.INSTALLATION SERVICING SPACES (3/3))
I
In case obstacles exist in front of both inlet and outlet sides
I
(Pattern 1)
When obstacles in front of the outlet side is higher than the outdoor unit.
(1) When nothing is obstructing the top.
(There is no height limit for
obstructions on the inlet side.)
(2) When something is obstructing the top.
The relations between H, A and L are
shown in the table below.
-------
L
A
L :a;0.5H
1000 or more
L:a;H
0.5H<L:;;;H
1250 or more
L> H Set the frame to be L :;;. H
Refer to the column of L :;;; H for A.
Get the lower part of the frame sealed so that
air from the outlet does not bypass.
Only two units at most can be installed in series.
(Pattern 2)
Where obstacles in front of the outlet side is lower than the outdoor unit
(1 )When nothing is obstructing the top.
{There is no height limit for
obstructions on the inlet side.)
The relations between H, A and Lare
shown in the table below.
L
A
L :a;0.5H
250 or more
0.5H<L:;;;H 300 or more
(2) When something is obstructing the top.
The relations between H, A and Lare
shown in the table below.
-------
L
A
L:a;0.5H
250 or more
L:a;H
0.5H<L:;;;H
300 or more
L>H Set the frame to be L :;;; H
Refer to the column of L :;;. H for A.
Get the lower part of the frame sealed so
that air from the outlet does not bypass.
If the dimensions is ( ) or more, you do not
need to place the frame including the case
of L>H .
( 3-3 IN CASE OF STACKED INSTALLATION )
I
When nothing is obstructing the top
I
(Units: mm)
500 or less
1000
or more
1000
or more
H
(Units: mm)
(1) In case obstacles exist in front
of the outlet side .
(2) In case obstacles exist in
front of the inlet side.
• Do not exceed two levels for stacked installation.
• Install a roof cover similar to A (field supply),
as the outdoor units with downward drainage are prone to
dripping.
• Install the upper-level outdoor unit so that its bottom frame
is a sufficient height above the roof cover. This is to prevent
the buildup of ice on the underside of the bottom frame.
(A space of at least 500mm is recommended.)
• It is not necessary to install a roof cover if there is no
danger of drain dripping.
A
In this case, the space between the upper and lower
outdoor units should be at least 100mm. (Close off the gap
between the upper and lower units so there is no reintake of
discharged air.)
(3-4 IN CASE OF MULTIPLE-ROW INSTALLATI ON ( FOR ROOF TOP USE, ETC.))
(1) In case of installing one unit
(2) In case of installing multiple units
per row.
(2 units or more) in lateral
connection per row.
1000rmore
The relation of dimensions of H,A and
Lare as shown in the table below.
----...........
L
A
L:a; 0.5H
250 or more
L:a;H
0.5H<L:a;H
300 or more
L> H
Can not be installed
•In case of side piping outlet, ensure
a space sufficient for piping.
26
100
L
Summary of Contents for FDMA125AV16
Page 22: ...4 15 3 30 RZA125AV16 RZA140AV16 RZA125AV16 RZA140AV16...
Page 50: ...49...
Page 51: ...50...
Page 52: ...51...
Page 53: ...52...
Page 54: ...53...
Page 55: ...54 49 48 49 50 50...
Page 56: ...55...
Page 58: ...MEMO...
Page 59: ...MEMO...
Page 60: ...MEMO 3P727715 6 B...