factory set for high static pressure (SECOND CODE No.
02) at the time of shipping.

Setting air filter sign

Remote controllers are equipped with liquid crystal display air
filter signs to display the time to clean air filters.

Change the SECOND CODE No. According to 

Table 3

depending on the amount of dirt or dust in the room. (SECOND
CODE No. Is factory set to "01" for filter contamination-light.)

Table 3

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

Refer to the manual of the remote controller

.

Computerised control (forced off and on/off operation)

1

Wire specifications and how to perform wiring

-

Connect the input wire (option) to connector X40A on the 
indoor PCB.

Wire specifications (to extend the optional wire):

(See figure 8)

2

Actuation

-

The following table explains "forced off" and "on/off 
operations" in response to input A.

3

How to select forced off and on/off operation

Change the second code No. according to 

Table 4

.  (Second

code No. is factory set to “01” for forced off.)

Table 4

T

EST

 

OPERATION

Refer to the section of 

"For the following items, take special care

during construction and check after installation is finished" on page 2

.

After finishing the construction of refrigerant piping, drain piping,
and electric wiring, conduct test operation accordingly to protect
the unit.

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours. (Not necessary for the
straight cooling type.)

4

Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.

5

Press Inspection/Test Operation button 4 times and operate at
Test Operation mode for 3 minutes.

6

Press Inspection/Test Operation button and operate normally.

7

Confirm function of unit during operation. 

Refer to the manual of

the remote controller on how to operate.

Precautions

In case something is wrong with the unit and it does not operate, refer
to the malfunction diagnosis label attached to the unit.

External static 

pressure

Mode No.

FIRST CODE No.

SECOND 

CODE No.

Low: 50 Pa 

13 (23)

6

01

High: 100 Pa 

02

Setting

Spacing time of 
display air filter 

sign (long life 

type)

Mode No.

FIRST 

CODE No.

SECOND 

CODE No.

Air filter 

contamination - 

light

±2500 hrs

10 (20)

0

01

Air filter 

contamination - 

heavy

±1250 hrs

02

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

1

Input A (Input “ON”=closed contact)

Forced off

on/off operation

Input "on" stops ope 
disables control

input off 

 on: starts operation remote, 

control is still enabled

Input "off" enables control 

input on 

 off: stops operation remote, 

control is still enabled

Setting

Mode No.

FIRST CODE No.

SECOND CODE No.

Forced off

12 (22)

1

01

ON/OFF 

operation

02

NOTE

If the main power supply is turned off during operation,
operation will restart automatically after the power
turns back on again.

Summary of Contents for FDYMP100L7V1

Page 1: ...INSTALLATION AND OPERATION MANUAL FDYMP71L7V1 FDYMP100L7V1 FDYMP125L7V1 Split System air conditioners ...

Page 2: ... 25 10 43 5 46 18 35 12 25 18 35 12 25 RP71 125 RYP71 125 RYEP71 125 RYP71 125 RYEP71 125 1 2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 M S S 1 X40A 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 M 3 8 9 10 2 1 6 4 7 1 2 3 P1 P2 7 6 11 8 1 10 9 4 3 2 5 5 6 C DB C WB C DB C WB C DB C WB C DB C WB C DB C WB C DB C DB 1 2 3 4 9 8 7 5 6 10 11 12 15 14 13 ...

Page 3: ...givande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til våre instrukser vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen että niitä käytetään ohjeidemme mukais...

Page 4: ...here volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves can be found Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may damage electri...

Page 5: ...ee figure 6 For other installation than standard installation contact your Daikin dealer for details 2 The fan speed for this indoor unit is preset to provide high external static pressure If lower external static pressure is required reset the external static pressure by changing the initial setting from the remote controller Refer to Setting of static pressure on page 5 3 Install the suspension ...

Page 6: ...nsulate it DRAIN PIPING WORK 1 Install the drain pipes Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal to or greater than that of the connecting pipe For connection to the drain socket use a flexible hose field supply and clamp it firmly This to avoid leaks due to operating vibration of the unit After clamping isolate ...

Page 7: ...he remote controller supplied with the remote controller 5 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do not obstruct other equipment such...

Page 8: ...ff Table 4 TEST OPERATION Refer to the section of For the following items take special care during construction and check after installation is finished on page 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater...

Page 9: ... when not using for long periods of time Electricity is consumed as long as the switch is on Turn off the main power supply switch in order to save energy Turn on the main power supply switch 6 hours before restarting operation in order to ensure smooth operation Refer to Maintenance on page 8 When the display shows TIME TO CLEAN AIR FILTER have a qualified service person to clean the filters Refe...

Page 10: ...s this noise Dust from the units Dust may blow out from the unit after starting operation from long resting time Dust absorbed by the unit blows out The units give off odours The unit absorbs the smell of rooms furniture cigarettes etc and then emits them The liquid crystal display of the remote controller shows Happens immediately after the main power supply switch is turned on Shows that the rem...

Page 11: ...Remove any obstacle Check if the earth is connected Clean the air filter After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch at least 6 hours before operation What to do when stopping the system for a long period Turn on FAN OPERATION for a half day a...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14036 1B ...

Reviews: