D-EIMHP01505-22_00EN 19/59
▪
When the installation height of the unit needs to be increased, do NOT use stands to only
support the corners.
▪
Stands under the unit must be at least 100 mm wide.
There are two sides which can be mounted facing the wall. It is important to respect the minimum distances in any case.
The unit must be fixed to prevent it from tilting.
Observe the minimum installation space requirements.
Figure 10
– Indoor Unit minimum space requirements
The indoor unit and the equipment pipes shall be installed in such a way that it shall be protected against accidental
damage in the occupied space.
Fasten the unit in place using four foundation M8 bolts.
4.5. Additional installation site requirements
▪
When installing, take strong winds, typhoons or earthquakes into account, improper installation may result in the
unit turning over.
▪
Take care that in the event of a water leak, water cannot cause any damage to the installation space and
surroundings.
Unit mounting holes
ø10 mm