1-16
Model
Indoor (FCQN)
100E
100E
Outdoor (RQ)
90D
100D
Voltage range**
Indoor (FCQN)
220-240V/1Ph/50Hz +
!
Outdoor (RQ)
220-240V/1Ph/50Hz +
!
Power supply cable size*
(mm
2
)
Number of conductors
4.0
3
4.0
3
Interconnection cable size*
(mm
2
)
Number of conductors
2.5
3&4
2.5
3&4
Recommended time delay fuse*
(A)
25
30
A
4WV
OF
COMP
N
L
R
S
T
N
4WV
A
OF
L
N
COMP
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Outdoor Coil Sensor
FCQN 100/125E - RQ 100/125D (3 PH)
Model
Indoor (FCQN)
100E
125E
Outdoor (RQ)
100D
125D
Voltage range**
Indoor (FCQN)
220-240V/1Ph/50Hz +
!
Outdoor (RQ)
380-415V/3N~/50Hz +
!
Power supply cable size*
(mm
2
)
Number of conductors
2.5
5
2.5
5
Interconnection cable size*
(mm
2
)
Number of conductors
1.5
3&4
1.5
3&4
Recommended time delay fuse*
(A)
13
18
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.