10
|
Configuration
Installer reference guide
196
EPRA14~W1 + ET9W
Daikin Altherma 3 H HT F
4P644739-1 – 2021.02
-14
0
1
2
3
4
5
6
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
COP
10.5 (b)
2.5 (a)
a
[C‑03]=2.5 in case of COP=3 and LWT=35°C
b
[C‑03]=10.5 in case of COP=3 and LWT=55°C
NOTICE
Make sure to set the value of [5‑01] at least 1°C higher than the value of [C‑03].
Electricity and gas prices
INFORMATION
To set electricity and gas price values, do NOT use overview settings. Set them in the
menu structure instead ([7.5.1], [7.5.2], [7.5.3], and [7.6]). For more information on
how to set the energy prices, see the operation manual and the user reference
guide.
INFORMATION
Solar panels.
If solar panels are used, set the electricity price value very low to
promote the use of the heat pump.
#
Code
Description
[7.5.1]
N/A
User settings
>
Electricity price
>
High
[7.5.2]
N/A
User settings
>
Electricity price
>
Medium
[7.5.3]
N/A
User settings
>
Electricity price
>
Low
[7.6]
N/A
User settings
>
Gas price
Boiler efficiency
Depending on the used boiler, this should be chosen as follows:
#
Code
Description
[9.C.2]
[7‑05]
▪
0:
Very high
▪
1:
High
▪
2:
Medium
▪
3:
Low
▪
4:
Very low