![background image](http://html1.mh-extra.com/html/daikin/fcq100kvlt/fcq100kvlt_removal-manual_2460367013.webp)
Si281312E
Procedure to Remove Drain Pump, Float Switch
Removal Procedure
11
9. Procedure to Remove Drain Pump, Float Switch
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
According to the
procedure for the removal
of decoration panel,
remove the decoration
panel.
According to the
procedure for the removal
of drain pan, remove the
drain pan.
1. Removing the drain pump
1
Cut the cable tie with
nippers.
2
Pull out the drain hose.
3
Unscrew the 3 screws
that fix the drain pump
assembly, and then
remove the assembly.
4
Unscrew the 3 screws
that fix the drain pump
mounting bracket, and
then remove the
bracket.
2. Removing the float switch
1
Unscrew the 1 screw
that fixes the float
switch assembly, and
then remove the
assembly.
2
Slide the 2 protrusions
laterally, and then
remove the float switch.
Fixing screw
(3 pcs.)
Drain pump
assembly
Cable tie
Bolt (3 pcs.)
Vibro-isolating
rubber (3 pcs.)
Drain pump
Float switch
assembly
Float switch
Bracket
Bracket