3
Dimensional drawings
FCQ-B7
view A
680 Suspension position
view B
780
(Suspension
position)
860
∼
890
(Ceiling
opening)
Note:
1. Location of unit’s name plate
Main body: bell mouth inside the suction grille.
Decoration panel: panel inner frame inside the suction grille..
2. When installing an optional accessory, refer to the installation drawings.
+
For fresh air intake kit - inspection port is necessary
+
For high efficiency filter unit - inspection port is not necessary.
+
For branch duct chamber - inspection port is not necessary.
1 Liquid pipe connection
J
A Flare connection
2 Gas pipe connection
J
B Flare connection
3 Drain pipe connection VP25 (O.D.
J
32, I.D.
J
25)
4 Power supply connection
5 Transmission wiring connection
6 Air discharge grille
7 Air suction grille
8 Water supply intake
9 Corner decoration cover
10 Drain hose O.D.
J
32
Required installation space
When the discharge grill is closed, the required
space is 200mm or more
860
∼
890 (Ceiling opening)
Adjustable
(0
∼
550)
Hanging bolt
1000
mm
or
more
Required
service
space
1500 mm or more
1500 mm or more
1500 mm or more
1500 mm or more
view D
Prepared hole
Branch duct
connection
Note 3
300 or less
3TW22834-1A
3. In case of using an infrared remote control, this position will be a signal
receiver.
Refer to the drawing of infrared remote controller in detail
4. When it may exceed 30°C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation (Thickness 10mm or
more of glasswool or polyethylene form) is required.
Branch duct
connection
Branch duct connection
Prepared hole
Prepared hole
For fresh air intake kit connection(direct installation type)
view C
Prepared hole
Model
A
B
FCQ35B
6.35
9.52
FCQ50B, FCQ60B
6.35
12.70
•
4-Way Blow Ceiling Mounted Cassette
•
R-410A
•
FCQ35-60B7V1B
3
5
•
Split - Sky Air
•
Indoor Units