background image

8 Commissioning

Installer and user reference guide

17

FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12

If you want

Then

1

M

C1

C2

During cooling
operation

LL

2

12 (22)

6

01

Setup volume

2

02

During heating
operation

LL

2

12 (22)

3

01

Setup volume

2

02

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

1

M

C1

C2

±2500 h (light)

10 (20)

0

01

±1250 h (heavy)

02

No notification

3

02

8

Commissioning

8.1

Overview: Commissioning

This  chapter  describes  what  you  have  to  do  and  know  to
commission the system after it is installed.

Typical workflow

Commissioning typically consists of the following stages:

1

Checking the "Checklist before commissioning".

2

Performing a test run for the system.

8.2

Precautions when commissioning

INFORMATION

During  the  first  running  period  of  the  unit,  the  required
power may be higher than stated on the nameplate of the
unit.  This  phenomenon  is  caused  by  the  compressor,  that
needs  a  continuous  run  time  of  50  hours  before  reaching
smooth operation and stable power consumption.

NOTICE

Before starting up the system, the unit MUST be energised
for at least 6 hours to avoid compressor breakdown during
startup.

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

NOTICE

Do  NOT  operate  the  unit  until  the  refrigerant  piping  is
complete  (when  operated  this  way,  the  compressor  will
break).

NOTICE

Cooling  operation  mode

.  Perform  the  test  run  in  cooling

operation mode so that stop valves failing to open can be
detected.  Even  if  the  user  interface  was  set  to  heating
operation mode, the unit will run in cooling operation mode
during 2‑3 minutes (although the user interface will display
the heating icon), and then automatically switch to heating
operation mode.

NOTICE

If  you  cannot  operate  the  unit  in  test  run,  see 

"8.5  Error

codes when performing a test run" on page 18

.

WARNING

If the panels on the indoor units are not installed yet, make
sure  to  power  OFF  the  system  after  finishing  the  test  run.
To  do  so,  turn  OFF  operation  via  the  user  interface.  Do
NOT stop operation by turning OFF the circuit breakers.

8.3

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

(2)

Fan speed:

LL

: Low fan speed

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button

on the user interface.

Summary of Contents for FCAHG100FVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71FVEB FCAHG100FVEB FCAHG125FVEB FCAHG140FVEB...

Page 2: ...lectrical wiring 15 6 4 3 Guidelines when connecting the electrical wiring 15 6 4 4 Specifications of standard wiring components 15 6 4 5 To connect the electrical wiring on the indoor unit 15 7 Confi...

Page 3: ...ilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play...

Page 4: ...here there is machinery that emits electromagnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment In places where there is a risk of fire due to the...

Page 5: ...3 EC 1 3 6 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical parts Disconnect the power supply...

Page 6: ...s or for commercial use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read bef...

Page 7: ...or and indoor units Combining the indoor unit with options INFORMATION For year round cooling applications with low indoor humidity conditions such as Electronic Data Processing rooms contact your dea...

Page 8: ...g the unit in and out of the site 5 2 1 Installation site requirements of the indoor unit INFORMATION Also read the following requirements General installation site requirements See the General safety...

Page 9: ...epends on the air flow directions towards the wall 1500 500 200 a A A A b c a Air outlet and corners open b Air outlet closed corners open optional blocking pad kit required c Air outlet and corners c...

Page 10: ...ng Checking the refrigerant piping Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFORMATION This chapter only describes in...

Page 11: ...d e f a b a Drain piping b Refrigerant piping c Hanger bracket pitch suspension d Unit e Ceiling opening f Decoration panel If A Then B C A C B 860 mm min 20 mm 35 mm 910 mm max 35 mm 20 mm A Ceiling...

Page 12: ...installation space and surroundings 1 Push the drain hose as far as possible over the drain pipe connection 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part...

Page 13: ...Do NOT use mineral oil on flared part NEVER install a drier to this R32 unit to guarantee its lifetime The drying material may dissolve and damage the system NOTICE Take the following precautions on...

Page 14: ...prevent creation of large quantities of oxidised film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the n...

Page 15: ...c Flat washer Tightening torques Wiring Screw size Tightening torque N m Interconnection cable indoor outdoor M4 1 18 1 44 User interface cable M3 5 0 79 0 97 6 4 4 Specifications of standard wiring c...

Page 16: ...round air flow use the table below If the distance to the floor is m Then1 FCAHG71 FCAHG100 140 M C1 C2 2 7 3 2 13 23 0 01 2 7 x 3 0 3 2 x 3 6 02 3 0 x 3 5 3 6 x 4 2 03 Setting Air flow direction This...

Page 17: ...valves failing to open can be detected Even if the user interface was set to heating operation mode the unit will run in cooling operation mode during 2 3 minutes although the user interface will disp...

Page 18: ...within 10 seconds Test run starts 3 Check operation for 3 minutes 4 Check operation of the airflow direction Action Result 1 Press Return Setting Return Setting Air Volume direction Air Volume Directi...

Page 19: ...nit are incompatible 9 Hand over to the user Once the test run is finished and the unit operates properly please make sure the following is clear for the user Make sure that the user has the printed d...

Page 20: ...0 55 55 35 35 125 130 112 153 298 840 55 55 10 40 175 340 0 675 280 330 75 180 213 A c b i g a j d h a e f b c d j e f In case of installation with self cleaning decoration panel 75 210 420 420 710 86...

Page 21: ...wall 1500 500 200 a A A A b c a Air outlet and corners open b Air outlet closed corners open optional blocking pad kit required c Air outlet and corners closed optional blocking pad kit required B Mi...

Page 22: ...side forced off or on off control operation can be selected by the remote controller See installation manual for more details 5 Connect power of adapter for wiring to terminal block X2M of indoor unit...

Page 23: ...staller and user reference guide 23 FCAHG71 140FVEB Split system air conditioners 4P429475 1 2015 12 X A PCB connector X M Terminal strip X Y Connector Z C Noise filter ferrit core Z F Noise filter Op...

Page 24: ...o fan Number of fans 1 Number of motors output 48 W 106 W Fan speed 5 steps Piping connections Liquid outer diameter 9 52 mm flare Gas outer diameter 15 9 mm flare Drain outer diameter Vinyl pipe 25 m...

Page 25: ...ARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is not good for your health to e...

Page 26: ...r Contact your dealer for details 15 2 4 To operate the system 1 Press the operation mode selector button on the user interface several times and select the operation mode of your choice Cooling opera...

Page 27: ...s blocked 17 Maintenance and service NOTICE Never inspect or service the unit by yourself Ask a qualified service person to perform this work However as end user you may clean the air filter suction g...

Page 28: ...move stains use water or neutral detergent 17 2 Maintenance after a long stop period E g at the beginning of the season Check and remove everything that might be blocking inlet and outlet vents of ind...

Page 29: ...leaks into a room where combustible air from fan heaters gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before res...

Page 30: ...or indoor unit is not blocked by obstacles Remove any obstacle and make it well ventilated Check if the air filter is not clogged see 17 1 1 To clean the air filter on page 27 Check the temperature s...

Page 31: ...frost operation This is the noise of refrigerant caused by flow stop or flow change 18 1 9 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused...

Page 32: ...015 12 Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation Field supply Equipment not made by...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P429475 1 2015 12 Copyright 2015 Daikin...

Reviews: