Cx Off EvapPress Sen
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.
6.1.7.10 Condensing Pressure sensor fault
This alarm indicates that the condensing pressure transducer is not operating properly.
Symptom
Cause
Solution
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+CxOff CndPressSen
String in the alarm log:
CxOff CndPressSen
String in the alarm snapshot:
Cx Off CondPress Sen
Sensor is broken.
Check for sensor integrity.
Check correct sensors operation
according information about mVolt
(mV) range related to pressure values
in kPa.
Sensor is shorted.
Check if sensor is shorted with a
resistance measurement.
Sensor is not properly connected
(open).
Check for correct installation of the
sensor on refrigerant circuit pipe. The
transducer must be able to sense the
pressure through the valve’s needle.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.