EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-
- R410A - Air-cooled scroll chillers
EWAQ-
- R410A - Air-cooled scroll chillers
EWYQ-
- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
61
3. Double Chiller Pump
In the plant type Double Chiller Pump, every pair of pump have to be connected to the related
chiller. The enabling contact are available in the customer terminal block (Evaporator Pump#1 start
/ Evaporator Pump#2 start). Refer to the table 1.7 for the enumeration of the terminals.
4. Chiller with sectioned evaporator
In the plant where the evaporator is sectioned by a two way valve, connect the valve to the pump
enable provided by the chiller and the pump to the total opening feedback of the valve. The
enabling contact is available in the customer terminal block (Evaporator Pump#1 start). Refer to
the table 1.7 for the enumeration of the terminals.
5.10.3 Master Slave Operation
5.10.3.1 Master Slave configuration
The basic configuration of the Master Slave function requires the set of three parameters available
in the unit configuration menu 4.9.1:
Setpoint/Sub-
Menu
Default
Range
Description
M/S Address
Standalone
Standalone
Master
Slave 1
Slave 2
Slave 3
Define if the chiller works as standalone or if belongs to Master Slave
network.
Standalone: Current unit does not belong to the Master Slave network
Master: Current unit is defined Master
Slave 1: Current unit is defined Slave 1
Slave 2: Current unit is defined Slave 2. This address can be assigned only
if the parameter
M/S Num Of Unit
= 3 or 4
Slave 3: Current unit is defined Slave 3. This address can be assigned only
if the parameter
M/S Num Of Unit
= 4
Example:
If in a network there are 3 chillers then them have to be addressed like :
Ev. Pump #1
MASTER
PUMP
Ev. Pump #1
SLAVE 1
PUMP
Ev. Pump #1
SLAVE 2
PUMP
Ev. Pump #1
SLAVE 3
PUMP
Ev. Pump #1 Ev. Pump #2
MASTER
PUMP 2
PUMP 1
Ev. Pump #1 Ev. Pump #2
SLAVE 1
PUMP 2
PUMP 1
Ev. Pump #1 Ev. Pump #2
SLAVE 2
PUMP 2
PUMP 1
Ev. Pump #1 Ev. Pump #2
SLAVE 3
PUMP 2
PUMP 1
Ev. Pump #1
MASTER
PUMP
VALVE
Ev. Pump #1
SLAVE 1
PUMP
VALVE
Ev. Pump #1
SLAVE 2
PUMP
VALVE
Ev. Pump #1
SLAVE 3
PUMP
VALVE