Daikin EWAQ004BAVP Installation Manual Download Page 17

7 Hand-over to the user

Installation manual

17

EWAQ+005BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P469106-1 – 2017.01

INFORMATION

▪ To  purge  air,  use  all  air  purge  valves  present  in  the

system. This includes the manual air purge valve of the
outdoor unit, as well as any field-supplied valves.

▪ If the system contains a backup heater, also use the air

purge valve of the backup heater.

▪ If  the  system  contains  valve  kit  EKMBHBP1,  it  is

required to – during the air purge – manually switch the
position  of  the  valve  kit's  3‑way  valve  by  turning  its
knob, this to prevent air from remaining in the bypass.
For  more  information,  refer  to  the  instruction  sheet  of
the valve kit.

6.2.2

To perform a test run

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page and room temperature home page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 11

.

2

Go  to  [A.7.1]: 

  >  Installer  settings  >  Commissioning  >  Test

run.

3

Select a test and press 

Example: 

Heating.

4

Select OK and press 

.

Result: 

The  test  run  starts.  It  stops  automatically  when  done

(±30 min). To stop it manually, press 

, select OK and press 

.

INFORMATION

When  starting  up  the  system  in  a  cold  climate,  and  NO
backup heater kit was installed, it may be required to start
up  with  a  small  water  volume.  To  do  this,  gradually  open
the  heat  emitters.  As  a  result,  the  water  temperature  will
gradually  rise.  Monitor  the  inlet  water  temperature  ([6.1.6]
in  the  menu  structure)  and  make  sure  it  does  NOT  drop
below 15°C.

INFORMATION

If  2  user  interfaces  are  present,  you  can  start  a  test  run
from both user interfaces.

▪ The user interface used to start the test run displays a

status screen.

▪ The other user interface displays a "busy" screen. You

cannot  use  the  user  interface  as  long  as  the  "busy"
screen is shown.

6.2.3

To perform an actuator test run

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page and room temperature home page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 11

.

2

Make  sure  room  temperature  control  and  leaving  water
temperature control are turned OFF via the user interface.

3

Go  to  [A.7.4]: 

  >  Installer  settings  >  Commissioning  >

Actuator test run.

4

Select an actuator and press 

Example: 

Pump.

5

Select OK and press 

.

Result: 

The  actuator  test  run  starts.  It  automatically  stops  when

finished. To stop it manually, press 

, select OK and press 

.

Possible actuator test runs

▪ Backup heater (step 1) test

▪ Backup heater (step 2) test

▪ Pump test

INFORMATION

Make  sure  that  all  air  is  purged  before  executing  the  test
run. Also avoid disturbances in the water circuit during the
test run.

▪ 2-way valve test

▪ Bivalent signal test

▪ Alarm output test

▪ Cooling/heating signal test

▪ Circulation pump test

6.2.4

To perform an underfloor heating screed
dryout

Prerequisite: 

Make sure there is ONLY 1 user interface connected

to your system to perform an underfloor heating screed dryout.

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page and room temperature home page are turned OFF.

1

Go  to  [A.7.2]: 

  >  Installer  settings  >  Commissioning  >  UFH

screed dryout.

2

Set a dryout program.

3

Select Start dryout and press 

.

4

Select OK and press 

.

Result: 

The  underfloor  heating  screed  dryout  starts.  It  stops

automatically  when  done.  To  stop  it  manually,  press 

,  select  OK

and press 

.

NOTICE

To perform an underfloor heating screed dryout, room frost
protection needs to be disabled ([2‑06]=0). By default, it is
enabled  ([2‑06]=1).  However,  due  to  the  "installer-on-site"
mode  (see  "Checklist  before  commissioning"),  room  frost
protection  will  be  automatically  disabled  for  12  hours  after
the first power-on.

If  the  screed  dryout  still  needs  to  be  performed  after  the
first  12  hours  of  power-on,  manually  disable  room  frost
protection  by  setting  [2‑06]  to  "0",  and  KEEP  it  disabled
until the screed dryout has finished. Ignoring this notice will
result in cracking of the screed.

NOTICE

For the underfloor heating screed dryout to be able to start,
make sure the following settings are met:

▪ [4‑00]=1

▪ [C‑02]=0

▪ [D‑01]=0

▪ [4‑08]=0

▪ [4‑01]≠1

7

Hand-over to the user

Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:

▪ Fill in the installer setting table (in the operation manual) with the

actual settings.

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do in relation to maintaining the unit.

Summary of Contents for EWAQ004BAVP

Page 1: ... Packaged air cooled water chillers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAQ004BAVP EWAQ005BAVP EWYQ004BAVP EWYQ005BAVP ...

Page 2: ...ormatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un c...

Page 3: ...ser 17 7 1 About locking and unlocking 18 To activate or deactivate a function lock 18 To activate or deactivate button lock 18 8 Technical data 19 8 1 Piping diagram Outdoor unit 19 8 2 Wiring diagram Outdoor unit 20 1 About the documentation 1 1 About this document Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light...

Page 4: ...r unit Mind the following spacing guidelines 1200 250 400 250 400 250 350 350 mm mm a b b a a Air outlet b Air inlet INFORMATION If shut off valves are installed on the unit provide a minimum space of 400 mm at the air inlet side If shut off valves are NOT installed on the unit provide a minimum space of 250 mm Do NOT install the unit in sound sensitive areas e g near a bedroom so that the operati...

Page 5: ...er interface 2 b Optional equipment 4 Remote outdoor sensor 2 c Field supplied components 5 Space heating cooling operation control or shut off valve 2 e Interconnection cable 6 Interconnection cable between outdoor unit and control box 2 d a Refer to name plate on outdoor unit b Cable section 0 75 mm till 1 25 mm maximum length 500 m Applicable for both single user interface and dual user interfa...

Page 6: ...In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to install the unit on brackets to the wall 250 400 300 250 400 mm a a Maximum snowfall height 4 2 2 To install the outdoor unit CAUTION Do NOT rem...

Page 7: ... in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuated condensate cannot freeze INFORMATION For information on the available options contact your dealer NOTICE Provide at least 300 mm of free space below the unit Additionally make ...

Page 8: ...expected outdoor temperature Prevent from bursting Prevent from freezing 20 C 25 25 C 30 NOTICE The addition of glycol applies to BOTH cooling only models EWAQ004 005BAVP AND reversible models EWYQ004 005BAVP and is independent of cooling or heating operation ALWAYS add glycol if negative outdoor temperatures are expected The required concentration might differ depending on the type of glycol ALWA...

Page 9: ...e 16 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8 Close the drain and fill valve 9 Disconnect the water supply hose from the drain and fill valve 4 3 4 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and reduction o...

Page 10: ...tdoor unit If control box EKCB07CAV3 is part of the system you can also connect the user interface to the control box To do this connect the user interface to control box terminals X2M 20 21 and then connect the control box to the outdoor unit by connecting X2M 20 21 to outdoor unit terminals X5M 1 2 INFORMATION For details on how to connect the user interface to the control box refer to the insta...

Page 11: ...ences the following The calculations of the software What you can see on and do with the user interface How You can configure the system via the user interface First time Quick wizard When you turn ON the user interface for the first time via the indoor unit a quick wizard starts to help you configure the system Afterwards If necessary you can make changes to the configuration afterwards INFORMATI...

Page 12: ...button 01 02 06 0a 0e 00 03 07 0b 0f 00 00 04 08 0c 00 01 05 09 0d 20 Overview settings Confirm Adjust Scroll 5 Repeat previous steps if you have to modify other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 2 Basic configura...

Page 13: ...can send a separate heating cooling thermo ON OFF condition Option box EK2CB07CAV3 Code Description A 2 2 F 1 C 02 External backup heater source 0 No None 1 Bivalent Gas boiler oil boiler 2 N A 3 N A Code Description A 2 2 F 2 C 09 Alarm output 0 Normally open The alarm output will be powered when an alarm occurs 1 Normally closed The alarm output will NOT be powered when an alarm occurs This inst...

Page 14: ...cording to the difference between desired and actual room temperature This allows better matching of the heat pump capacity to actual required capacity and results in less start stop cycles of the heat pump and more economic operation N A 8 06 Leaving water temperature maximum modulation 0 C 10 C default 3 C Requires modulation to be enabled This is the value by which the desired leaving water tem...

Page 15: ...ype Indoor software type Unit control method Pump operation mode Power saving possible User interface location Options External sensor Control box Option box Leaving water Main Delta T source Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Space cooling On temp Backup heater Operation mode Enable BUH step 2 Equilibrium temp Prefer kWh ...

Page 16: ...e pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 4 If glycol was added to the system confirm the correct glycol concentration and check if glycol setting E 0D 1 NOTICE Make sure glycol setting E 0D matches the liquid inside the water circuit 0 water only 1 water glycol If th...

Page 17: ...settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually press select OK and press Possible actuator test runs Backup heater step 1 test Backup heater step 2 test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoi...

Page 18: ...ser to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific function to prevent people from changing its settings Button lock Locks all buttons to prevent users from changing settings To activate or deactivate a function lock 1 Press to go to the menu structure 2 ...

Page 19: ...9 CuT 7 9 CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrigerant flow Cooling Heating Liquid stop valveV Plate heat exchanger Gas stop valve with service port Air purge Flow sensor Pump Flow switch Outlet Shut off valve with drain fill valve E...

Page 20: ...tor W Connector X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blue BRN Brown GRN Green ORG Orange PPL Purple RED Red WHT White YLW Yellow Outdoor unit hydro module English Translation 1 Connection diagram 1 Connection diagram Compress...

Page 21: ... contact X M K1 Terminal strip X Y Connector K1A Relay for heating K2A Relay for cooling Optional Field supply Control box option backup heater English Translation 1 Connection diagram 1 Connection diagram BUH option Backup heater option Control box Control box Only for Only for 2 Notes 2 Notes Earth wiring 15 Wire number 15 Field supply 1 Several wiring possibilities Option Wiring depending on mo...

Page 22: ...30V 230V 230V Control box External room thermostat main zone signal signal signal 2 or 3 core 2 core 2 core Power limitation demand input 4 Power limitation demand input 3 Power limitation demand input 2 Power limitation demand input 1 Only for normal power supply installation Only for preferential kWh rate power supply installation normal kWh rate power supply for unit 230 V or L N earth Backup h...

Page 23: ......

Page 24: ...4P469106 1 2017 01 Copyright 2017 Daikin ...

Reviews: