background image

5

Wiring diagrams

3D043881

FAQ71BUV1B

A1P

Printed circuit board

HAP

Light emitting diode (service monitor green)

M1S

Motor (swing flap)

M1F

Motor (indoor fan)

R1T

Thermistor (air)

R2T

Thermistor (coil)

SS1

Selector switch (emergency)

X1M

Terminal block

X2M

Terminal block

Power supply

?

Signal receiver circuit

.

Signal transmission circuit

Infrared remote control

Receiver / display unit

A2P

Printed circuit board

A3P

Printed circuit board

BS1

Push button (on/off)

H1P

Light emitting diode (on-red)

H2P

Light emitting diode (timer-green)

H3P

Light emitting diode (filter sign-red)

H4P

Light emitting diode (defrost-orange)

SS1

Selector switch (main/sub)

SS2

Selector switch (wireless address set)

Connector for optional parts

X15A

Connector (float switch)

X35A

Connector (group control adapter)

Wired remote control

R1T

Thermistor (air)

SS1

Selector switch (main/sub)

To outdoor

unit

Note) 4

In case of simultaneous

operation system.

To

outdoor

unit

Notes

1.

D

: Terminal,

F

: Connector,

: Field wiring

2. In case using central remote control, connect it to the

unit in accordance with the attached instruction

manual.

3. Remote control model varies according to the

combination system, confirm technical materials and

catalogs, etc. before connecting.

4. X24A is connected when the infrared remote control

kit is being used.

5.

Shows short circuit connector

6. Symbols show as follows Red:red, Blk:black, Ylw:yellow,

Org:orange, Gry:gray, Prp:purple, Blu:blue

7. Confirm the method of setting the selector switch (SS1,

SS2) by installation manual and engeneering materials,

etc.

Receiver / display unit (attached to infrared remote control)

Note) 4

Indoor unit

(master)

Indoor unit

(slave)

Remote control

Norm.

Emerg.

Note) 2

Transmission wiring

connection/central remote

control

Wired remote control

Control box

SIDE

FRONT

ON/OFF input from outside

3D044228

FAQ100BUV1B

A1P

Printed circuit board

A2P

Printed circuit board

(Transformer) 230V/16V)

C1R

Capacitor (M1F)

HAP

Light emitting diode (service monitor green)

KAR

Magnetic relay (M1S)

KPR

Magnetic relay (M1P)

M1F

Motor (indoor fan)

M1S

Motor (swing flap)

Q1M

Thermo switch (M1F embedded)

R1T

Thermistor (air)

R2T

Thermistor (coil)

S1Q

Limit switch (swing flap)

SS1

Selector switch (emergency)

V1TR

Phase control circuit

X1M

Terminal block

X2M

Terminal block

?

Signal receiver circuit

.

Signal transmission circuit

Wired remote control

R1T

Thermistor (air)

SS1

Selector switch (main/sub)

Infrared remote control

Receiver / display unit

A3P

Printed circuit board

A4P

Printed circuit board

BS1

Push button (on/off)

H1P

Light emitting diode (on-red)

H2P

Light emitting diode (timer-green)

H3P

Light emitting diode (filter sign-red)

H4P

Light emitting diode (defrost-orange)

SS1

Selector switch (main/sub)

SS2

Selector switch (wireless address set)

Connector for optional parts

X15A

Connector (float switch)

X25A

Connector (drain pump)

X35A

Connector (group control adapter)

X16A

X61A

Connector (interface adapter for sky air series)

To outdoor

unit

Note) 4

Wired remote

control

Control box

In case of simultaneous

operation system.

To

outdoor

unit

Notes

1.

D

: Terminal

F

,

: Connector

2.

: Field wiring

3. In case using central remote control, connect it to

the unit in accordance with the attached

instruction manual.

4. X24A is connected when the infrared remote

control kit is being used.

5. Remote control model varies according to the

combination system, confirm technical materials

and catalogs, etc. before connecting.

6. Symbols show as follows Red:red, Blk:black,

Ylw:yellow, Org:orange, Gry:gray, Prp:purple,

Blu:blue

7. Confirm the method of setting the selector

switch (SS1, SS2) by installation manual and

engeneering materials, etc.

8. x15A, x25A are connected when the drain up kit

is being used. Connect it to the kit in accordance

with the attached installation manual.

Receiver / display unit

Note) 4

Indoor unit

(master)

Indoor unit

(slave)

Infrared remote

control

Emerg.

Norm.

Note) 8

Wall Mounted, Inverter Controlled Unit

R-410A

FAQ71-100BUV1B

1

5

8

Split - Sky Air

Indoor Units

Summary of Contents for FAQ71BUV1B x 2

Page 1: ...FAQ BU Wall Mounted Unit technical data Split Sky Air air conditioning systems...

Page 2: ...vironment Daikin Europe N V is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard ISO9001 pertains to quality assurance regarding design development manufacturi...

Page 3: ...5 Wiring diagrams 8 6 Sound level 10 Sound level data Sound pressure spectrum 7 Air flow patterns 11 8 Accessories 15 Standard accessories Optional accessories 9 Control systems 16 10 Safety device s...

Page 4: ...RZQ B Daikin remote controls give you easy control at your fingertips The wired remote control provides you with a schedule timer enabling to program the air conditioning daily or weekly The optional...

Page 5: ...1B RQ100B7V3B RQ100B7W1B NOMINAL CAPACITY 3 Cooling 1 nominal kW 7 10 10 10 Heating 2 nominal kW 8 00 11 20 NOMINAL INPUT Cooling nominal kW 2 65 2 53 3 56 3 52 Heating nominal kW 2 58 2 49 3 96 3 82...

Page 6: ...19 Speed steps 2 steps Type Cross flow fan Qty x motor output W 1 x 43 1 x 49 HEAT EXCHANGER Type Cross fin coil Multi louver fins and Hi XA tubes Rows x stages x fin pitch mm 2 x 16 x 1 4 2 x 12 x 1...

Page 7: ...1 V1 NOMINAL DISTRIBUTION SYSTEM VOLTAGE Phase 1 1 Frequency Hz 50 50 Voltage V 220 240 220 240 4D043953 NOTES 1 Nominal cooling capacities are based on indoor temperature 27 CDB 19 5 CWB outdoor temp...

Page 8: ...n Required space unit mm 50 or more 250 or more Required space J80 hole approx 450 approx 600 FAQ100BUV1B 8 5x20 Oval hole for wood screw Mounting location Detail j A Mounting hole for installation pl...

Page 9: ...ed pipe Indoor heat exchanger Field piping J9 5 C1220T 0 4D037995A FAQ71 100BUV1B Field piping J15 9 C1220T 0 Refrigerant pipe connection port diameters Model A B FAQ71 100BUV1B J 9 5 J 15 9 To outdoo...

Page 10: ...t board Transformer 230V 16V C1R Capacitor M1F HAP Light emitting diode service monitor green KAR Magnetic relay M1S KPR Magnetic relay M1P M1F Motor indoor fan M1S Motor swing flap Q1M Thermo switch...

Page 11: ...tch for safety 6 All field wiring and components must be provided by a licensed electrician 7 The unit shall be grounded in compilance with the applicable local and national codes 8 Wiring shown are g...

Page 12: ...UV1B Cooling FAQ100BUV1B Heating Octave band sound pressure level Octave band sound pressure level 4D027787A 4D027790A Octave band center frequency Hz Octave band center frequency Hz approximate thres...

Page 13: ...air velocity distribution Air flow direction 10 downward FAQ71BUV1B Cooling air temperature distribution Air flow direction 10 downward 4D039573A Wall Mounted Inverter Controlled Unit R 410A FAQ71 100...

Page 14: ...ion Air flow direction 65 C downward FAQ71BUV1B Heating air temperature distribution Air flow direction 65 C downward 4D039574A Wall Mounted Inverter Controlled Unit R 410A FAQ71 100BUV1B 7 Air flow p...

Page 15: ...ution Air flow direction 10 downward FAQ100BUV1B Cooling air temperature distribution Air flow direction 10 downward 4D028547A Wall Mounted Inverter Controlled Unit R 410A FAQ71 100BUV1B 7 Air flow pa...

Page 16: ...ion Air flow direction 65 C downward FAQ100BUV1B Heating air temperature distribution Air flow direction 65 C downward 4D028548A Wall Mounted Inverter Controlled Unit R 410A FAQ71 100BUV1B 7 Air flow...

Page 17: ...W Wiring adapter for electrical appendices 2 KRP4A51 Installation box for adapter PCB KRP4A93 Central remote control DCS302C51 Electrical box with earth terminal 3 blocks KJB311A Unified ON OFF contro...

Page 18: ...emote control 6 5 x 9 Round end slit Cover open Cover closed 5 x 7 Round end slit HoleJ5 5 x 10 Round end slit 3TW23651 2 BRC1D527 Wall Mounted Inverter Controlled Unit R 410A FAQ71 100BUV1B 1 9 9 1 1...

Page 19: ...ndoor unit j b Outdoor unit j c Infrared remote control j d Inlet air j e Discharged air j f Air outlet j g Air flow flap at air outlet j h Refrigerant piping connection electric wire j i Drain pipe j...

Reviews: