1-14
R
S
T
N
COMP
L
N
COMP
L
N
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Model
Indoor (FCRN)
100E
100E
Outdoor (RR)
90D
100D
Voltage range**
Indoor (FCRN)
220-240V/1Ph/50Hz +
!
Outdoor (RR)
220-240V/1Ph/50Hz +
!
Power supply cable size*
(mm
2
)
Number of conductors
4.0
3
4.0
3
Interconnection cable size*
(mm
2
)
Number of conductors
2.5
4
2.5
4
Recommended time delay fuse*
(A)
25
30
Model
Indoor (FCRN)
100E
125E
Outdoor (RR)
100D
125D
Voltage range**
Indoor (FCRN)
220-240V/1Ph/50Hz +
!
Outdoor (RR)
380-415V/3N~/50Hz +
!
Power supply cable size*
(mm
2
)
Number of conductors
2.5
5
4.0
5
Interconnection cable size*
(mm
2
)
Number of conductors
1.5
4
1.5
4
Recommended time delay fuse*
(A)
13
18
FCRN 100/125E - RR 100/125D (3 PH)
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
1 IM-5CKE-0912(0)DAIKIN-EN.indd 14
1 IM-5CKE-0912(0)DAIKIN-EN.indd 14