background image

8 Configuration

Installation manual

28

EWAA011~016DA + EWYA009~016DA

Packaged air-cooled water chillers

and packaged air to water heat pumps

4P620240-1 – 2020.06

Emitter type

Heating  up  or  cooling  down  the  main  zone  can  take  longer.  This
depends on:

▪ The water volume of the system

▪ The heater emitter type of the main zone

The  setting 

Emitter  type

  can  compensate  for  a  slow  or  a  quick

heating/cooling system during the heat up/cool down cycle. In room
thermostat  control, 

Emitter 

type

  influences  the  maximum

modulation  of  the  desired  leaving  water  temperature,  and  the
possibility  for  usage  of  the  automatic  cooling/heating  changeover
based on the indoor ambient temperature.

It is important to set 

Emitter type

 correctly and in accordance with

your system layout. The target delta T for the main zone depends on
it.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 60°C

Fixed 8°C

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–8/2=

36°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. fan coil units).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

8.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"8.2.5  Configuration

wizard: Main zone" 

[

4

 27].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"8.2.5 Configuration wizard: Main zone" 

[

4

 27].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"8.2.5  Configuration

wizard: Main zone" 

[

4

 27].

Summary of Contents for EWAA Series

Page 1: ...t pumps English https daikintechnicaldatahub eu Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA011 016DAV3P EWAA011 016DAW1P EWAA011 016DAV3P H EWAA011...

Page 2: ...n side No top side obstacle Suction side obstacle No top side obstacle Discharge side obstacle No top side obstacle Suction discharge side obstacle Top side obstacle Suction discharge side obstacle Wa...

Page 3: ...ngen van siguiendo las disposiciones de secondo le prescrizioni per de acordo com o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til b...

Page 4: ...staava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 5: ...n wizard Language 26 8 2 2 Configuration wizard Time and date 26 8 2 3 Configuration wizard System 26 8 2 4 Configuration wizard Backup heater 27 8 2 5 Configuration wizard Main zone 27 8 2 6 Configur...

Page 6: ...lated room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater WARNING Make sure installation servicing maintenance and repai...

Page 7: ...MUST be in accordance with the instructions from this manual See 9 Commissioning 433 3 About the box 3 1 Outdoor unit 3 1 1 To remove the accessories from the outdoor unit NOTICE Unpacking Top packagi...

Page 8: ...cturer Be aware that R32 refrigerant does NOT contain an odour WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ign...

Page 9: ...414 349 214 111 480 490 107 148 B B B 406 C D F E A Discharge side B Distance between anchor points C Bottom frame D Knockout hole for snow E Drain hole for safety valve F Drain holes Snow In regions...

Page 10: ...ume Check that the total water volume in the installation is higher than the minimum water volume the internal water volume of the outdoor unit NOT included If Then the minimum water volume is Cooling...

Page 11: ...n This shut off valve and drain point are field supplied NOTICE Install air purge valves at all local high points 5 2 2 To fill the water circuit To fill the water circuit use a field supply filling k...

Page 12: ...eezing the glycol will prevent the liquid inside the piping from freezing NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table...

Page 13: ...X5M 0 88 10 X9M 2 45 10 X10M 0 88 10 6 3 Connections to the outdoor unit Item Description Power supply main See 6 3 2 To connect the main power supply 414 User interface See 6 3 3 To connect the user...

Page 14: ...er See 4 3 1 To open the outdoor unit 49 2 Insert the cables at the back of the unit and route them through the unit to the appropriate terminal blocks b c a d a High voltage options b Low voltage opt...

Page 15: ...r See 4 3 1 To open the outdoor unit 49 2 Connect the preferential kWh rate power supply 1N or 3N depending on model see name plate N L N PE Q1DI X1M L X1M L1 X1M L2 X1M L3 X1M N X1M N X1M X1M L3 L2 L...

Page 16: ...25 mm Maximum length 200 m 2 9 Control 1 6 Room sensor offset 1 Open the service cover See 4 3 1 To open the outdoor unit 49 2 Connect the user interface cable to the outdoor unit Fix the cable with...

Page 17: ...t is installed proceed as follows 1 Remove the WLAN cartridge and USB memory stick if any 2 Push the rear plate on each of the 4 spots where the snap fits are located 6 3 4 To connect the shut off val...

Page 18: ...or unit 49 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A...

Page 19: ...s to the cable tie mountings 6 3 9 To connect the power consumption digital inputs Wires 2 per input signal 0 75 mm Power limitation digital inputs 12 V DC 12 mA detection voltage supplied by PCB 9 9...

Page 20: ...8 8 Limit setting kw The wiring of the Smart Grid in case of low voltage contacts is as follows 14 13 S11S 6 5 S4S 4 3 X5M S10S 10 9 a a Jumper factory mounted If you also connect a safety thermostat...

Page 21: ...l backup heater kit For reversible models you can install the external backup heater kit EKLBUHCB6W1 If you do so then under certain conditions you also need to install a bypass valve kit EKMBHBP1 See...

Page 22: ...l Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 1 Connect the backup heater power supply A...

Page 23: ...X15M F1B LV HV 2 On the outdoor unit connect the HV cable to the appropriate terminals as shown in the illustration below 6 7 8 9 10 X15M X3M 1 X3M 2 X3M 3 X3M 4 X3M 5 EKLBUHCB6W HV 1 2 3 4 5 X3M 3 On...

Page 24: ...h cable ties to the cable tie mountings 7 Finishing the outdoor unit installation 7 1 To check the insulation resistance of the compressor NOTICE If after installation refrigerant accumulates in the c...

Page 25: ...ton in the home screen For example 2 9 Accessing settings via the code in the overview field settings Code For example C 07 See also To access the installer settings 425 8 5 Menu structure Overview in...

Page 26: ...cy is set to Automatic and a heat pump failure occurs the backup heater automatically takes over the heat load When Emergency is set to Manual and a heat pump failure occurs the space heating stops To...

Page 27: ...ll a flow switch EKFLSW1 8 2 4 Configuration wizard Backup heater INFORMATION Restriction Backup heater settings are only applicable in case the optional external backup heater kit is installed The ba...

Page 28: ...nt e g fan coil units Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Code Description 2 9 C 07 0 L...

Page 29: ...offset curve Which type of curve you use to make adjustments depends on your personal preference See 8 3 4 Using weather dependent curves 430 Availability The weather dependent curve is available for...

Page 30: ...oint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent To change the type of weather dependent curve To change the type for...

Page 31: ...type for the main zone 1 1 contact The used external room thermostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external ro...

Page 32: ...s 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installer settings Configuration wizard Backup...

Page 33: ...to the wiring diagrams and according to the applicable legislation The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed...

Page 34: ...est run starts It stops automatically when ready 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test Backup h...

Page 35: ...water chillers and packaged air to water heat pumps 4P620240 1 2020 06 Explain the user how to properly operate the system and what to do in case of problems Show the user what to do for the maintena...

Page 36: ...Low pressure switch b Water OUT screw connection male 1 S1NPH Pressure sensor c Drain valve water circuit Y1E Electronic expansion valve main d Plate heat exchanger Y3E Electronic expansion valve inje...

Page 37: ...for normal power supply standard Only for preferential kWh rate power supply outdoor Only for preferential kWh rate power supply outdoor Outdoor Outdoor SWB1 Hydro switch box 1 front side SWB2 Hydro s...

Page 38: ...voltage supplied by PCB Space C H On OFF output Space cooling heating ON OFF output SWB Hydro switch box 1 front side 6 Options 6 Options English Translation Continuous Continuous current DHW pump out...

Page 39: ...2 core signal 2 core signal 2 core signal 2 core Flow switch signal 2 core 2 core 2 core 5 core R2T External sensor floor or ambient Only for KRTETS WLAN cartridge signal 2 core 3m included A14P P1 P2...

Page 40: ...4P620240 1 2020 06 Copyright 2020 Daikin 4P620240 1 0000000C Verantwortung f r Energie und Umwelt...

Reviews: