8

ADDITIONAL CHARGE

The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 5 m, additional charge after vacuuming is not
necessary. When the piping length is more than 5 m, use the table below.

Additional Charge Operation

This operation must be done by using gas cylinder and a precise weighing machine obligatorily. The additional charge is top up into
the outdoor unit by suction valve via service  port.
• Remove the service valve plug.
• Connect the low pressure manifold to the suction service port, center manifold to the cylinder tank and close the high pressure

manifold (see figure below).
Purge all the flexible hose with refrigerant gas.

• Start the air conditioner unit.
• Open the gas cylinder and low pressure manifold valve.
• When the required refrigerant quantity is pumped in the unit, close the low pressure manifold and the gas cylinder valve.
• Disconnect the manometer and the gas cylinder. Place back the service port cap.

Indoor

FDYM30CV1M

FDYM40CV1M

FDYM60CV1M

 FDYM71CV1M

FDYM80CV1M

FDYB30CV1M

FDYB40CV1M

FDYB60CV1M

 FDYB71CV1M

Outdoor

RY30CV1M

RY40CV1M

RY60CV1M

RY71CV1M

RY80CV1M

Additional

23

23

22

56

56

 Charge (g/m)

Additional Charge

Indoor

FDYM90CV1M

FDYM100CV1M

FDYM1250CV1M

 FDYM140CV1M

FDYM160CV1M

FDYB90CV1M

FDYB1250CV1M

 FDYB140CV1M

FDYB160CV1M

Outdoor

RY90CV1M

RY100CV1M

RY125CV1M

RY90CY1M

RY125CY1M

RY140CY1M

RY160CY1M

Additional

55

57

56

56

106

 Charge (g/m)

Refrigerant Gas Tank

Flexible Hose

High Pressure Gauge

Manifold

Low Side
Pressure Gauge

Gas Valve

Refrigerant Piping

Indoor Unit

Outdoor Unit

Liquid Valve

Check Refrigerant Leak

Check with refrigerant detector whether there is a leak on the flare type connection of the indoor unit and outdoor unit.
Hints: After operation for sometime, check if there is oil traces, there is a leak.

Heat Pump Unit

E.g.
FDYM30CV1M & RY30CV1M with 12m piping length, additional piping length is 4.4m. Thus,
Additional charge = 4.4[m] x 23[g/m]

 = 101.2 [g]

Summary of Contents for FDYB30CV1M

Page 1: ...0CV1M RY80CV1M FDYM90CV1M FDYB90CV1M RY90CV1M FDYM90CV1M FDYB90CV1M RY90CY1M FDYM100CV1M RY100CV1M FDYM125CV1M FDYB125CV1M RY125CV1M FDYM125CV1M FDYB125CV1M RY125CY1M FDYM140CV1M FDYB140CV1M RY140CY1M...

Page 2: ...8 8 4 2 5 3 9 9 4 8 4 FDYM90CV1M 359 999 956 917 408 5 378 541 256 173 306 70 5 160 5 248 220 0 FDYB90CV1M 14 1 39 3 37 6 36 1 16 1 14 9 21 3 10 1 6 8 12 0 2 8 6 3 9 8 8 7 FDYM100CV1M 371 2 1312 1264...

Page 3: ...B C D E F G H I J K L M N O RY60CV1M 855 628 328 513 182 44 93 149 101 113 603 126 164 17 49 33 7 24 7 12 9 20 0 7 1 1 7 3 7 5 9 4 0 4 4 23 7 5 0 6 4 0 7 1 9 RY71CV1M 855 730 328 513 182 44 93 149 10...

Page 4: ...M N P RY90CV1M RY90CY1M 1030 850 400 390 414 827 72 196 91 488 448 141 5 746 5 82 RY100CV1M RY125CV1M 40 6 33 5 15 7 15 4 16 3 32 6 2 8 7 7 3 6 19 2 17 6 5 6 29 4 3 2 RY125CY1M RY140CY1M All dimensio...

Page 5: ...l A B C D E F G H J K L M N RY160CY1M 1030 850 400 448 746 5 320 25 50 85 40 141 5 20 60 40 6 33 5 15 7 17 6 29 4 12 6 1 0 2 0 3 3 1 6 5 6 0 8 2 4 All dimensions are in mm in J H C F K K B G A L E L M...

Page 6: ...OM WARNING Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation and experienced with this type of appliance All field wiring must be in...

Page 7: ...allation provide clearance for servicing ease as shown in diagram and table below C mm inch D mm inch FDYM30CV1M FDYB30CV1M FDYM40CV1M FDYB40CV1M 200 500 FDYM60CV1M 7 9 19 7 FDYB60CV1M FDYM71CV1M FDYB...

Page 8: ...V1M FDYM71CV1M FDYM80CV1M Data FDYB30CV1M FDYB40CV1M FDYB60CV1M FDYB71CV1M Maximum Length Am ft 12 39 4 12 39 4 15 49 2 15 49 2 15 49 2 Maximum Elevation B m ft 5 16 4 5 16 4 8 26 2 8 26 2 8 26 2 Maxi...

Page 9: ...hips from entering the pipe Insert the flare nuts mounted on the connection parts of both indoor and outdoor unit into the copper pipes The exact length of pipe protruding from the face of the flare d...

Page 10: ...Power Supply Cable N 4WV OF COMP L N N COMP OF 4WV FDYM80CV1M RY80CV1M There must be a all pole switch with a minimum 3 mm contact gap and fuse circuit breaker as recommended in the fixed installation...

Page 11: ...There must be a all pole switch with a minimum 3 mm contact gap and fuse circuit breaker as recommended in the fixed installation circuits FDYM90CV1M FDYB90CV1M RY90CY1M FDYM125CV1M FDYB125CV1M RY125...

Page 12: ...r manifold gauge with the vacuum pump Connect the manifold gauge to the service port of the 3 ways valve Start the vacuum pump Check the low pressure manifold gauge until it indicate 0 9 bar The evacu...

Page 13: ...linder valve Disconnect the manometer and the gas cylinder Place back the service port cap Indoor FDYM30CV1M FDYM40CV1M FDYM60CV1M FDYM71CV1M FDYM80CV1M FDYB30CV1M FDYB40CV1M FDYB60CV1M FDYB71CV1M Out...

Page 14: ...he installer 1 Charging procedures Single phase compressors Evacuate the system to 500 microns Hg 67Pa To reduce evacuation time use short large diameter hoses and connect to unrestricted service port...

Page 15: ...mooth drainage of water Check that 1 Condenser fan is running with warm air blowing off the condensing unit 2 Evaporator blower is running and discharge cool air 3 The remote controller incorporates a...

Page 16: ...for any faulty contacts caused by loose connections foreign matters etc Tighten the wires onto the terminal block if necessary 1 No maintenance needed if the refrigerant circuit remain sealed However...

Page 17: ...5 Discharge air flow has bad odor 6 Condensation on the front air grille of the indoor unit 7 Water flowing out from the air conditioner unit 8 Hissing air flow sound from the air conditioner unit du...

Reviews: