FDYMP71~125L7V1
Split System air conditioners
4PW14036-1B

Installation and operation manual

4

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the switch box cover to
wire the outdoor unit, indoor units and the remote controller. For
details on hooking up the remote controller, refer to the
"Installation manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.

Specifications for field wire

Use H07RN-F as wiring between indoor units in case of no
protection.

Allowable length of transmission wiring between the indoor unit and
the remote controller is max. 500 m.

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring

Remove the switch box cover as shown in 

figure 15

, and make the

connections.

Precautions

1.

Observe the notes mentioned below when wiring to the power supply
terminal board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

2.

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

3.

Remote controller cords and wires connecting the units should be
located at least 50 mm away from power supply wiring. Not following
this guideline may result in malfunction due to electrical noise.

4.

For the remote controller wiring, refer to the "Installation manual of
the remote controller" supplied with the remote controller.

5.

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire system.

6.

Use only specified wires and tightly connect wires to the terminals.
Be careful that wires do not place external stress on the terminals.
Keep wiring in neat order so that they do not obstruct other
equipment such as popping open the switch box cover. Make sure
the cover closes tight. Incomplete connections could result in
overheating, and in the worst case, electric shock or fire.

W

IRING

 

EXAMPLE

Fit the power supply wiring of each system with a switch and
fuse as shown in 

figure 7

9

 and 

10

.

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit. (Normal
operation) 

(See figure 10)

For group control 

(See figure 7)

For group control, cut the jumper indicated as “master/slave” on the
PCB of the “slave” indoor units (=slave PCB). Do not cut the jumper
on the PCB of the indoor unit to which the remote controller is
connected (=master PCB).

Use with 2 remote controllers 

(See figure 9)

Connection

Wire

Size

Between indoor units

H05VV-U4G

Local codes

Unit-Remote controller

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to the chapter 

"Wiring example" on

page 4

.

1

Switch box

2

Switch box cover

3

Power supply wiring port

4

Transmission wiring port

5

Wiring diagram

6

Wiring clamp

7

Remote controller wiring

8

Terminal for remote controller wiring

9

Power supply wiring

10

Terminal for power supply wiring

11

Earth screw

NOTE

The customer has the ability to select the remote
controller thermistor.

1

Power supply

2

Main switch

3

Fuse

4

Outdoor unit

5

Indoor unit (M=master, S=slave)

6

Remote controller (optional accessory)

Master

Slave

NOTE

It is not necessary to designate an indoor unit address
when using group control. The address is auto-
matically set when the power is activated.

Summary of Contents for FDYMP100L7V1

Page 1: ...INSTALLATION AND OPERATION MANUAL FDYMP71L7V1 FDYMP100L7V1 FDYMP125L7V1 Split System air conditioners ...

Page 2: ... 25 10 43 5 46 18 35 12 25 18 35 12 25 RP71 125 RYP71 125 RYEP71 125 RYP71 125 RYEP71 125 1 2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 M S S 1 X40A 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 P1 P2 6 6 M 3 8 9 10 2 1 6 4 7 1 2 3 P1 P2 7 6 11 8 1 10 9 4 3 2 5 5 6 C DB C WB C DB C WB C DB C WB C DB C WB C DB C WB C DB C DB 1 2 3 4 9 8 7 5 6 10 11 12 15 14 13 ...

Page 3: ...givande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til våre instrukser vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen että niitä käytetään ohjeidemme mukais...

Page 4: ...here volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves can be found Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may damage electri...

Page 5: ...ee figure 6 For other installation than standard installation contact your Daikin dealer for details 2 The fan speed for this indoor unit is preset to provide high external static pressure If lower external static pressure is required reset the external static pressure by changing the initial setting from the remote controller Refer to Setting of static pressure on page 5 3 Install the suspension ...

Page 6: ...nsulate it DRAIN PIPING WORK 1 Install the drain pipes Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal to or greater than that of the connecting pipe For connection to the drain socket use a flexible hose field supply and clamp it firmly This to avoid leaks due to operating vibration of the unit After clamping isolate ...

Page 7: ...he remote controller supplied with the remote controller 5 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do not obstruct other equipment such...

Page 8: ...ff Table 4 TEST OPERATION Refer to the section of For the following items take special care during construction and check after installation is finished on page 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater...

Page 9: ... when not using for long periods of time Electricity is consumed as long as the switch is on Turn off the main power supply switch in order to save energy Turn on the main power supply switch 6 hours before restarting operation in order to ensure smooth operation Refer to Maintenance on page 8 When the display shows TIME TO CLEAN AIR FILTER have a qualified service person to clean the filters Refe...

Page 10: ...s this noise Dust from the units Dust may blow out from the unit after starting operation from long resting time Dust absorbed by the unit blows out The units give off odours The unit absorbs the smell of rooms furniture cigarettes etc and then emits them The liquid crystal display of the remote controller shows Happens immediately after the main power supply switch is turned on Shows that the rem...

Page 11: ...Remove any obstacle Check if the earth is connected Clean the air filter After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch at least 6 hours before operation What to do when stopping the system for a long period Turn on FAN OPERATION for a half day a...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14036 1B ...

Reviews: