ESIE07-05
Functional Control
Part 2 – Functional Description
2–59
3
2
4
5
1
2.7
Enable Soft Load
Function
description
The Soft load function can be enabled by keyboard in the user menu. The Soft load function limits the
unit load to a predetermined value (Max stage) for a set period (Max time). This function finds wide
application where the water temperature is high at the start up but without having a consistent thermal
load. This function allows energy saving during unit start up avoiding compressors useless loading.
Y
Enable Soft Load
Max stage
Enable Soft Load
Max Time
50 %
20 min
Y